Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062823R1 is a SACE Tmax T7L 1000 A three-pole fixed moulded case circuit breaker with front terminals, a PR332/P LSIG electronic trip unit, stored-energy operating mechanism and 120 kA ultimate breaking capacity at 400 V AC.
£10,094.81
The ABB 1SDA062823R1 is a high-performance SACE Tmax T7L moulded case circuit breaker (MCCB) designed for protection and control of demanding low-voltage power distribution systems. Identified by ABB as T7L 1000 PR332/P LSIG In=1000A 3p F F M, it combines a 1000 A rated uninterrupted current with the advanced PR332/P electronic trip unit, three-pole construction and a stored-energy operating mechanism.
The T7L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, making the breaker suitable for industrial installations with high prospective fault currents. Its PR332/P LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and integrated earth-fault (G) protection for comprehensive protection and coordination within electrical distribution networks.
This configuration is a three-pole, fixed circuit breaker with front terminals and a stored-energy operating mechanism with push-button control. The overload protection threshold is adjustable from 400–1000 A, while the instantaneous short-circuit release is adjustable from 1500–15000 A, providing flexibility for demanding high-current distribution applications.
The ABB SACE Tmax T7L range is designed for high-current low-voltage distribution systems where substantial short-circuit interruption capability is required. The 1SDA062823R1 combines a 1000 A rating with an ultimate breaking capacity of 120 kA at 400 V AC, providing robust protection for industrial feeders, main distribution boards and switchgear with high prospective fault levels.
The integrated PR332/P LSIG electronic trip unit provides four principal protection functions. Long-time protection responds to sustained overloads, short-time protection assists selective coordination, instantaneous protection provides rapid response to severe short circuits, and integrated earth-fault protection detects ground-fault conditions. This comprehensive protection package makes the breaker particularly suitable for sophisticated industrial distribution networks where selectivity and continuity of supply are important.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062823R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame / breaker size | T7 1000 |
| Short-circuit performance level | L |
| Rated uninterrupted current (Iu) | 1000 A |
| Overload protection adjustment range | 400–1000 A |
| Rated voltage | 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) | 120 kA at 400 V AC |
| Number of poles | 3 |
| Trip unit | PR332/P LSIG electronic trip unit |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) and earth-fault (G) |
| Short-time delayed short-circuit adjustment range | 600–10000 A |
| Instantaneous short-circuit adjustment range | 1500–15000 A |
| Integrated earth-fault protection | Yes |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| Main circuit connection | Bolted connection |
| Operating mechanism | Stored-energy mechanism |
| Control element | Push button |
| Motor drive | Optional |
| Protection rating | IP20 |
| Weight | approx. 12.5 kg |
| GTIN / EAN | 8015644653729 |
| Application | Power distribution protection and control |
| Product group | 310511 – T-Max T4 - T8 |
The ABB 1SDA062823R1 is a 1000 A three-pole moulded case circuit breaker designed to protect and control high-current low-voltage power distribution circuits against overload, short-circuit and earth-fault conditions.
The T7L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 400 V AC, providing high interruption performance for demanding industrial distribution systems.
The circuit breaker is equipped with an ABB PR332/P LSIG electronic trip unit, providing long-time overload, short-time short-circuit, instantaneous short-circuit and integrated earth-fault protection.
Overload protection is adjustable from 400–1000 A, short-time delayed short-circuit protection from 600–10000 A, and instantaneous short-circuit protection from 1500–15000 A.
LSIG identifies long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault or ground-fault (G) protection functions.
ABB SACE Tmax moulded case circuit breakers combine high interruption performance with advanced electronic protection and flexible operating configurations for dependable protection and control of demanding industrial and commercial power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.