1SDA062943R1 ABB T7L 1250 PR332/P LSIG 1250 A 4-Pole MCCB

1SDA062943R1 ABB T7L 1250 PR332/P LSIG 1250 A 4-Pole MCCB

ABB 1SDA062943R1 is a SACE Tmax T7L 1250 A four-pole fixed moulded case circuit breaker with front terminals, lever operation and a PR332/P LSIG electronic trip unit providing overload, short-circuit and earth-fault protection.

SKU: 1SDA062943R1MPN: 1SDA062943R1
Price
List Price £15,541.25 ex VAT
Your Price (ex VAT) Save 25%
£11,655.94 25% OFF
You save £3,885.31 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,655.94
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,655.94

Why Choose the ABB T7L 1250 PR332/P LSIG 1SDA062943R1 Circuit Breaker?

The ABB 1SDA062943R1 is a high-performance SACE Tmax T7L 1250 moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. This configuration combines a 1250 A rated current, four-pole construction and the advanced ABB PR332/P LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.

As part of the ABB SACE Tmax T7 series, the T7L 1250 is engineered for high-current industrial and commercial installations requiring substantial fault-interruption capability. The L performance level provides high breaking capacity while the four-pole configuration enables protection and switching of three-phase systems incorporating a neutral conductor.

The 1SDA062943R1 is supplied as a four-pole fixed circuit breaker with front terminals and a lever operating mechanism. Its PR332/P LSIG solid-state release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection, supporting selective and coordinated protection throughout complex distribution networks.

Key Advantages

  • High-performance ABB SACE Tmax T7L moulded case circuit breaker.
  • 1250 A rated current for high-current power distribution.
  • Four-pole construction for three-phase systems incorporating a neutral conductor.
  • PR332/P LSIG electronic trip unit for comprehensive circuit protection.
  • Integrated long-time, short-time, instantaneous and earth-fault protection functions.
  • 500–1250 A adjustable overload protection range.
  • Fixed configuration with front terminals and lever operation.

Key Features

  • ABB SACE Tmax T7L 1250 series.
  • 1250 A rated uninterrupted current (Iu).
  • Four-pole (4P) construction.
  • PR332/P LSIG solid-state electronic release.
  • L: long-time overload protection.
  • S: short-time delayed short-circuit protection.
  • I: instantaneous short-circuit protection.
  • G: earth-fault protection.
  • 500–1250 A overload adjustment range.
  • 750–12500 A short-time delayed short-circuit adjustment range.
  • 1875–18750 A instantaneous short-circuit adjustment range.
  • Rated operational voltage of 690 V AC.
  • IP20 degree of protection.

Advanced LSIG Protection for 1250 A Distribution Systems

The ABB SACE Tmax T7 platform is designed for high-current low-voltage installations where reliable fault interruption and coordinated protection are essential. The T7L 1250 combines a 1250 A current rating with the high-breaking-capacity L performance level, making it suitable for main distribution, feeder and installation protection in demanding electrical systems.

The PR332/P LSIG electronic trip unit combines adjustable long-time overload, short-time delayed and instantaneous short-circuit protection with an integrated earth-fault protection function. Its overload range of 500–1250 A, short-time range of 750–12500 A and instantaneous range of 1875–18750 A provide substantial flexibility when coordinating protection across high-current distribution networks.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Four-pole main incomer and feeder protection.
  • High-current electrical switchboards.
  • Transformer, generator and installation protection.
  • Manufacturing and process-industry electrical systems.
  • Distribution systems requiring integrated earth-fault protection.
  • Fixed switchgear requiring configurable electronic LSIG protection.

Technical Specifications

Series SACE Tmax T7
ABB designation T7L 1250 PR332/P LSIG In=1250A 4p F F
Order code 1SDA062943R1
GTIN / EAN 8015644654924
Product type Moulded case circuit breaker (MCCB)
Frame T7
Performance level L
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Number of poles 4
Trip unit PR332/P LSIG
Trip-unit technology Solid-state electronic / microprocessor
Protection functions Long-time, short-time, instantaneous and earth fault
Overload protection adjustment 500–1250 A
Short-time delayed short-circuit adjustment 750–12500 A
Instantaneous short-circuit adjustment 1875–18750 A
Rated operational voltage 690 V AC
Installation Fixed
Terminal position Front
Main-circuit connection Bolted connection
Operating mechanism Lever
Motor operator Optional
Integrated motor operator No
Degree of protection IP20
Power loss 47 W
Net weight 12.5 kg
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062943R1?

The ABB 1SDA062943R1 is a SACE Tmax T7L 1250 four-pole fixed moulded case circuit breaker rated at 1250 A, with front terminals, lever operation and a PR332/P LSIG electronic trip unit.

What protection functions does the PR332/P LSIG trip unit provide?

The PR332/P LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the overload adjustment range of the ABB 1SDA062943R1?

The overload protection setting is adjustable from 500–1250 A, allowing the long-time protection characteristic to be matched to the requirements of the protected circuit.

What are the short-circuit protection ranges of the ABB 1SDA062943R1?

The short-time delayed short-circuit protection is adjustable from 750–12500 A, while the instantaneous short-circuit protection range is 1875–18750 A.

Is the ABB 1SDA062943R1 a four-pole fixed circuit breaker?

Yes. The 1SDA062943R1 is a four-pole fixed Tmax T7L circuit breaker with front terminals and lever operation, making it suitable for three-phase distribution systems incorporating a neutral conductor.

Trusted ABB Power Distribution Protection

ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, advanced electronic protection and robust fault-interruption performance for dependable protection and coordination in demanding industrial and commercial low-voltage distribution systems.