Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA061852R1 Tmax T5S 600 A three-pole fixed motor circuit protector with PR221DS-I electronic magnetic release and front terminals for industrial motor protection applications.
The ABB 1SDA061852R1 is a high-performance Tmax T5S motor circuit protector (MCP) designed for dependable short-circuit protection in industrial motor control and power distribution applications. As part of the proven ABB SACE Tmax T series, this device is engineered for installations requiring robust protection, compact panel integration and recognised UL/CSA compliance.
This breaker features a PR221DS-I electronic magnetic release, providing instantaneous protection for motor circuits where overload protection is typically handled separately by the starter or motor protection device. Its fixed three-pole construction and front terminal arrangement make it suitable for integration into switchboards, motor control centres and OEM machinery panels.
With a 600 A rated uninterrupted current, 600 V AC rated operational voltage and ABB’s reliable Tmax T5S platform, the 1SDA061852R1 provides a strong solution for demanding industrial environments where safe and consistent motor circuit protection is essential.
Motor circuit protectors are used to provide fast protection against short-circuit faults in motor feeder circuits. When combined with suitable overload and control equipment, the ABB 1SDA061852R1 helps create a coordinated and reliable motor protection system for demanding industrial applications.
The Tmax T5S platform is designed for dependable operation in power distribution and motor control environments. Its compact moulded case construction, high durability and fixed front terminal arrangement make it well suited to panel builders and engineers working with industrial electrical systems.
Tick the specs you need, then view products that match.
| Current | 600 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 3-pole | |
| Device Type | MCCB | |
| Trip Unit | Electronic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T5S | |
| Model | T5S600 MCP-UL/CSA PR221DS-I In=600 3p FF | |
| Product ID | 1SDA061852R1 | |
| EAN | 8015644643393 | |
| Product type | Motor circuit protector / moulded case circuit breaker | |
| Rated current | 600 A | |
| Rated uninterrupted current | 600 A | |
| Rated operational voltage | 600 V AC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Number of poles | 3 | |
| Release | PR221DS-I | |
| Release type | Electronic magnetic release | |
| Short-circuit performance level | S | |
| Connection type | Front terminals | |
| Mounting type | Fixed | |
| Standards | UL / CSA | |
| Mechanical durability | 20,000 operating cycles | |
| Dimensions (H × W × D) | approx. 205 × 140 × 103.5 mm | |
| Weight | approx. 5.1 kg |
The ABB 1SDA061852R1 is used for short-circuit protection in industrial motor circuits, switchboards and motor control centre applications.
This model has a 600 A rated uninterrupted current, making it suitable for high-current motor protection applications.
It is fitted with a PR221DS-I electronic magnetic release for instantaneous fault protection.
The ABB 1SDA061852R1 is a three-pole fixed motor circuit protector with front terminals.
It is typically installed in motor control centres, industrial control panels, switchboards and OEM machinery systems.
ABB Tmax motor circuit protectors and moulded case circuit breakers are trusted by panel builders, electrical engineers and industrial facilities worldwide for reliable protection, durable construction and consistent performance in demanding motor control applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.