1SDA062933R1 ABB T7L 1250 PR332/P LI 1250 A 3-Pole Moulded Case Circuit Breaker

1SDA062933R1 ABB T7L 1250 PR332/P LI 1250 A 3-Pole Moulded Case Circuit Breaker

ABB T7L 1250 PR332/P LI 3-pole moulded case circuit breaker with a 1250 A rated current, fixed front-terminal configuration, electronic LI protection and 120 kA breaking capacity at 415 V AC.

SKU: 1SDA062933R1MPN: 1SDA062933R1
Price
List Price £10,999.11 ex VAT
Your Price (ex VAT) Save 25%
£8,249.33 25% OFF
You save £2,749.78 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,249.33
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,249.33

Why Choose the ABB T7L 1250 PR332/P LI Moulded Case Circuit Breaker?

The ABB T7L 1250 PR332/P LI is a high-performance 3-pole moulded case circuit breaker (MCCB) designed for protection and control of high-current low-voltage power distribution systems. As part of the proven ABB Tmax T7 series, it combines a 1250 A rated uninterrupted current with electronic protection and high short-circuit breaking capability for demanding industrial and commercial installations.

Equipped with the PR332/P LI solid-state electronic trip unit, the T7L 1250 provides long-time overload and instantaneous short-circuit protection. Its adjustable protection settings allow the breaker to be coordinated with cables, switchgear and downstream equipment, helping provide dependable protection across high-current distribution networks.

With an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, a 3-pole configuration and fixed mounting with front terminals, the T7L 1250 is engineered for main distribution, feeder and switchboard applications where reliable interruption of substantial prospective fault currents is required.

Key Advantages

  • High-performance ABB Tmax T7 moulded case circuit breaker.
  • 1250 A rated uninterrupted current for high-current distribution circuits.
  • 120 kA Icu at 415 V AC for demanding fault conditions.
  • PR332/P LI electronic trip unit for long-time and instantaneous protection.
  • 500–1250 A adjustable overload release range for protection coordination.
  • 3-pole configuration for three-phase low-voltage distribution systems.
  • Fixed mounting with front terminals for straightforward switchboard integration.

Key Features

  • ABB Tmax T7 series.
  • T7L 1250 performance level.
  • 1250 A rated uninterrupted current.
  • 3-pole construction.
  • PR332/P LI solid-state electronic release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 500–1250 A overload release adjustment range.
  • 1875–18750 A instantaneous short-circuit adjustment range.
  • 120 kA ultimate short-circuit breaking capacity at 415 V AC.
  • 690 V AC rated voltage.
  • Fixed mounting with front terminals.
  • Lever operating mechanism.
  • IP20 protection rating.

Reliable Circuit Protection for Power Distribution

Moulded case circuit breakers such as the ABB Tmax T7 protect low-voltage electrical distribution circuits against overload and short-circuit conditions. The electronic trip unit monitors circuit current and initiates interruption when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected electrical equipment.

The T7L 1250 combines a high 1250 A current rating with 120 kA breaking capability at 415 V AC and adjustable PR332/P LI protection. This combination makes it well suited to high-capacity three-phase distribution systems requiring coordinated overload protection and rapid interruption of severe short-circuit faults.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incomer and feeder circuit protection.
  • High-current three-phase power distribution systems.
  • Commercial building electrical distribution.
  • Manufacturing and process-industry electrical systems.
  • Power distribution centres and switchgear assemblies.
  • High-fault-level low-voltage electrical networks.

Technical Specifications

Series Tmax T7
ABB order code 1SDA062933R1
Product type Moulded case circuit breaker
Rated uninterrupted current (Iu) 1250 A
Rated voltage 690 V AC
Number of poles 3
Trip unit PR332/P
Protection functions LI
Ultimate short-circuit breaking capacity (Icu) 120 kA at 415 V AC
Overload release adjustment range 500–1250 A
Instantaneous short-circuit adjustment range 1875–18750 A
Mounting type Fixed
Terminal configuration Front terminals
Main circuit connection Bolted connection
Operating mechanism Lever
Protection rating IP20
Weight approx. 11.2 kg
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB T7L 1250 PR332/P LI used for?

This moulded case circuit breaker is designed to protect high-current low-voltage distribution circuits against overload and short-circuit conditions in industrial and commercial electrical systems.

What is the rated current of ABB order code 1SDA062933R1?

The ABB T7L 1250 1SDA062933R1 has a rated uninterrupted current of 1250 A, with an adjustable overload release range of 500–1250 A.

What is the breaking capacity of the ABB T7L 1250 1SDA062933R1?

The breaker has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.

Which trip unit is fitted to the ABB T7L 1250 1SDA062933R1?

This model is equipped with the ABB PR332/P LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection.

How many poles does the ABB T7L 1250 1SDA062933R1 have?

This version has a 3-pole configuration for use in three-phase low-voltage electrical distribution systems.

Is the ABB 1SDA062933R1 fixed or withdrawable?

ABB order code 1SDA062933R1 is a fixed-mounted circuit breaker with front terminals and a lever operating mechanism.