ABB T7S 1000 PR332/P LI four-pole moulded case circuit breaker with 1000 A rated current and electronic LI protection for industrial power distribution.
£5,657.69
The ABB 1SDA062749R1 is a premium SACE Tmax T7S moulded case circuit breaker (MCCB) engineered to provide dependable protection for low voltage power distribution systems. Designed for demanding industrial, commercial and infrastructure applications, this fixed four-pole circuit breaker delivers reliable protection against overloads and short circuits while providing complete conductor isolation where required.
Featuring the advanced PR332/P LI electronic trip unit, the breaker provides accurate Long-time and Instantaneous protection, enabling dependable fault detection while maintaining excellent system reliability. The electronic release allows accurate protection settings that help safeguard switchboards, transformers, generators and critical electrical equipment.
With a 1000 A rated current, 690 V AC rated operational voltage and a 50 kA breaking capacity at 400/415 V AC, the ABB T7S is ideally suited to main distribution boards, industrial switchboards and high-current power distribution systems where safety and operational continuity are essential.
The ABB SACE Tmax T7S range is engineered to protect low voltage electrical installations from overload and short-circuit faults while maintaining excellent operational continuity. The PR332/P LI electronic trip unit enables accurate protection settings and dependable coordination across demanding power distribution systems.
Its four-pole construction makes this MCCB suitable for installations requiring complete conductor isolation, providing dependable protection for industrial facilities, commercial buildings, utilities and infrastructure projects.
Tick the specs you need, then view products that match.
| Current | 1000 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 50 kA | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T7S 1000 PR332/P LI In=1000A 4P F F | |
| Product code | 1SDA062749R1 | |
| Product type | Moulded case circuit breaker (MCCB) | |
| Rated current (In) | 1000 A | |
| Rated uninterrupted current (Iu) | 1000 A | |
| Number of poles | 4 | |
| Rated operational voltage | Up to 690 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Breaking capacity (Icu) | 50 kA at 400/415 V AC | |
| Breaking capacity (Ics) | 50 kA at 400/415 V AC | |
| Short-time withstand current (Icw) | 20 kA for 1 second | |
| Trip unit | PR332/P LI electronic release | |
| Protection functions | Long-time and Instantaneous protection | |
| Connection type | Front terminals | |
| Mounting | Fixed | |
| Operating mechanism | Lever | |
| Electrical durability | 2000 cycles | |
| Mechanical durability | 10000 cycles | |
| Power loss | 30 W per pole at rated operating conditions | |
| Standards | IEC 60947-2 | |
| Dimensions (H × W × D) | Approx. 268 × 280 × 154 mm | |
| Weight | Approx. 12.5 kg |
This moulded case circuit breaker protects low voltage power distribution systems against overloads and short circuits in industrial and commercial installations.
The PR332/P LI electronic trip unit provides Long-time and Instantaneous protection for dependable circuit protection.
This model features a four-pole fixed configuration, making it suitable for applications requiring complete conductor isolation.
The breaker has a rated uninterrupted current of 1000 A.
It is commonly installed in industrial switchboards, main distribution panels, commercial buildings and infrastructure power distribution systems.
ABB SACE Tmax moulded case circuit breakers are trusted by electrical engineers, panel builders and industrial operators worldwide for delivering dependable protection, high interruption performance and long-term reliability in critical electrical distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.