Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062722R1 is a SACE Tmax T7V 800 A three-pole fixed moulded case circuit breaker with front terminals, a stored-energy operating mechanism, PR231/P LS/I electronic protection and 150 kA ultimate breaking capacity at 380–415 V AC.
£6,944.40
The ABB 1SDA062722R1 is a high-performance SACE Tmax T7V 800 moulded case circuit breaker (MCCB) designed for protection and switching in demanding low-voltage power distribution systems. This configuration combines an 800 A rated current, three-pole construction and the ABB PR231/P LS/I electronic trip unit for reliable overload and short-circuit protection.
As part of the advanced ABB SACE Tmax T7 series, the T7V 800 provides exceptionally high fault-breaking performance for industrial switchboards, infrastructure and power distribution installations. Its V short-circuit performance level delivers a rated ultimate breaking capacity of 150 kA at 380–415 V AC, while the breaker is suitable for rated operational voltages up to 690 V AC.
The 1SDA062722R1 is configured as a three-pole fixed circuit breaker with front terminals and a stored-energy operating mechanism. Its PR231/P LS/I solid-state release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, making this breaker suitable for high-current feeders and distribution circuits requiring dependable electronic protection.
The ABB SACE Tmax T7 platform is engineered for high-current low-voltage distribution systems where reliable interruption of severe fault currents is essential. The T7V performance level provides an ultimate breaking capacity of 150 kA at 380–415 V AC, making the 1SDA062722R1 particularly suitable for installations with high prospective short-circuit currents.
The PR231/P LS/I electronic trip unit combines long-time overload protection with short-time and instantaneous short-circuit protection. Its adjustable overload setting supports coordination with the protected circuit, while the breaker’s high breaking capacity helps protect cables, switchgear and downstream electrical equipment during severe fault conditions.
| Series | SACE Tmax T7 |
|---|---|
| Order code | 1SDA062722R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Trip unit | PR231/P LS/I electronic release |
| Release type | Electronic (EL) |
| Protection functions | Long-time, short-time and instantaneous |
| Overload adjustment range | 320–800 A |
| Short-circuit performance level | V |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–230 V AC | 200 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 380–415 V AC | 150 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 100 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 60 kA |
| Rated service short-circuit breaking capacity (Ics) at 380–415 V AC | 150 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 45 kA |
| Rated short-time withstand current (Icw) | 15 kA for 1 s |
| Installation | Fixed |
| Terminal connection | Front |
| Operating mechanism | Stored-energy |
| Electrical durability | 3000 operating cycles |
| Mechanical durability | 10,000 operating cycles |
| Power loss | 32 W per pole at rated operating conditions |
| Standard | IEC |
| EAN | 8015644652715 |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA062722R1 is a SACE Tmax T7V 800 three-pole fixed moulded case circuit breaker rated at 800 A and fitted with a PR231/P LS/I electronic trip unit.
The breaker has a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, providing high fault-interruption capability for demanding distribution systems.
The PR231/P LS/I electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The overload release can be adjusted over a range of 320–800 A, allowing the protection setting to be matched to the requirements of the protected circuit.
The 1SDA062722R1 is a fixed three-pole circuit breaker with front terminals and a stored-energy operating mechanism.
ABB SACE Tmax T7 moulded case circuit breakers combine high-current capability, advanced electronic protection and substantial short-circuit breaking performance for dependable protection of demanding industrial and commercial low-voltage distribution systems.