Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062825R1 is a T7L1000 1000 A four-pole fixed moulded case circuit breaker with a PR231/P-I electronic trip unit, stored-energy operating mechanism and 120 kA ultimate breaking capacity at 400–415 V AC.
£10,026.01
The ABB T7L1000 PR231/P-I is a high-performance moulded case circuit breaker (MCCB) designed for reliable short-circuit protection and switching in high-current low-voltage power distribution systems. As part of the proven ABB SACE Tmax T7 series, it combines a 1000 A rated current with the PR231/P electronic trip unit and T7L high-breaking-capacity performance.
The PR231/P-I solid-state release provides adjustable instantaneous short-circuit protection, allowing rapid interruption of severe fault currents. This configuration is particularly suitable where overload protection is provided separately or where dedicated instantaneous protection is required as part of a coordinated electrical distribution system.
This model is supplied in a 4-pole fixed configuration with front terminals and a stored-energy operating mechanism. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 120 kA at 400–415 V AC, the T7L1000 is engineered for demanding industrial and commercial switchboard applications.
Moulded case circuit breakers such as the ABB Tmax T7 provide dependable switching, isolation and fault protection for low-voltage electrical distribution systems. The high interruption capability of the T7L frame enables severe prospective short-circuit currents to be safely interrupted before they cause extensive damage to conductors and connected equipment.
The PR231/P-I electronic release is configured specifically for instantaneous short-circuit protection. Its adjustable operating threshold allows the protection characteristics to be coordinated with the electrical installation, while the four-pole construction enables simultaneous switching of all three phases and the neutral conductor.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062825R1 |
| ABB product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker |
| Frame | T7L |
| Rated uninterrupted current | 1000 A |
| Rated operational voltage | 690 V AC |
| Number of poles | 4 |
| Trip unit | PR231/P |
| Release type | Electronic / solid-state |
| Protection function | I — instantaneous short-circuit protection |
| Instantaneous short-circuit release adjustment | 1000–10000 A |
| Ultimate breaking capacity (Icu) at 400–415 V AC | 120 kA |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| Operating mechanism | Stored-energy mechanism |
| Motor drive | Optional |
| Weight | approx. 15.5 kg |
This Tmax T7L moulded case circuit breaker is designed for switching and instantaneous short-circuit protection of high-current low-voltage power distribution circuits.
The circuit breaker has a rated uninterrupted current of 1000 A.
The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection, with an adjustment range of 1000–10000 A.
The T7L1000 provides an ultimate short-circuit breaking capacity of 120 kA at 400–415 V AC.
This model is a 4-pole fixed circuit breaker with front terminals and a stored-energy operating mechanism for integration into low-voltage switchboards and power-distribution systems.
ABB SACE Tmax circuit breakers are widely used in industrial, commercial and infrastructure power systems where dependable switching, electronic fault protection and high short-circuit breaking capacity are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.