Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA060697R1 is an 800 A three-pole withdrawable SACE Emax E2N-A air circuit breaker with a PR121/P electronic LSI trip unit and a 50 kA service short-circuit breaking capacity at 480 V AC.
£7,360.25
The ABB E2N-A 800 PR121/P-LSI In=800A 3p W, order code 1SDA060697R1, is a SACE Emax E2N-A withdrawable air circuit breaker engineered for industrial low-voltage power distribution. It combines an 800 A rated current with ABB's electronic PR121/P-LSI trip unit, providing configurable protection for demanding switchboard, feeder and main distribution applications.
This circuit breaker uses a three-pole withdrawable configuration, allowing the breaker body to be racked into and out of a compatible fixed part. The withdrawable execution simplifies inspection, maintenance and replacement compared with permanently mounted configurations and is particularly valuable in switchgear where serviceability and reduced maintenance disruption are important.
The integrated PR121/P electronic release provides LSI protection, combining long-time overload, short-time short-circuit and instantaneous short-circuit protection. The E2N-A platform provides substantial short-circuit performance, including a rated service short-circuit breaking capacity of 50 kA at 480 V AC, making the 1SDA060697R1 a capable solution for demanding industrial power distribution.
The ABB E2N-A platform combines the robust switching architecture of the SACE Emax family with electronic protection for demanding industrial distribution systems. In this withdrawable version, the circuit breaker can be moved between operating, test and disconnected positions within a compatible fixed part, supporting safer and more efficient inspection and maintenance procedures.
Its PR121/P-LSI release provides long-time, short-time and instantaneous protection against overload and short-circuit conditions. Combined with an 800 A current rating and 50 kA service short-circuit breaking capacity at 480 V AC, the 1SDA060697R1 provides a strong combination of protection performance, serviceability and switchgear integration.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA060697R1 |
| Product type | Air circuit breaker |
| Sub-type / frame | E2N-A |
| Frame size | 800 A |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational current (Ie) | 800 A |
| Rated voltage (Ur) | 600 V |
| Number of poles | 3P |
| Execution | Withdrawable (W) |
| Trip unit | PR121/P |
| Release type | Electronic |
| Protection functions | LSI – Long-time, Short-time, Instantaneous |
| Rated service short-circuit breaking capacity (Ics) at 240 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 480 V AC | 50 kA |
| Rated service short-circuit breaking capacity (Ics) at 600 V AC | 50 kA |
| Short-time current capability | 50 kA |
| Mounting system | Withdrawable breaker for compatible fixed part |
| Standard | UL 1066 |
| Product group | 310513 – New Emax |
The ABB 1SDA060697R1 is a SACE Emax E2N-A three-pole withdrawable air circuit breaker rated at 800 A and equipped with a PR121/P electronic trip unit providing LSI protection.
The PR121/P-LSI release provides long-time (L), short-time (S) and instantaneous (I) protection functions for overload and short-circuit protection.
The E2N-A configuration provides a rated service short-circuit breaking capacity of 65 kA at 240 V AC and 50 kA at both 480 V AC and 600 V AC.
The ABB 1SDA060697R1 is a withdrawable (W) air circuit breaker designed for use with a compatible E2 fixed part, allowing the breaker body to be racked out for inspection, servicing or replacement.
The circuit breaker has a three-pole (3P) configuration for three-phase industrial power distribution applications.
ABB SACE Emax air circuit breakers are engineered for demanding electrical distribution applications where dependable fault interruption, electronic protection and serviceable withdrawable switchgear integration are required.