ABB 1SDA062712R1 T7V 800 fixed three-pole 800 A moulded-case circuit breaker with front terminals, PR332/P LSIRc electronic protection and 150 kA ultimate breaking capacity at 380–415 V AC.
£8,173.28
The ABB 1SDA062712R1 is a high-performance SACE Tmax T7V 800 moulded-case circuit breaker designed for demanding low-voltage power distribution systems. Rated at 800 A, this three-pole breaker combines fixed installation, front terminals and an advanced PR332/P LSIRc electronic trip unit for overload, selective short-circuit, instantaneous short-circuit and residual-current protection.
The T7V performance level provides exceptional fault-clearing capability, including a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. The breaker is rated for operation up to 690 V AC, making it suitable for high-capacity industrial and commercial distribution networks where substantial prospective fault currents may be present.
The PR332/P LSIRc trip unit combines adjustable long-time, short-time and instantaneous overcurrent protection with an integrated residual-current function. With an 800 A rated current, three-pole construction, fixed mounting and front connections, the 1SDA062712R1 provides a comprehensive protection solution for main switchboards, distribution feeders and critical industrial power systems.
The PR332/P LSIRc electronic trip unit provides multiple protection functions within a single circuit-breaker platform. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short circuits, instantaneous protection provides rapid interruption of severe faults, and the residual-current function provides additional protection by monitoring current leakage towards earth.
Combined with the T7V breaker's 150 kA Icu at 380–415 V AC, these protection functions make the 1SDA062712R1 particularly suitable for high-capacity distribution networks where both substantial short-circuit performance and residual-current monitoring are required. Its fixed construction and front bolted connections provide a robust arrangement for permanent integration into industrial and commercial switchboards.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062712R1 |
| Product type | Moulded-case circuit breaker |
| Performance level | V |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Trip unit | PR332/P LSIRc |
| Trip unit technology | Electronic |
| Protection functions | LSIRc |
| Long-time protection | L |
| Short-time delayed protection | S |
| Instantaneous protection | I |
| Residual-current protection | Rc |
| Overload protection setting range | 320–800 A |
| Short-time delayed short-circuit setting range | 480–8000 A |
| Instantaneous short-circuit setting range | 1200–12000 A |
| Residual-current setting range | 0.2–1 × In |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Icu at 220–230 V AC | 200 kA |
| Icu at 380–415 V AC | 150 kA |
| Icu at 440 V AC | 130 kA |
| Icu at 500 V AC | 100 kA |
| Icu at 690 V AC | 60 kA |
| Ics at 380–415 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 15 kA |
| Mounting type | Fixed |
| Terminal connection | Front |
| Main circuit connection | Bolted connection |
| Degree of protection | IP20 |
| Electrical durability | 3000 cycles |
| Mechanical durability | 10000 cycles |
| Power loss at rated conditions | 32 W per pole |
| Product width | 210 mm |
| Product height | 268 mm |
| Product depth | 154 mm |
| Net weight | 9.7 kg |
| Standards | IEC |
| EAN | 8015644652616 |
| Customs tariff number | 85362090 |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA062712R1 is a Tmax T7V 800 three-pole moulded-case circuit breaker rated at 800 A, with fixed front terminals and a PR332/P LSIRc electronic trip unit.
LSIRc combines long-time overload protection (L), short-time delayed protection (S), instantaneous short-circuit protection (I) and residual-current protection (Rc).
The T7V 800 has a rated ultimate short-circuit breaking capacity (Icu) of 150 kA at 380–415 V AC. Its Icu is 200 kA at 220–230 V AC, 130 kA at 440 V AC, 100 kA at 500 V AC and 60 kA at 690 V AC.
The PR332/P LSIRc configuration provides an overload setting range of 320–800 A, a short-time delayed short-circuit setting range of 480–8000 A and an instantaneous short-circuit setting range of 1200–12000 A.
The 1SDA062712R1 is a fixed three-pole circuit breaker with front-positioned bolted main connections, designed for permanent integration into compatible low-voltage switchboards and power distribution assemblies.
ABB SACE Tmax circuit breakers provide industrial and commercial power distribution systems with high breaking performance, adjustable electronic protection and integrated protection options for demanding low-voltage switchgear applications.