Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062834R1 is a SACE Tmax T7V 1000 A three-pole fixed moulded case circuit breaker with front terminals, lever operation, a PR231/P LS/I electronic trip unit and 150 kA ultimate breaking capacity at 380–415 V AC.
£9,230.39
The ABB 1SDA062834R1 is a high-performance SACE Tmax T7V 1000 moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. This configuration combines a 1000 A rated current, three-pole construction and the ABB PR231/P LS/I electronic trip unit for comprehensive overload and short-circuit protection.
As part of the ABB SACE Tmax T7 series, the T7V 1000 is engineered for installations with exceptionally high prospective fault currents. Its V performance level provides a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with operation supported on low-voltage systems up to 690 V AC.
The 1SDA062834R1 is supplied as a three-pole fixed circuit breaker with front terminals and a lever operating mechanism. Its PR231/P LS/I solid-state release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, with adjustable protection settings that support coordination with high-current feeders and downstream equipment.
The ABB SACE Tmax T7 platform is engineered for high-current low-voltage installations where dependable interruption of severe prospective fault currents is essential. The T7V 1000 combines a 1000 A current rating with ABB's V performance level, providing an ultimate breaking capacity of 150 kA at 380–415 V AC and up to 200 kA at 220–230 V AC.
The PR231/P LS/I electronic trip unit combines long-time overload protection with short-time and instantaneous short-circuit protection. The overload setting is adjustable from 400–1000 A, while short-circuit protection can be adjusted over a 1000–10000 A range, supporting protection coordination across demanding distribution networks.
| Series | SACE Tmax T7 |
|---|---|
| ABB designation | T7V 1000 PR231/P LS/I In=1000A 3p F F |
| Order code | 1SDA062834R1 |
| EAN | 8015644653835 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | T7 |
| Performance level | V |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 3 |
| Trip unit | PR231/P LS/I electronic release |
| Protection functions | Long-time, short-time and instantaneous |
| Overload release adjustment | 400–1000 A |
| Short-circuit release adjustment | 1000–10000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 60 kA |
| Rated service short-circuit breaking capacity (Ics) at 380–415 V AC | 150 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 45 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Installation | Fixed |
| Terminal connection | Front terminals |
| Operating mechanism | Lever |
| Degree of protection | IP20 |
| Electrical durability | 3000 operating cycles |
| Mechanical durability | 10,000 operating cycles |
| Power loss | 50 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 268 × 210 × 154 mm |
| Net weight | 9.7 kg |
| Standard | IEC |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA062834R1 is a SACE Tmax T7V 1000 three-pole fixed moulded case circuit breaker rated at 1000 A, with front terminals, lever operation and a PR231/P LS/I electronic trip unit.
The T7V 1000 has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC and up to 200 kA at 220–230 V AC.
The PR231/P LS/I electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The overload release can be adjusted from 400–1000 A, while the short-circuit protection adjustment range is 1000–10000 A.
The 1SDA062834R1 is a fixed three-pole circuit breaker with front terminals and a lever operating mechanism.
ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, configurable electronic protection and substantial short-circuit breaking performance for dependable protection of demanding industrial and commercial low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.