1sda062899r1  t7h 1250 pr232/p lsi in=1250a 3 pole abb mccb

1sda062899r1 t7h 1250 pr232/p lsi in=1250a 3 pole abb mccb

ABB 1SDA062899R1 Tmax T7H 1250 moulded case circuit breaker with PR231/P-LSIG electronic release, 1250 A rated current, three poles, fixed front terminals and rated operational voltage up to 690 V AC.

SKU: 1SDA062899R1Alt SKU: T7H 1250 PR232/P LSI In=1250A 3p F FMPN: 1SDA062899R1
Price
List Price £9,464.30 ex VAT
Your Price (ex VAT) Save 25%
£7,098.23 25% OFF
You save £2,366.08 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,098.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,098.23

Why Choose the ABB 1SDA062899R1 Tmax T7H Moulded Case Circuit Breaker?

The ABB 1SDA062899R1 is a high-capacity Tmax T7H moulded case circuit breaker (MCCB) designed for reliable protection in demanding industrial power distribution, commercial electrical installations and low voltage networks. As part of the ABB SACE Tmax T series, it provides robust switching performance, dependable fault protection and long-term reliability for critical electrical systems.

This breaker is supplied as a fixed three-pole MCCB with front terminals, a lever operating mechanism and a PR231/P-LSIG electronic release. The LSIG protection functions provide long-time, short-time, instantaneous and ground fault protection, making the unit suitable for installations requiring accurate fault detection, selectivity and enhanced electrical safety.

With a rated current of 1250 A and rated operational voltage up to 690 V AC, the ABB 1SDA062899R1 is ideal for main distribution boards, transformer protection, generator protection, feeder circuits and industrial switchgear. Its high short-circuit performance level supports dependable operation in demanding power distribution environments.

Key Advantages

  • High-capacity ABB Tmax T7H moulded case circuit breaker.
  • 1250 A rated current for heavy-duty electrical distribution.
  • Three-pole configuration for three-phase systems.
  • PR231/P-LSIG electronic release with ground fault protection.
  • Fixed version with front terminal connections.
  • Lever operating mechanism for straightforward manual operation.
  • High breaking capacity for demanding low voltage installations.

Key Features

  • ABB SACE Tmax T series.
  • T7H 1250 frame size.
  • 1250 A rated uninterrupted current.
  • Three-pole MCCB design.
  • PR231/P-LSIG solid-state release.
  • Rated operational voltage up to 690 V AC.
  • Rated insulation voltage 1000 V.
  • Rated impulse withstand voltage 8 kV.
  • Fixed circuit breaker with front terminals.
  • Suitable for transformer, generator and installation protection.

Reliable Protection for Industrial Power Distribution

Moulded case circuit breakers such as the ABB Tmax T7H protect electrical installations by interrupting overload, short-circuit and earth fault conditions before they can damage equipment or compromise operational safety. The PR231/P-LSIG electronic release supports dependable protection coordination in high-current distribution systems.

The ABB 1SDA062899R1 is suitable for power circuit protection in transformer, generator and installation applications. Its fixed front terminal arrangement supports panel and switchboard installation, while the high breaking capacity helps ensure reliable performance in demanding industrial environments.

Typical Applications

  • Main low voltage switchboards.
  • Industrial power distribution systems.
  • Transformer protection and feeder circuits.
  • Generator protection and changeover systems.
  • Commercial building electrical distribution.
  • Motor control centres and process plant panels.
  • Infrastructure, utilities and heavy industrial installations.

Technical Specifications

Tick the specs you need, then view products that match.

Current 1250 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 70 kA
Trip Unit Electronic
Manufacturer ABB
Series SACE Tmax T
Model T7H 1250 PR231/P LSIG In=1250A 3p F F
Product code 1SDA062899R1
EAN 8015644654481
Product type Moulded Case Circuit Breaker
Breaker type Automatic circuit breaker
Rated current 1250 A
Rated uninterrupted current 1250 A
Number of poles 3P
Release PR231/P-LSIG
Release type Electronic
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 8 kV
Short-circuit performance level H
Rated ultimate breaking capacity 70 kA at 415 V AC
Rated service breaking capacity 70 kA at 415 V AC
Rated short-time withstand current 20 kA for 1 s
Terminal connection Fixed front terminals
Operating mechanism Lever operating mechanism
Electrical durability 2000 cycles
Mechanical durability 10000 cycles
Standards IEC
Product net width 210 mm
Product net height 268 mm
Product net depth 154 mm
Product net weight approx. 13.6 kg

Frequently Asked Questions

What is the ABB 1SDA062899R1 used for?

The ABB 1SDA062899R1 is used to protect low voltage electrical distribution systems against overloads, short circuits and ground faults in industrial, commercial and infrastructure applications.

What is the rated current of this MCCB?

This ABB Tmax T7H moulded case circuit breaker has a rated current of 1250 A.

What trip unit is fitted to the ABB 1SDA062899R1?

The breaker is fitted with a PR231/P-LSIG electronic release, providing long-time, short-time, instantaneous and ground fault protection functions.

How many poles does the ABB 1SDA062899R1 have?

The ABB 1SDA062899R1 is a three-pole moulded case circuit breaker suitable for three-phase electrical systems.

What type of terminals does this breaker use?

This model is a fixed circuit breaker supplied with front terminal connections for switchboard and panel installation.

Trusted by Electrical Engineers Worldwide

ABB Tmax moulded case circuit breakers are trusted by panel builders, electrical contractors and industrial engineers for dependable protection, strong breaking performance and long-term reliability in demanding power distribution systems.