Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB T7S 1000 PR332/P LSIRc four-pole moulded case circuit breaker with 1000 A rated current and electronic LSIRc protection for industrial power distribution.
£7,333.32
The ABB 1SDA062752R1 is a high-performance SACE Tmax T7S moulded case circuit breaker (MCCB) designed to provide dependable protection for low voltage power distribution systems. Built for demanding industrial, commercial and infrastructure applications, this fixed four-pole circuit breaker delivers reliable protection against overloads, short circuits and residual current faults while supporting complete conductor isolation where required.
Featuring the advanced PR332/P LSIRc electronic trip unit, the breaker provides Long-time, Short-time, Instantaneous and residual current protection. This comprehensive protection package helps improve selectivity, reduce unwanted downtime and protect critical electrical assets across complex power distribution networks.
With a 1000 A rated current, 690 V AC rated operational voltage and 50 kA breaking capacity at 400/415 V AC, the ABB T7S is ideally suited to main switchboards, industrial distribution panels, motor control centres and high-current electrical systems where safety, uptime and long service life are essential.
The ABB SACE Tmax T7S range is engineered to protect low voltage electrical installations from overload, short-circuit and residual current fault conditions while maintaining excellent operational continuity. The PR332/P LSIRc electronic trip unit enables accurate protection settings and supports selective coordination across complex power distribution networks.
Its four-pole construction makes this MCCB suitable for systems where neutral switching or full conductor isolation is required, providing dependable protection for industrial facilities, commercial buildings, utilities and infrastructure projects.
Tick the specs you need, then view products that match.
| Current | 1000 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 50 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T7S 1000 PR332/P LSIRc In=1000A 4P F F | |
| Product code | 1SDA062752R1 | |
| Product type | Moulded case circuit breaker (MCCB) | |
| Rated current (In) | 1000 A | |
| Rated uninterrupted current (Iu) | 1000 A | |
| Number of poles | 4 | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Breaking capacity (Icu) | 50 kA at 400/415 V AC | |
| Breaking capacity (Ics) | 50 kA at 400/415 V AC | |
| Short-time withstand current (Icw) | 20 kA for 1 second | |
| Trip unit | PR332/P LSIRc electronic release | |
| Protection functions | Long-time, Short-time, Instantaneous and residual current protection | |
| Connection type | Front terminals | |
| Mounting | Fixed | |
| Operating mechanism | Lever | |
| Electrical durability | 2000 cycles | |
| Mechanical durability | 10000 cycles | |
| Power loss | 30 W per pole at rated operating conditions | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | 268 × 280 × 154 mm | |
| Weight | Approx. 12.5 kg |
This moulded case circuit breaker protects low voltage power distribution systems against overloads, short circuits and residual current faults in industrial and commercial installations.
The PR332/P LSIRc electronic trip unit provides Long-time, Short-time, Instantaneous and residual current protection for comprehensive circuit protection and improved selectivity.
This model features a four-pole fixed configuration, making it suitable for applications requiring neutral switching or full conductor isolation.
The breaker has a rated uninterrupted current of 1000 A.
It is commonly installed in industrial switchboards, main distribution panels, commercial buildings and infrastructure power distribution systems.
ABB SACE Tmax moulded case circuit breakers are trusted by electrical engineers, panel builders and industrial operators worldwide for delivering dependable protection, high interruption performance and long-term reliability in critical electrical distribution systems.