Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062728R1 is a Tmax T7V 800 A three-pole fixed moulded-case circuit breaker with a PR332/P LSIRc electronic trip unit, residual-current protection and 150 kA ultimate breaking capacity at 380–415 V AC.
£8,990.59
The ABB 1SDA062728R1, designated T7V 800 PR332/P LSIRc In=800A 3p F F M, is a high-performance three-pole moulded-case circuit breaker (MCCB) designed for protection and control of demanding low-voltage electrical distribution systems. As part of the proven ABB Tmax T7 series, it combines an 800 A current rating with the advanced PR332/P LSIRc electronic trip unit for comprehensive circuit and residual-current protection.
The T7V version provides exceptionally high short-circuit interruption performance, with a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. The PR332/P LSIRc electronic release provides long-time, short-time and instantaneous overcurrent protection together with residual-current protection, enabling the breaker to protect installations against a broad range of electrical faults.
With a rated uninterrupted current of 800 A, a three-pole configuration, fixed installation and front terminals, the 1SDA062728R1 is well suited to main distribution boards, industrial switchboards and high-power infrastructure. Its stored-energy operating mechanism and motorisable design also provide flexibility for automated switching and control applications.
Moulded-case circuit breakers such as the ABB Tmax T7 protect electrical distribution systems against overloads, short circuits and other potentially damaging fault conditions. The T7V 800 combines an 800 A continuous-current capability with very high short-circuit interruption performance, making it particularly suitable for installations with substantial prospective fault currents.
The PR332/P LSIRc electronic trip unit extends conventional overcurrent protection with residual-current functionality. Adjustable protection thresholds allow engineers to coordinate the breaker with upstream and downstream protection devices, while the fixed construction, front terminals and stored-energy mechanism support integration into sophisticated low-voltage switchboards.
| Series | Tmax T7 |
|---|---|
| ABB order code | 1SDA062728R1 |
| ABB product group | 310511-T-Max T4 - T8 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | T7V 800 |
| Rated uninterrupted current | 800 A |
| Number of poles | 3 |
| Trip unit | PR332/P LSIRc |
| Protection functions | Long-time, short-time, instantaneous and residual-current protection |
| Overload adjustment range | 320–800 A |
| Short-time delayed short-circuit adjustment | 480–8000 A |
| Instantaneous short-circuit adjustment | 1200–12000 A |
| Rated operational voltage | up to 690 V AC |
| Rated insulation voltage | 1000 V |
| Ultimate short-circuit breaking capacity Icu at 220–230 V AC | 200 kA |
| Ultimate short-circuit breaking capacity Icu at 380–415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity Icu at 440 V AC | 130 kA |
| Ultimate short-circuit breaking capacity Icu at 500 V AC | 100 kA |
| Ultimate short-circuit breaking capacity Icu at 690 V AC | 60 kA |
| Rated short-time withstand current Icw | 15 kA for 1 s |
| Protection rating | IP20 |
| Installation | Fixed |
| Terminal connection | Front |
| Main circuit connection | Bolt connection |
| Operating mechanism | Stored-energy mechanism, motor drive optional |
| Dimensions (H × W × D) | approx. 268 × 210 × 178 mm |
| Weight | approx. 11 kg |
The ABB 1SDA062728R1 is an 800 A three-pole moulded-case circuit breaker designed to protect demanding low-voltage electrical distribution systems against overloads, short circuits and residual-current faults.
This circuit breaker is equipped with an ABB PR332/P LSIRc electronic trip unit, providing adjustable long-time, short-time and instantaneous protection together with residual-current protection.
The T7V 800 has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it suitable for electrical installations with very high prospective fault currents.
The PR332/P LSIRc trip unit provides an adjustable overload protection range of 320–800 A, with additional adjustable short-time and instantaneous short-circuit protection.
The breaker is typically installed in low-voltage switchboards, industrial distribution panels, power distribution centres and infrastructure systems requiring high-current protection, residual-current protection and high short-circuit breaking performance.
ABB Tmax moulded-case circuit breakers are widely used in industrial, commercial and infrastructure power distribution systems, providing dependable circuit protection, flexible electronic trip functionality and high short-circuit interruption performance.
We use cookies