1SDA062716R1 ABB T7V 800 PR331/P LSIG 4P 800 A Circuit Breaker

1SDA062716R1 ABB T7V 800 PR331/P LSIG 4P 800 A Circuit Breaker

ABB 1SDA062716R1 is an 800 A four-pole SACE Tmax T7V fixed moulded case circuit breaker with front terminals, a PR331/P electronic trip unit, LSIG protection and 150 kA ultimate breaking capacity at 380-415 V AC.

SKU: 1SDA062716R1MPN: 1SDA062716R1
Price
List Price £12,410.45 ex VAT
Your Price (ex VAT) Save 25%
£9,307.84 25% OFF
You save £3,102.61 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,307.84
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,307.84

Why Choose the ABB 1SDA062716R1 T7V 800 Circuit Breaker?

The ABB 1SDA062716R1 is a high-performance four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax T7 range, engineered for demanding low-voltage power distribution applications. Identified as T7V 800 PR331/P LSIG In=800A 4P F F, it combines an 800 A rated current with ABB's PR331/P electronic trip unit and high short-circuit interruption capability.

The PR331/P electronic trip unit provides comprehensive LSIG protection, incorporating long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection. The overload release is adjustable from 320–800 A, while short-time and instantaneous protection settings provide flexibility for coordinating the breaker with upstream and downstream protection devices.

The 1SDA062716R1 is a four-pole fixed circuit breaker with front terminals and lever operating mechanism. Its T7V construction provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, making it particularly suitable for industrial switchboards and main distribution systems with high prospective fault currents.

Key Advantages

  • High-performance ABB SACE Tmax T7V moulded case circuit breaker.
  • 800 A rated current for high-current low-voltage distribution.
  • High 150 kA ultimate breaking capacity at 380–415 V AC.
  • PR331/P electronic trip unit with adjustable protection settings.
  • Comprehensive LSIG protection against overload, short-circuit and earth-fault conditions.
  • Four-pole configuration for three-phase and neutral distribution systems.
  • Fixed installation with front terminals for practical switchboard integration.

Key Features

  • ABB SACE Tmax T7V 800 circuit breaker.
  • 800 A rated uninterrupted current.
  • Four-pole (4P) configuration.
  • PR331/P electronic trip unit.
  • LSIG protection functions.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated ground-fault protection.
  • Fixed (F) circuit breaker execution.
  • Front terminals (F).
  • Lever operating mechanism for manual switching.

PR331/P LSIG Electronic Circuit Protection

The PR331/P electronic trip unit provides four complementary protection functions. The L function protects against sustained overloads, the S function provides delayed short-circuit protection for selective coordination, and the I function provides rapid interruption of severe short-circuit currents. The additional G function provides protection against earth-fault conditions.

Combined with the high-breaking-capacity T7V 800 platform, these LSIG functions make the ABB 1SDA062716R1 suitable for main and feeder circuits where protection coordination and high fault interruption capability are important. Its four-pole configuration also supports three-phase and neutral distribution systems, while the fixed front-terminal construction facilitates integration into compatible low-voltage switchboards.

Typical Applications

  • Industrial low-voltage main distribution boards.
  • High-current feeder and sub-main protection.
  • Four-pole three-phase and neutral distribution systems.
  • Manufacturing and process plant switchboards.
  • Commercial building electrical distribution.
  • Infrastructure and utility distribution assemblies.
  • Installations requiring electronic ground-fault protection.

Technical Specifications

Series SACE Tmax T7
Order code / MPN 1SDA062716R1
Product group 310511-T-Max T4 - T8
Product type Moulded case circuit breaker
Breaker designation T7V 800
Frame size T7
Rated uninterrupted current (Iu) 800 A
Number of poles 4
Trip unit PR331/P
Trip technology Electronic / solid-state
Protection functions LSIG
Long-time protection L
Short-time protection S
Instantaneous protection I
Ground-fault protection G
Overload release setting range 320–800 A
Short-time delayed short-circuit setting range 480–8000 A
Instantaneous short-circuit setting range 1200–12000 A
Rated operational voltage 690 V AC
Ultimate breaking capacity (Icu) at 220–230 V AC 200 kA
Ultimate breaking capacity (Icu) at 380–415 V AC 150 kA
Ultimate breaking capacity (Icu) at 440 V AC 130 kA
Ultimate breaking capacity (Icu) at 500 V AC 100 kA
Ultimate breaking capacity (Icu) at 690 V AC 60 kA
Installation type Fixed
Terminal configuration Front terminals
Operating mechanism Lever operated
Degree of protection IP20
EAN 8015644652654
Application Low-voltage power distribution protection

Frequently Asked Questions

What is the ABB 1SDA062716R1?

The ABB 1SDA062716R1 is an 800 A four-pole SACE Tmax T7V moulded case circuit breaker with a PR331/P electronic trip unit, LSIG protection, fixed installation and front terminals.

What protection functions does the ABB 1SDA062716R1 provide?

The PR331/P trip unit provides LSIG protection: long-time overload protection (L), short-time short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault protection (G).

What is the breaking capacity of the ABB 1SDA062716R1?

The breaker provides an ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC, with voltage-dependent breaking capacities ranging up to 200 kA at 220–230 V AC.

What protection adjustment ranges are available on the ABB 1SDA062716R1?

The overload release can be adjusted from 320–800 A, the short-time delayed short-circuit release from 480–8000 A, and the instantaneous short-circuit release from 1200–12000 A.

What does F F mean in T7V 800 PR331/P LSIG 4P F F?

The F F designation identifies a fixed circuit breaker with front terminals, designed for permanent installation within a compatible low-voltage switchboard or distribution assembly.

Trusted ABB Circuit Protection

ABB SACE Tmax moulded case circuit breakers combine high short-circuit interruption performance with advanced electronic protection, providing dependable switching and circuit protection for demanding industrial, commercial and infrastructure power distribution systems.