1SDA062808R1 ABB T7L 1000 PR332/P LSIRc 3P 1000 A Circuit Breaker

1SDA062808R1 ABB T7L 1000 PR332/P LSIRc 3P 1000 A Circuit Breaker

ABB 1SDA062808R1 is a 1000 A three-pole SACE Tmax T7L fixed moulded case circuit breaker with front terminals, a PR332/P LSIRc electronic trip unit, residual-current protection and 120 kA ultimate breaking capacity at 380-415 V AC.

SKU: 1SDA062808R1MPN: 1SDA062808R1
Price
List Price £12,325.43 ex VAT
Your Price (ex VAT) Save 25%
£9,244.07 25% OFF
You save £3,081.36 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,244.07
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,244.07

Why Choose the ABB 1SDA062808R1 T7L 1000 Circuit Breaker?

The ABB 1SDA062808R1 is a high-performance three-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax T7 range, engineered for demanding low-voltage power distribution applications. Identified as T7L 1000 PR332/P LSIRc In=1000A 3P F F, it combines a 1000 A rated current with ABB's advanced PR332/P electronic trip unit and residual-current protection.

The PR332/P LSIRc electronic trip unit provides comprehensive protection against overload and short-circuit conditions together with Rc residual-current protection. The overload protection is adjustable from 0.4–1 × In, equivalent to 400–1000 A, while magnetic protection is adjustable from 1.5–15 × In. The residual-current function provides an additional protection range of 0.2–1 × In.

The 1SDA062808R1 is supplied as a three-pole fixed circuit breaker with front terminals and lever operating mechanism. Its T7L construction provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making it particularly suitable for industrial switchboards, main distribution assemblies and high-current feeder circuits where high fault interruption capability and residual-current protection are required.

Key Advantages

  • High-performance ABB SACE Tmax T7L moulded case circuit breaker.
  • 1000 A rated current for high-current low-voltage distribution.
  • High 120 kA ultimate breaking capacity at 380–415 V AC.
  • Advanced PR332/P LSIRc electronic trip unit.
  • Adjustable overload and short-circuit protection for flexible circuit coordination.
  • Rc residual-current protection for enhanced earth-leakage fault detection.
  • Fixed installation with front terminals for practical switchboard integration.

Key Features

  • ABB SACE Tmax T7L 1000 circuit breaker.
  • 1000 A rated uninterrupted current.
  • Three-pole (3P) configuration.
  • PR332/P LSIRc electronic trip unit.
  • Long-time overload protection.
  • Short-circuit protection.
  • Rc residual-current protection.
  • Overload adjustment from 0.4–1 × In.
  • Magnetic protection adjustment from 1.5–15 × In.
  • Residual-current adjustment from 0.2–1 × In.
  • Fixed (F) circuit breaker execution.
  • Front terminals (F).
  • Lever operating mechanism for manual switching.

PR332/P LSIRc Electronic and Residual-Current Protection

The PR332/P LSIRc electronic trip unit combines adjustable overcurrent protection with residual-current monitoring. Its overload protection can be set between 400–1000 A, while the short-circuit protection range extends from 1500–15000 A. These adjustable settings allow the breaker protection characteristics to be coordinated with the electrical installation and other protective devices.

The additional Rc residual-current function detects current imbalance associated with leakage to earth and extends the protection provided by the breaker beyond conventional overcurrent protection. Combined with the T7L platform's 120 kA Icu at 380–415 V AC, this makes the ABB 1SDA062808R1 particularly suitable for high-current distribution systems requiring both substantial short-circuit interruption capability and residual-current protection.

Typical Applications

  • Industrial low-voltage main distribution boards.
  • High-current feeder and sub-main protection.
  • Manufacturing and process plant switchboards.
  • Commercial building main electrical distribution.
  • Infrastructure and utility distribution assemblies.
  • Installations requiring residual-current protection.
  • Power distribution systems with high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax T7
Order code / MPN 1SDA062808R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker
Breaker designation T7L 1000
Frame size T7
Short-circuit performance level L
Rated current (In) 1000 A
Rated uninterrupted current (Iu) 1000 A
Number of poles 3
Trip unit PR332/P-LSIRc
Trip technology Electronic / solid-state
Protection configuration LSIRc
Overload adjustment 0.4–1 × In
Overload release setting range 400–1000 A
Short-circuit protection adjustment 1.5–15 × In
Short-circuit release setting range 1500–15000 A
Residual-current protection adjustment 0.2–1 × In
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Ultimate breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380–415 V AC 120 kA
Ultimate breaking capacity (Icu) at 440 V AC 100 kA
Ultimate breaking capacity (Icu) at 500 V AC 85 kA
Ultimate breaking capacity (Icu) at 690 V AC 50 kA
Service breaking capacity (Ics) at 380–415 V AC 120 kA
Rated short-time withstand current (Icw) 20 kA for 1 s
Installation type Fixed
Terminal configuration Front terminals
Operating mechanism Lever operated
Power loss at rated operating conditions 30 W per pole
Standards IEC
EAN 8015644653576
Application Low-voltage power distribution and residual-current protection

Frequently Asked Questions

What is the ABB 1SDA062808R1?

The ABB 1SDA062808R1 is a 1000 A three-pole SACE Tmax T7L moulded case circuit breaker with a PR332/P LSIRc electronic trip unit, residual-current protection, fixed installation and front terminals.

What protection does the ABB 1SDA062808R1 provide?

The PR332/P LSIRc trip unit provides adjustable overload and short-circuit protection together with Rc residual-current protection, providing comprehensive protection for demanding low-voltage distribution circuits.

What is the breaking capacity of the ABB 1SDA062808R1?

The T7L 1000 provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC. Its voltage-dependent Icu ratings also include 200 kA at 220–230 V AC, 100 kA at 440 V AC, 85 kA at 500 V AC and 50 kA at 690 V AC.

What protection adjustment ranges are available on the ABB 1SDA062808R1?

The overload protection is adjustable from 400–1000 A, the short-circuit protection from 1500–15000 A, and the residual-current function from 0.2–1 × In.

What does 3P F F mean on the ABB T7L 1000?

3P identifies the three-pole configuration, while F F identifies a fixed circuit breaker with front terminals for permanent installation within a compatible low-voltage switchboard or distribution assembly.

Trusted ABB Circuit Protection

ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with advanced electronic and residual-current protection, supporting dependable low-voltage power distribution across demanding industrial, commercial and infrastructure applications.