ABB 1SDA062703R1 is a SACE Tmax T7L 800 A four-pole fixed moulded case circuit breaker with front terminals, a PR332/P LSIG electronic trip unit, stored-energy operating mechanism and 120 kA ultimate breaking capacity at 380–415 V AC.
£10,626.15
The ABB 1SDA062703R1 is a high-performance SACE Tmax T7L moulded case circuit breaker (MCCB) designed for protection and control of demanding low-voltage power distribution systems. Identified by ABB as T7L 800 PR332/P LSIG In=800A 4p F F M, it combines an 800 A rated current with the advanced PR332/P electronic trip unit and a stored-energy operating mechanism.
The T7L performance level provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, making the breaker suitable for industrial installations with high prospective fault currents. Its PR332/P LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection for comprehensive power distribution protection.
This configuration is a four-pole, fixed circuit breaker with front terminals, enabling switching and protection across all four poles in suitable three-phase distribution systems with neutral conductors. The PR332/P provides adjustable protection functions, while the stored-energy operating mechanism makes the breaker suitable for sophisticated industrial switchboards and power distribution assemblies.
Moulded case circuit breakers such as the ABB SACE Tmax T7L protect electrical distribution systems against potentially damaging overload, short-circuit and earth-fault conditions. The 1SDA062703R1 combines an 800 A rating with an ultimate breaking capacity of 120 kA at 380–415 V AC, providing robust protection for demanding industrial installations.
The integrated PR332/P LSIG electronic trip unit provides comprehensive adjustable protection. Long-time protection responds to sustained overloads, short-time protection supports selective fault coordination, instantaneous protection provides rapid response to severe short circuits, and earth-fault protection detects ground faults. Its four-pole construction additionally supports applications where the neutral conductor must form part of the circuit-breaker switching and protection arrangement.
| Series | SACE Tmax T7 |
|---|---|
| ABB order code | 1SDA062703R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame / breaker size | T7 800 |
| Short-circuit performance level | L |
| Rated current | 800 A |
| Overload protection adjustment | 0.4–1 × In |
| Ultimate short-circuit breaking capacity (Icu) | 200 kA at 220–230 V AC |
| Number of poles | 4 |
| Trip unit | PR332/P LSIG electronic trip unit |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) and earth-fault (G) |
| Instantaneous protection adjustment | 1.5–15 × In |
| Earth-fault protection adjustment | 0.2–1 × In |
| Neutral protection settings | OFF / 50% / 100% / 200% |
| Installation | Fixed |
| Terminal configuration | Front terminals |
| Operating mechanism | Stored-energy mechanism |
| Dimensions (H × W × D) | approx. 268 × 235 × 178 mm |
| Weight | approx. 11.2 kg |
| Application | Power distribution protection and control |
| Product group | 310511 – T-Max T4 - T8 |
The ABB 1SDA062703R1 is an 800 A four-pole moulded case circuit breaker designed to protect and control low-voltage power distribution circuits against overload, short-circuit and earth-fault conditions.
The T7L configuration provides an ultimate short-circuit breaking capacity of 120 kA at 380–415 V AC, with breaking capacity varying according to the system voltage.
The circuit breaker is equipped with an ABB PR332/P LSIG electronic trip unit, providing long-time, short-time, instantaneous and earth-fault protection functions.
The 1SDA062703R1 is a four-pole (4P) circuit breaker, making it suitable for applications where switching and protection of the neutral conductor are required alongside the three phase conductors.
LSIG identifies long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault or ground-fault (G) protection functions.
ABB SACE Tmax moulded case circuit breakers combine high interruption performance with advanced electronic protection functions, providing dependable protection and control for demanding industrial and commercial power distribution systems.