Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA060643R1 is a fixed three-pole Tmax T5L 400 A UL/CSA moulded-case circuit breaker with front terminals, a TMA thermomagnetic release and 100 kA ultimate breaking capacity at 400 V AC, 50 Hz.
£3,198.32
The ABB 1SDA060643R1 is a Tmax T5L 400 moulded-case circuit breaker (MCCB) designed for dependable protection and switching in demanding low-voltage power distribution systems. This UL/CSA configuration is supplied as a fixed three-pole breaker with front terminals and an ABB TMA thermomagnetic trip unit.
Rated at 400 A, the T5L 400 combines thermal overload protection with adjustable instantaneous magnetic short-circuit protection. The overload release can be set from 280–400 A, while the instantaneous short-circuit release is adjustable from 2000–4000 A, allowing the breaker protection to be matched to the requirements of the installation.
The T5L performance level provides a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, 50 Hz. Together with its 600 V rated voltage, fixed construction and front bolted connections, the 1SDA060643R1 is well suited to industrial switchboards, commercial distribution equipment and high-fault-level electrical systems.
A thermomagnetic circuit breaker combines two complementary protection principles. The thermal element responds to sustained overload conditions, while the magnetic element operates rapidly when a high short-circuit current is detected. This provides straightforward and dependable protection without requiring an electronic trip unit.
The ABB 1SDA060643R1 uses a TMA 400 A thermomagnetic release with adjustable overload and instantaneous protection thresholds. Combined with the T5L breaker's 100 kA Icu at 400 V AC, this makes it particularly suitable for distribution circuits where both high fault interruption capability and adjustable conventional protection are required.
| Series | SACE Tmax T5 |
|---|---|
| Order code | 1SDA060643R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Breaker designation | T5L 400 |
| Rated uninterrupted current (Iu) | 400 A |
| Number of poles | 3 |
| Trip unit | TMA thermomagnetic release |
| Overload release adjustment range | 280–400 A |
| Instantaneous short-circuit release adjustment range | 2000–4000 A |
| Rated voltage | 600 V |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 100 kA |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Mounting type | Fixed |
| Main connection position | Front |
| Main-circuit connection | Bolted connection |
| Operating element | Toggle handle |
| Complete device with protection unit | Yes |
| Integrated motor operator | No |
| Optional motor operator | Yes |
| Integrated earth-fault protection | No |
| Degree of protection | IP20 |
| Power loss per pole at rated operating conditions | 19.5 W |
| Mechanical durability | 20,000 cycles |
| Maximum mechanical operating rate | 120 cycles per hour |
| Dimensions (W × H × D) | 140 × 205 × 103.5 mm |
| Net weight | 3.25 kg |
| EAN / GTIN | 8015644631581 |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA060643R1 is a Tmax T5L 400 A three-pole moulded-case circuit breaker with fixed mounting, front terminals and a TMA thermomagnetic protection release.
The breaker has a rated uninterrupted current of 400 A, with its thermal overload release adjustable from 280–400 A.
The TMA magnetic short-circuit release is adjustable from 2000–4000 A, providing instantaneous protection against high fault currents.
The breaker has a rated ultimate short-circuit breaking capacity of 100 kA at 400 V AC, 50 Hz.
Yes. The 1SDA060643R1 is a complete three-pole Tmax T5L circuit breaker with its TMA thermomagnetic protection unit, supplied in a fixed configuration with front main-circuit connections.
ABB SACE Tmax moulded-case circuit breakers combine robust switching technology with coordinated overload and short-circuit protection, providing dependable circuit protection for demanding industrial, commercial and infrastructure power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.