ABB 1SDA062932R1 T7L 1250 is a 1250 A three-pole fixed moulded case circuit breaker with a PR331/P-LSIG electronic trip unit and 120 kA breaking capacity at 380–415 V AC for comprehensive low-voltage power distribution protection.
£9,172.95
The ABB 1SDA062932R1, extended product type T7L 1250 PR331/P LSIG In=1250A 3p F F, is a high-performance moulded case circuit breaker (MCCB) designed for protection and switching in high-current low-voltage electrical distribution systems. As part of the established ABB SACE Tmax T7 series, it combines a 1250 A rated current with an advanced PR331/P-LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.
This T7L configuration is a fixed three-pole circuit breaker with front terminals, making it suitable for demanding industrial switchboards and power distribution assemblies. The PR331/P-LSIG solid-state release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and ground-fault protection, enabling protection characteristics to be configured for effective coordination within the electrical installation.
With a rated uninterrupted current of 1250 A and a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, the T7L 1250 is engineered for installations with high prospective fault currents. Its robust Tmax construction, electronic protection and fixed front-terminal arrangement make it well suited to industrial plants, infrastructure and large low-voltage power distribution systems.
Moulded case circuit breakers such as the ABB Tmax T7L protect low-voltage electrical distribution systems against excessive currents caused by overloads and short circuits. The PR331/P-LSIG trip unit adds ground-fault protection, helping provide a comprehensive protection solution for cables, switchgear and connected electrical equipment in demanding distribution networks.
The electronic LSIG protection functions allow the breaker characteristics to be coordinated with other protection devices throughout the electrical system. Combined with the high breaking capacity of the T7L platform, the 1SDA062932R1 provides a robust solution for industrial power systems requiring configurable protection, high fault-current interruption capability and dependable operation.
| Series | SACE Tmax T7 |
|---|---|
| ABB product group | 310511-T-Max T4 - T8 |
| Order code | 1SDA062932R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Breaker type | T7L 1250 |
| Rated current | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Trip unit | PR331/P-LSIG electronic release |
| Protection functions | Long-time, short-time, instantaneous and ground-fault protection |
| Overload protection adjustment | 0.4–1 × In |
| Instantaneous protection adjustment | 1.5–15 × In |
| Ground-fault protection adjustment | 0.2–1 × In |
| Rated operational voltage | up to 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 8 kV |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Installation version | Fixed |
| Terminal type | Front terminals |
| Operating mechanism | Manual |
| Dimensions (H × W × D) | approx. 268 × 210 × 154 mm |
| Weight | approx. 9.7 kg |
The ABB 1SDA062932R1 is a 1250 A moulded case circuit breaker used for switching and protection of high-current low-voltage electrical distribution circuits against overloads, short circuits and ground faults.
The circuit breaker has a rated uninterrupted current of 1250 A, with adjustable long-time overload protection from 0.4–1 × In.
The T7L configuration provides a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it suitable for electrical systems with high prospective fault currents.
The breaker is fitted with an ABB PR331/P-LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground-fault protection functions.
This model is a fixed three-pole circuit breaker with front terminals, designed for installation in low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax moulded case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems where dependable circuit protection, high breaking capacity and configurable electronic protection are required.