1SDA062834R1 ABB T7V 1000 PR231/P LS/I 1000 A 3-Pole MCCB

1SDA062834R1 ABB T7V 1000 PR231/P LS/I 1000 A 3-Pole MCCB

ABB 1SDA062834R1 is a SACE Tmax T7V 1000 A three-pole fixed moulded case circuit breaker with front terminals, lever operation, a PR231/P LS/I electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA062834R1MPN: 1SDA062834R1
Price
List Price £12,307.18 ex VAT
Your Price (ex VAT) Save 25%
£9,230.39 25% OFF
You save £3,076.80 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,230.39
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,230.39

Why Choose the ABB T7V 1000 PR231/P LS/I 1SDA062834R1 Circuit Breaker?

The ABB 1SDA062834R1 is a high-performance SACE Tmax T7V 1000 moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. This configuration combines a 1000 A rated current, three-pole construction and the ABB PR231/P LS/I electronic trip unit for comprehensive overload and short-circuit protection.

As part of the ABB SACE Tmax T7 series, the T7V 1000 is engineered for installations with exceptionally high prospective fault currents. Its V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with operation supported on low-voltage systems up to 690 V AC.

The 1SDA062834R1 is supplied as a three-pole fixed circuit breaker with front terminals and a lever operating mechanism. Its PR231/P LS/I solid-state release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, with adjustable protection settings that support coordination with high-current feeders and downstream equipment.

Key Advantages

  • High-performance ABB SACE Tmax T7V moulded case circuit breaker.
  • 1000 A rated current for high-current power distribution.
  • 150 kA ultimate short-circuit breaking capacity at 380–415 V AC.
  • PR231/P LS/I electronic trip unit for overload and short-circuit protection.
  • 400–1000 A adjustable overload setting for application flexibility.
  • 1000–10000 A short-circuit protection adjustment.
  • Three-pole fixed configuration with front terminals and lever operation.

Key Features

  • ABB SACE Tmax T7V 1000 series.
  • 1000 A rated current.
  • Three-pole (3P) construction.
  • PR231/P LS/I solid-state electronic release.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • V very-high-breaking-capacity performance level.
  • 150 kA Icu at 380–415 V AC.
  • 1000 V rated insulation voltage (Ui).
  • 8 kV rated impulse withstand voltage (Uimp).
  • 15 kA short-time withstand current for 1 s.

Very High Breaking Capacity with LS/I Electronic Protection

The ABB SACE Tmax T7 platform is engineered for high-current low-voltage installations where dependable interruption of severe prospective fault currents is essential. The T7V 1000 combines a 1000 A current rating with ABB's V performance level, providing an ultimate breaking capacity of 150 kA at 380–415 V AC and up to 200 kA at 220–230 V AC.

The PR231/P LS/I electronic trip unit combines long-time overload protection with short-time and instantaneous short-circuit protection. The overload setting is adjustable from 400–1000 A, while short-circuit protection can be adjusted over a 1000–10000 A range, supporting protection coordination across demanding distribution networks.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and feeder protection in high-current switchboards.
  • Transformer and installation protection.
  • Manufacturing and process-industry electrical systems.
  • Commercial and infrastructure distribution assemblies.
  • Installations with very high prospective short-circuit currents.
  • Fixed switchgear requiring comprehensive electronic LS/I protection.

Technical Specifications

Series SACE Tmax T7
ABB designation T7V 1000 PR231/P LS/I In=1000A 3p F F
Order code 1SDA062834R1
EAN 8015644653835
Product type Moulded case circuit breaker (MCCB)
Frame T7
Performance level V
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Number of poles 3
Trip unit PR231/P LS/I electronic release
Protection functions Long-time, short-time and instantaneous
Overload release adjustment 400–1000 A
Short-circuit release adjustment 1000–10000 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 150 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 60 kA
Rated service short-circuit breaking capacity (Ics) at 380–415 V AC 150 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 45 kA
Rated short-time withstand current (Icw) 15 kA for 1 s
Installation Fixed
Terminal connection Front terminals
Operating mechanism Lever
Degree of protection IP20
Electrical durability 3000 operating cycles
Mechanical durability 10,000 operating cycles
Power loss 50 W per pole at rated operating conditions
Dimensions (H × W × D) 268 × 210 × 154 mm
Net weight 9.7 kg
Standard IEC
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062834R1?

The ABB 1SDA062834R1 is a SACE Tmax T7V 1000 three-pole fixed moulded case circuit breaker rated at 1000 A, with front terminals, lever operation and a PR231/P LS/I electronic trip unit.

What is the breaking capacity of the ABB T7V 1000 1SDA062834R1?

The T7V 1000 has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC and up to 200 kA at 220–230 V AC.

What protection functions does the PR231/P LS/I trip unit provide?

The PR231/P LS/I electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What are the protection adjustment ranges of the ABB 1SDA062834R1?

The overload release can be adjusted from 400–1000 A, while the short-circuit protection adjustment range is 1000–10000 A.

Is the ABB 1SDA062834R1 fixed or withdrawable?

The 1SDA062834R1 is a fixed three-pole circuit breaker with front terminals and a lever operating mechanism.

Trusted ABB Power Distribution Protection

ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, configurable electronic protection and substantial short-circuit breaking performance for dependable protection of demanding industrial and commercial low-voltage distribution systems.