ABB T7L 1000 PR232/P LSI 4-pole moulded case circuit breaker with a 1000 A rated current, fixed front-terminal configuration, LSI electronic protection and 120 kA breaking capacity at 415 V AC.
£10,755.26
The ABB T7L 1000 PR232/P LSI is a high-performance 4-pole moulded case circuit breaker (MCCB) designed for protection and control of demanding low-voltage power distribution systems. As part of the established ABB Tmax T7 series, it combines a 1000 A rated current with electronic protection and high short-circuit breaking performance.
Equipped with the PR232/P LSI electronic trip unit, the T7L 1000 provides long-time, short-time and instantaneous protection functions for dependable protection against overload and short-circuit conditions. Its adjustable protection settings support effective coordination within industrial and commercial electrical distribution networks.
With an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, a rated operational voltage of up to 690 V AC and a fixed four-pole configuration with front terminals, this breaker is well suited to switchboards and power distribution assemblies requiring high fault-current capability.
Moulded case circuit breakers such as the ABB Tmax T7 protect electrical distribution circuits against overload and short-circuit conditions. The electronic protection unit monitors circuit current and initiates interruption when configured protection thresholds are exceeded, helping protect cables, switchgear and connected electrical equipment.
The T7L 1000 combines a high current rating and high breaking capacity with adjustable LSI protection. Its four-pole construction enables switching of all three phases and the neutral, making it suitable for demanding low-voltage distribution systems where coordinated protection and reliable isolation are important.
| Series | Tmax T7 |
|---|---|
| ABB order code | 1SDA062827R1 |
| Product type | Moulded case circuit breaker |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Number of poles | 4 |
| Trip unit | PR232/P |
| Protection functions | LSI |
| Ultimate short-circuit breaking capacity (Icu) | 120 kA at 415 V AC |
| Service short-circuit breaking capacity (Ics) | 120 kA at 415 V AC |
| Overload release adjustment range | 400–1000 A |
| Short-time delayed short-circuit adjustment range | 600–10000 A |
| Instantaneous short-circuit adjustment range | 1500–12000 A |
| Rated short-time withstand current (Icw) | 20 kA for 1 s |
| Mounting type | Fixed |
| Terminal configuration | Front terminals |
| Operating mechanism | Stored-energy mechanism |
| ABB product group | 310511-T-Max T4 - T8 |
This moulded case circuit breaker is designed to protect high-current low-voltage distribution circuits against overload and short-circuit conditions in industrial and commercial electrical systems.
The ABB T7L 1000 1SDA062827R1 has a rated uninterrupted current of 1000 A, with an overload release adjustment range of 400–1000 A.
The breaker has an ultimate short-circuit breaking capacity of 120 kA at 415 V AC.
This model is equipped with the ABB PR232/P LSI electronic trip unit, providing long-time, short-time and instantaneous protection functions.
This version has a 4-pole configuration, enabling switching of the three phase conductors and neutral in suitable low-voltage distribution systems.
ABB order code 1SDA062827R1 is a fixed-mounted circuit breaker with front terminals and a stored-energy operating mechanism.
ABB Tmax moulded case circuit breakers are widely used by electrical engineers, panel builders and industrial operators for dependable circuit protection, power distribution and control in demanding low-voltage installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.