1SDA062801R1 ABB T7L 1000 PR231/P-I 1000 A 3-Pole MCCB

1SDA062801R1 ABB T7L 1000 PR231/P-I 1000 A 3-Pole MCCB

ABB 1SDA062801R1 is a SACE Tmax T7L 1000 A three-pole fixed moulded case circuit breaker with front terminals, manual operation, a PR231/P-I electronic trip unit and 120 kA ultimate breaking capacity at 380–415 V AC.

SKU: 1SDA062801R1MPN: 1SDA062801R1
Price
List Price £9,845.14 ex VAT
Your Price (ex VAT) Save 25%
£7,383.86 25% OFF
You save £2,461.29 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,383.86
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,383.86

Why Choose the ABB T7L 1000 PR231/P-I 1SDA062801R1 Circuit Breaker?

The ABB 1SDA062801R1 is a high-performance SACE Tmax T7L 1000 moulded case circuit breaker (MCCB) designed for short-circuit protection and switching in demanding low-voltage electrical systems. This configuration combines a 1000 A rated current, three-pole construction and the ABB PR231/P-I electronic trip unit with adjustable instantaneous protection.

As part of the ABB SACE Tmax T7 series, the T7L 1000 provides high fault-breaking capability for industrial switchboards, motor circuits and power distribution installations. Its L performance level delivers a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacities defined across low-voltage systems up to 690 V AC.

The 1SDA062801R1 is supplied as a three-pole fixed circuit breaker with front terminals and manual operation. Its PR231/P-I electronic release provides adjustable instantaneous short-circuit protection from 1.5 to 12 × In, making the breaker particularly suitable for applications where high-capacity fault protection is required and overload protection is coordinated separately.

Key Advantages

  • High-performance ABB SACE Tmax T7L moulded case circuit breaker.
  • 1000 A rated current for high-current electrical systems.
  • 120 kA ultimate short-circuit breaking capacity at 380–415 V AC.
  • PR231/P-I electronic trip unit with adjustable instantaneous protection.
  • Instantaneous protection adjustable from 1.5 to 12 × In.
  • Three-pole fixed configuration with front terminals.
  • Manual operation for straightforward integration into fixed switchgear assemblies.

Key Features

  • ABB SACE Tmax T7L 1000 series.
  • 1000 A rated current.
  • Three-pole (3P) construction.
  • PR231/P-I electronic release.
  • Adjustable instantaneous short-circuit protection.
  • 1.5–12 × In instantaneous protection adjustment.
  • L high-breaking-capacity performance level.
  • 120 kA Icu at 380–415 V AC.
  • Breaking capacity up to 200 kA at 220–230 V AC.
  • Suitable for systems up to 690 V AC.
  • Fixed installation with front terminals.
  • Manual operating mechanism.

High-Capacity Short-Circuit Protection

The ABB SACE Tmax T7 platform is designed for high-current low-voltage installations where dependable interruption of substantial prospective fault currents is essential. The T7L performance level provides an ultimate breaking capacity of 120 kA at 380–415 V AC and up to 200 kA at 220–230 V AC, providing robust protection for demanding electrical systems.

The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection from 1.5 to 12 times the breaker rated current. This characteristic makes the T7L 1000 particularly suitable for motor-protection and other applications where the MCCB provides high-capacity short-circuit protection while overload protection is coordinated by separate equipment.

Typical Applications

  • High-current industrial motor circuits.
  • Motor control centres and industrial switchboards.
  • Low-voltage power distribution systems.
  • Manufacturing and process-industry installations.
  • Applications with high prospective short-circuit currents.
  • Industrial machinery and plant electrical systems.
  • Fixed switchgear requiring high fault-breaking capability.

Technical Specifications

Series SACE Tmax T7
Order code 1SDA062801R1
Product type Moulded case circuit breaker (MCCB)
Rated current (In) 1000 A
Number of poles 3
Trip unit PR231/P-I electronic release
Protection function Adjustable instantaneous short-circuit protection
Instantaneous protection adjustment 1.5–12 × In
Short-circuit performance level L
Rated operational voltage up to 690 V AC
Rated ultimate short-circuit breaking capacity (Icu) at 220–230 V AC 200 kA
Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC 120 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 100 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 50 kA
Installation Fixed
Terminal connection Front terminals
Operation Manual
Dimensions (H × W × D) 268 × 210 × 154 mm
Weight approx. 9.7 kg
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062801R1?

The ABB 1SDA062801R1 is a SACE Tmax T7L 1000 three-pole fixed moulded case circuit breaker rated at 1000 A and equipped with a PR231/P-I electronic trip unit.

What is the breaking capacity of the ABB T7L 1000 1SDA062801R1?

The T7L 1000 has a rated ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacity varying according to system voltage.

What protection does the PR231/P-I trip unit provide?

The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection, with its threshold adjustable from 1.5 to 12 × In.

What is the rated current of the ABB 1SDA062801R1?

The circuit breaker has a rated current of 1000 A and is designed for high-current low-voltage electrical applications.

Is the ABB 1SDA062801R1 fixed or withdrawable?

The 1SDA062801R1 is a fixed three-pole circuit breaker with front terminals and manual operation.

Trusted ABB Power and Motor Protection

ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, electronic protection and substantial short-circuit breaking performance for dependable protection of demanding industrial motor and low-voltage electrical systems.