1SDA062857R1 ABB T7V 1000 PR231/P-I 1000 A 4-Pole MCCB

1SDA062857R1 ABB T7V 1000 PR231/P-I 1000 A 4-Pole MCCB

ABB 1SDA062857R1 is specified as a SACE Tmax T7V 1000 A four-pole fixed moulded case circuit breaker with front terminals, a PR231/P-I electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA062857R1MPN: 1SDA062857R1
Price
List Price £14,001.56 ex VAT
Your Price (ex VAT) Save 25%
£10,501.17 25% OFF
You save £3,500.39 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,501.17
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,501.17

Why Choose the ABB T7V 1000 1SDA062857R1 Circuit Breaker?

The ABB 1SDA062857R1, specified here as T7V 1000 PR231/P I In=1000A 4p F F, is a high-performance SACE Tmax T7 moulded case circuit breaker (MCCB) designed for demanding low-voltage power distribution applications. It combines a 1000 A rated current with a PR231/P-I electronic trip unit and a four-pole fixed configuration with front terminals.

The T7V performance level is designed for installations with high prospective short-circuit currents, providing an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection, enabling rapid interruption of severe fault currents in high-current distribution systems.

With its four-pole construction, fixed installation and front-terminal arrangement, this configuration is suited to three-phase four-wire distribution systems where all four conductors are switched by the circuit breaker. Its combination of a 1000 A current rating, high breaking performance and electronic instantaneous protection makes it suitable for industrial switchboards, main distribution assemblies and high-current feeder protection.

Key Advantages

  • High-performance 1000 A moulded case circuit breaker for demanding power distribution applications.
  • 150 kA ultimate breaking capacity at 380–415 V AC for systems with very high prospective fault currents.
  • PR231/P-I electronic trip unit for adjustable instantaneous short-circuit protection.
  • Rapid response to severe short-circuit conditions.
  • Four-pole configuration for three-phase four-wire distribution systems.
  • Fixed installation with front terminals for integration into low-voltage switchboards.
  • ABB SACE Tmax T7 platform for industrial power distribution applications.

Key Features

  • ABB SACE Tmax T7V 1000 configuration.
  • 1000 A rated current.
  • PR231/P-I electronic protection trip unit.
  • Instantaneous short-circuit (I) protection.
  • Adjustable instantaneous protection threshold.
  • 150 kA Icu at 380–415 V AC.
  • Four-pole (4P) construction.
  • Fixed (F) installation.
  • Front terminals (F).
  • Designed for high-current low-voltage power distribution.
  • ABB order code 1SDA062857R1.

High-Performance Instantaneous Protection for Power Distribution

The ABB SACE Tmax T7 platform is designed for high-current low-voltage distribution systems where substantial short-circuit interruption capability is required. In the specified T7V configuration, the 1SDA062857R1 combines a 1000 A rating with 150 kA ultimate breaking capacity at 380–415 V AC, making it suitable for switchboards and feeders exposed to very high prospective fault currents.

The PR231/P-I electronic trip unit is focused on instantaneous short-circuit protection, rapidly initiating breaker operation when current exceeds its configured fault threshold. Combined with four-pole construction, this configuration is suited to high-current three-phase four-wire distribution systems where robust short-circuit protection and simultaneous switching of four conductors are required.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Three-phase four-wire distribution systems.
  • High-current feeder protection.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure distribution assemblies.
  • Systems with high prospective short-circuit currents.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series SACE Tmax T7
Specified model T7V 1000 PR231/P I In=1000A 4p F F
ABB order code 1SDA062857R1
Product type Moulded case circuit breaker (MCCB)
Frame / breaker size T7 1000
Short-circuit performance level V
Rated current (In) 1000 A
Ultimate short-circuit breaking capacity (Icu) 200 kA at 220–230 V AC
Number of poles 4
Trip unit PR231/P-I electronic trip unit
Protection function Instantaneous short-circuit (I)
Installation Fixed
Terminal configuration Front terminals
Application Power distribution and high-current short-circuit protection
Product group 310511 – T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062857R1 used for?

The ABB 1SDA062857R1, specified as T7V 1000 PR231/P-I, is a 1000 A four-pole moulded case circuit breaker intended for high-current low-voltage power distribution and short-circuit protection.

What breaking capacity does the specified ABB T7V 1000 configuration provide?

The T7V performance level provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with breaking capacity varying according to the operating voltage.

Which trip unit is specified for the ABB 1SDA062857R1?

The specified circuit breaker configuration uses an ABB PR231/P-I electronic trip unit providing adjustable instantaneous short-circuit protection.

What does the I designation mean on the PR231/P-I trip unit?

The I designation identifies instantaneous short-circuit protection, which is designed to initiate rapid circuit interruption when a severe short-circuit current exceeds the configured protection threshold.

What does 4p F F mean on this ABB Tmax T7 configuration?

4p identifies a four-pole circuit breaker, while F F denotes a fixed installation configuration with front terminals.

Trusted ABB Power Distribution Protection

ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with electronic protection and flexible installation configurations for dependable protection of demanding industrial and commercial power distribution systems.