ABB Tmax T7H 1250 four pole moulded case circuit breaker with PR332/P LSIG electronic release, 1250 A rating and 690 V AC operating voltage.
£9,327.56
The ABB 1SDA062911R1 is a premium Tmax T7H moulded case circuit breaker (MCCB) designed to deliver dependable protection for industrial power distribution systems, commercial installations and critical low voltage applications. As part of the proven ABB SACE Tmax T series, it combines high fault interruption capability with advanced electronic protection and outstanding operational reliability.
This breaker is supplied as a fixed four-pole MCCB with front terminals, a lever operating mechanism and an advanced PR332/P LSIG electronic trip unit. The LSIG protection functions provide adjustable long-time, short-time, instantaneous and ground fault protection, allowing excellent discrimination and enhanced protection for complex electrical installations.
With a rated current of 1250 A and a rated operational voltage of up to 690 V AC, the ABB 1SDA062911R1 is ideal for switchboards, transformer protection, generator applications, industrial feeders and major commercial power distribution systems where maximum reliability is essential.
The ABB Tmax T7H range provides advanced overload, short-circuit and ground fault protection for modern electrical installations. The PR332/P LSIG trip unit allows engineers to configure protection parameters for optimum selectivity while helping minimise unnecessary downtime.
Its robust construction, excellent fault interruption capability and four-pole design make the ABB 1SDA062911R1 an ideal solution for demanding industrial applications requiring dependable protection and complete circuit isolation.
Tick the specs you need, then view products that match.
| Current | 1250 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 70 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T7H 1250 PR332/P LSIG In=1250A 4p F F | |
| Product code | 1SDA062911R1 | |
| EAN | 8015644654603 | |
| Product type | Moulded Case Circuit Breaker | |
| Rated current | 1250 A | |
| Rated uninterrupted current | 1250 A | |
| Number of poles | 4P | |
| Release | PR332/P LSIG | |
| Release type | Electronic | |
| Rated operational voltage | 690 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Rated ultimate breaking capacity (Icu) | 70 kA at 415 V AC | |
| Rated service breaking capacity (Ics) | 70 kA at 415 V AC | |
| Rated short-time withstand current (Icw) | 20 kA for 1 second | |
| Terminal connection | Fixed front terminals | |
| Operating mechanism | Lever operated | |
| Electrical durability | 2000 cycles | |
| Mechanical durability | 10000 cycles | |
| Power loss | 47 W per pole | |
| Standards | IEC | |
| Dimensions (H × W × D) | 268 × 280 × 154 mm | |
| Weight | 12.5 kg |
It protects industrial and commercial electrical distribution systems against overloads, short circuits and ground faults.
The ABB 1SDA062911R1 has a rated current of 1250 A.
This model is equipped with the PR332/P LSIG electronic trip unit, providing adjustable long-time, short-time, instantaneous and ground fault protection.
The ABB 1SDA062911R1 is supplied as a four-pole MCCB for complete three-phase and neutral isolation.
It is commonly used in industrial switchboards, commercial electrical distribution systems, transformer protection and generator installations.
ABB Tmax circuit breakers are trusted worldwide by panel builders, OEMs and electrical engineers for delivering dependable protection, outstanding breaking performance and reliable operation in demanding industrial environments.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.