Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA060739R1 SACE Emax E3S-A 3200 A three-pole fixed air circuit breaker with PR122/P-LSI electronic long-time, short-time and instantaneous protection.
£16,144.85
The ABB 1SDA060739R1 is a SACE Emax E3S-A 3200 air circuit breaker designed for high-current low-voltage power distribution and protection. This three-pole fixed breaker combines a 3200 A rated current with ABB's advanced PR122/P-LSI electronic trip unit, providing long-time, short-time and instantaneous overcurrent protection.
Configured as a fixed three-pole breaker, the 1SDA060739R1 uses a VR-HR rear terminal arrangement for integration into compatible switchboards and busbar systems. The E3S-A frame provides a 65 kA short-circuit rating at 480 V, making this breaker suitable for substantial industrial and commercial distribution systems requiring high current capacity and dependable fault interruption.
The fitted PR122/P-LSI R3200 electronic release provides adjustable protection for coordinating the breaker with downstream and upstream protective devices. This configuration is identified with a 48,000 A instantaneous reference and combines ABB's Emax switching platform with electronic protection for demanding UL-oriented power distribution applications.
The ABB PR122/P-LSI electronic trip unit combines three important protection functions. The L function protects against sustained overloads, the S function provides short-time protection that can assist selective coordination between protective devices, and the I function provides rapid instantaneous intervention during severe short-circuit conditions.
This combination makes the 1SDA060739R1 well suited to high-current distribution systems where protection coordination is important. Together with the 3200 A rating and 65 kA short-circuit capability at 480 V, the E3S-A provides a robust switching and protection solution for major feeders, incomers and other high-capacity low-voltage circuits.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB detailed designation | E3S-A 3200 PR122/P LSI R3200 Im48000 3P F VR-HR UL |
| Order code / MPN | 1SDA060739R1 |
| Product type | Air circuit breaker |
| Frame | E3 |
| Performance level | S |
| Rated current (In) | 3200 A |
| Trip unit | PR122/P-LSI R3200 |
| Protection functions | L, S, I |
| Long-time protection | Yes |
| Short-time protection | Yes |
| Instantaneous protection | Yes |
| Instantaneous reference | 48,000 A |
| Short-circuit current rating at 480 V | 65 kA |
| Short-time current | 65 kA |
| Number of poles | 3P |
| Execution | Fixed |
| Terminal arrangement | VR-HR |
| Configuration | UL |
The ABB 1SDA060739R1 is a SACE Emax E3S-A 3200 A three-pole fixed air circuit breaker fitted with a PR122/P-LSI R3200 electronic overcurrent release.
The fitted PR122/P-LSI trip unit provides long-time (L) overload protection, short-time (S) short-circuit protection and instantaneous (I) short-circuit protection.
The ABB 1SDA060739R1 has a rated current of 3200 A and uses a PR122/P-LSI R3200 electronic trip unit.
The E3S-A 3200 configuration has a 65 kA short-circuit rating at 480 V and a 65 kA short-time current capability.
The 1SDA060739R1 is a fixed-version air circuit breaker with a VR-HR rear terminal arrangement, intended for permanent installation within a compatible switchboard.
ABB SACE Emax air circuit breakers combine high-current switching capability with configurable electronic protection, providing dependable overload and short-circuit protection for demanding industrial, commercial and infrastructure power distribution systems.