Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA062711R1 T7V 800 fixed three-pole 800 A moulded-case circuit breaker with front terminals, PR332/P LSIG electronic protection and 150 kA ultimate breaking capacity at 380–415 V AC.
£8,106.36
The ABB 1SDA062711R1 is a high-performance SACE Tmax T7V 800 moulded-case circuit breaker designed for demanding low-voltage power distribution systems. Rated at 800 A, this three-pole breaker combines fixed installation, front terminals and an advanced PR332/P LSIG electronic trip unit for comprehensive overload, short-circuit and earth-fault protection.
The T7V performance level provides exceptionally high fault-clearing capability, with a rated ultimate short-circuit breaking capacity of 150 kA at 380–415 V AC. The breaker is also rated for operation up to 690 V AC, making it suitable for high-capacity industrial and commercial distribution networks where substantial prospective fault currents may be present.
The PR332/P LSIG trip unit provides long-time overload protection, selective short-time protection, instantaneous short-circuit protection and earth-fault protection. Combined with its 800 A rated current, three-pole construction and fixed front-terminal configuration, the 1SDA062711R1 provides a robust protection solution for main switchboards, distribution feeders and critical industrial power systems.
The PR332/P LSIG electronic trip unit provides four complementary protection functions for demanding distribution networks. Long-time protection responds to sustained overload conditions, short-time protection enables selective coordination during short circuits, instantaneous protection provides rapid interruption of severe faults, and the earth-fault function detects potentially damaging current flowing outside the intended phase conductors.
Combined with the T7V breaker's exceptional 150 kA Icu at 380–415 V AC, these LSIG functions make the 1SDA062711R1 particularly suitable for high-capacity distribution networks close to transformers or other sources capable of delivering substantial fault currents. Its fixed front-terminal configuration provides a robust arrangement for permanent integration into industrial and commercial switchboards.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062711R1 |
| Product type | Moulded-case circuit breaker |
| Performance level | V |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Trip unit | PR332/P LSIG |
| Trip unit type | Electronic |
| Protection functions | LSIG |
| Long-time protection | L |
| Short-time selective protection | S |
| Instantaneous protection | I |
| Earth-fault protection | G |
| Long-time protection setting range | 320–800 A |
| Instantaneous short-circuit setting range | 1200–12000 A |
| Earth-fault setting range | 0.2–1 × In |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Icu at 220–230 V AC | 200 kA |
| Icu at 380–415 V AC | 150 kA |
| Icu at 440 V AC | 130 kA |
| Icu at 500 V AC | 100 kA |
| Icu at 690 V AC | 60 kA |
| Ics at 380–415 V AC | 150 kA |
| Rated short-time withstand current (Icw), 1 s | 15 kA |
| Mounting type | Fixed |
| Terminal connection | Front terminals |
| Operation | Manual |
| Product width | 210 mm |
| Product height | 268 mm |
| Product depth | 154 mm |
| Net weight | 9.7 kg |
| Standards | IEC |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA062711R1 is a Tmax T7V 800 three-pole moulded-case circuit breaker rated at 800 A, with fixed front terminals and a PR332/P LSIG electronic trip unit.
The T7V 800 has a rated ultimate short-circuit breaking capacity (Icu) of 150 kA at 380–415 V AC. Its Icu is 200 kA at 220–230 V AC, 130 kA at 440 V AC, 100 kA at 500 V AC and 60 kA at 690 V AC.
The circuit breaker is fitted with an ABB PR332/P LSIG electronic trip unit providing long-time overload, selective short-time, instantaneous short-circuit and earth-fault protection.
LSIG represents long-time overload protection (L), short-time selective protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G).
The 1SDA062711R1 is a fixed three-pole circuit breaker with front terminals, designed for permanent integration into compatible low-voltage switchboards and distribution assemblies.
ABB SACE Tmax circuit breakers provide industrial and commercial power distribution systems with high breaking performance, adjustable electronic protection and dependable integration into demanding low-voltage switchgear applications.