Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062863R1 is a SACE Tmax T7V 1000 A four-pole fixed moulded case circuit breaker with front terminals, a stored-energy operating mechanism, PR332/P LSIG electronic protection and 150 kA ultimate short-circuit breaking capacity at 380–415 V AC.
£13,296.68
The ABB 1SDA062863R1 is a high-performance SACE Tmax T7V 1000 moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. This configuration combines a 1000 A rated current, four-pole construction and the advanced ABB PR332/P LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.
As part of the ABB SACE Tmax T7 series, the T7V 1000 is engineered for installations with exceptionally high prospective fault currents. Its V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, while the breaker is rated for operational voltages up to 690 V AC.
The 1SDA062863R1 is supplied as a four-pole fixed circuit breaker with front terminals and a stored-energy operating mechanism. Its PR332/P LSIG electronic release provides long-time overload, short-time delayed, instantaneous and earth-fault protection, allowing coordinated protection of high-current distribution networks while also monitoring faults to earth.
The ABB SACE Tmax T7 platform is engineered for high-current low-voltage installations where dependable interruption of severe prospective fault currents and selective protection are essential. The T7V 1000 combines a 1000 A current rating with ABB's V performance level, delivering an ultimate breaking capacity of 150 kA at 380–415 V AC and up to 200 kA at 220–230 V AC.
The PR332/P LSIG electronic trip unit adds earth-fault protection to the long-time, short-time and instantaneous functions used for distribution protection. Adjustable overload, short-circuit and earth-fault settings allow the breaker to be coordinated with upstream and downstream protection devices while providing additional protection against current flowing to earth.
| Series | SACE Tmax T7 |
|---|---|
| ABB designation | T7V 1000 PR332/P LSIG In=1000A 4p F F M |
| Order code | 1SDA062863R1 |
| EAN | 8015644654122 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T7 |
| Performance level | V |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 4 |
| Trip unit | PR332/P LSIG |
| Trip-unit technology | Solid-state electronic |
| Protection functions | Long-time, short-time, instantaneous and earth fault |
| Overload release adjustment | 400–1000 A |
| Short-time delayed short-circuit adjustment | 600–10000 A |
| Instantaneous short-circuit adjustment | 1500–15000 A |
| Earth-fault protection adjustment | 0.2–1 × In |
| Neutral protection setting | OFF / 50% / 100% / 200% |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 60 kA |
| Rated service short-circuit breaking capacity (Ics) at 380–415 V AC | 150 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 45 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Installation | Fixed |
| Terminal connection | Front terminals |
| Main-circuit connection | Bolted connection |
| Operating mechanism | Stored-energy mechanism |
| Motor drive | Supported |
| Degree of protection | IP20 |
| Power loss | 50 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 268 × 280 × 178 mm |
| Net weight | approx. 14 kg |
| Standard | IEC |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA062863R1 is a SACE Tmax T7V 1000 four-pole fixed moulded case circuit breaker rated at 1000 A, with front terminals, a stored-energy operating mechanism and a PR332/P LSIG electronic trip unit.
The T7V 1000 has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with an Icu of up to 200 kA at 220–230 V AC.
The PR332/P LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.
The overload release is adjustable from 400–1000 A, the short-time delayed short-circuit function from 600–10000 A, the instantaneous function from 1500–15000 A, and earth-fault protection from 0.2–1 × In.
Yes. The G function of the PR332/P LSIG trip unit provides integrated earth-fault protection, making the breaker suitable for distribution systems requiring protection against faults to earth as well as overloads and short circuits.
ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, advanced electronic protection and substantial short-circuit breaking performance for dependable protection and coordination in demanding industrial and commercial low-voltage distribution systems.
We use cookies