Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062729R1 is an 800 A four-pole SACE Tmax T7V fixed moulded case circuit breaker with front terminals, a stored-energy operating mechanism, PR231/P-I electronic short-circuit protection and 150 kA ultimate breaking capacity at 380-415 V AC.
£9,019.58
The ABB 1SDA062729R1 is a high-performance four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax T7 range, designed for demanding low-voltage power distribution applications. Identified as T7V 800 PR231/P I In=800A 4P F F M, it combines an 800 A rated current with a PR231/P electronic trip unit and the high fault-interruption performance of the T7V platform.
The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection, with a setting range of 800–8000 A. This protection characteristic makes the breaker particularly suitable where rapid interruption of high fault currents is required, while selectable neutral protection supports its use in four-pole three-phase and neutral distribution systems.
The 1SDA062729R1 is supplied as a four-pole fixed circuit breaker with front terminals and a stored-energy operating mechanism. It provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for industrial switchboards, main distribution assemblies and other installations with high prospective short-circuit currents.
The PR231/P-I electronic trip unit provides adjustable protection against high short-circuit currents. Its release can be set across an 800–8000 A range, allowing the instantaneous protection threshold to be matched to the characteristics of the protected circuit and coordinated with other protection devices within the distribution system.
Combined with the T7V high-breaking-capacity platform, the ABB 1SDA062729R1 can interrupt prospective fault currents up to 150 kA at 380–415 V AC. Its four-pole construction, selectable neutral protection, fixed front-terminal arrangement and stored-energy mechanism make it particularly suited to demanding three-phase distribution and switchboard applications.
| Series | SACE Tmax T7 |
|---|---|
| Order code / MPN | 1SDA062729R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Moulded case circuit breaker |
| Breaker designation | T7V 800 |
| Frame size | T7 |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 4 |
| Trip unit | PR231/P-I |
| Trip technology | Electronic / solid-state |
| Protection function | Adjustable instantaneous short-circuit protection |
| Short-circuit release adjustment range | 800–8000 A |
| Neutral protection setting | OFF / 50% / 100% |
| Rated voltage | 690 V AC |
| Ultimate breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Ultimate breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 130 kA |
| Ultimate breaking capacity (Icu) at 500 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 60 kA |
| Installation type | Fixed |
| Terminal configuration | Front terminals |
| Main circuit connection | Bolted connection |
| Operating mechanism | Stored-energy mechanism |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP20 |
| EAN | 8015644652784 |
| Application | Low-voltage power distribution and high-current short-circuit protection |
The ABB 1SDA062729R1 is an 800 A four-pole SACE Tmax T7V moulded case circuit breaker with a PR231/P-I electronic trip unit, fixed installation, front terminals and a stored-energy operating mechanism.
The PR231/P-I electronic trip unit provides adjustable instantaneous short-circuit protection, with the short-circuit release adjustable from 800–8000 A.
The T7V 800 provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. Its voltage-dependent Icu ratings include 200 kA at 220–230 V AC and 60 kA at 690 V AC.
The ABB 1SDA062729R1 has a rated uninterrupted current of 800 A and is supplied as a four-pole circuit breaker.
The F F M designation identifies a fixed circuit breaker with front terminals and a stored-energy operating mechanism. A motor drive is not integrated as standard but can be added as an optional operating accessory.
ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with electronic protection and flexible operating mechanisms, supporting dependable low-voltage power distribution across demanding industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.