1SDA060321R1 ABB T6L 630 PR222DS/P-LSI 630 A 3P 1000 V AC Moulded-Case Circuit Breaker

1SDA060321R1 ABB T6L 630 PR222DS/P-LSI 630 A 3P 1000 V AC Moulded-Case Circuit Breaker

ABB 1SDA060321R1 is a 630 A three-pole fixed Tmax T6L moulded-case circuit breaker for 1000 V AC applications with front terminals and a PR222DS/P-LSI electronic trip unit providing long-time, short-time and instantaneous protection.

SKU: 1SDA060321R1MPN: 1SDA060321R1
Price
List Price £7,800.58 ex VAT
Your Price (ex VAT) Save 25%
£5,850.44 25% OFF
You save £1,950.15 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,850.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,850.44

Why Choose the ABB T6L 630 1SDA060321R1 Moulded-Case Circuit Breaker?

The ABB 1SDA060321R1 is a high-performance Tmax T6L 630 three-pole moulded-case circuit breaker (MCCB) designed for demanding low-voltage AC power distribution applications operating at voltages up to 1000 V AC. As part of the ABB Tmax T4–T8 range, it combines a rated uninterrupted current of 630 A with the PR222DS/P-LSI electronic trip unit and the high-voltage capability of the T6L platform.

The PR222DS/P-LSI electronic trip unit provides long-time, short-time and instantaneous protection functions. This LSI protection arrangement protects electrical circuits against sustained overloads and short-circuit faults while providing adjustable electronic settings that support effective protection coordination within industrial and commercial distribution systems.

The 1SDA060321R1 is supplied as a fixed, three-pole circuit breaker with front terminals. At 1000 V AC, the T6L 630 provides a rated ultimate short-circuit breaking capacity of 12 kA and a rated service short-circuit breaking capacity of 6 kA, making it a purpose-designed solution for high-voltage AC distribution systems requiring reliable ABB electronic circuit protection.

Key Advantages

  • High-performance ABB Tmax T6L 630 moulded-case circuit breaker.
  • 630 A rated uninterrupted current for high-current distribution applications.
  • Designed for operation at up to 1000 V AC.
  • Advanced PR222DS/P-LSI electronic trip unit.
  • LSI protection covering long-time, short-time and instantaneous fault conditions.
  • Fixed three-pole configuration with front terminals for switchboard integration.

Key Features

  • ABB Tmax T6L 630 circuit-breaker platform.
  • PR222DS/P-LSI electronic solid-state release.
  • 630 A rated current (In).
  • 378–6300 A short-time delayed short-circuit setting range.
  • 945–7560 A instantaneous short-circuit setting range.
  • Three-pole (3P) construction.
  • Fixed execution with front terminals.
  • 1000 V AC rated operational voltage.

Advanced LSI Protection for 1000 V AC Distribution

Electronic moulded-case circuit breakers monitor circuit current and initiate tripping when configured protection thresholds are exceeded. The PR222DS/P-LSI release provides long-time protection against sustained overloads together with short-time and instantaneous functions for short-circuit protection, allowing effective coordination between protective devices within a distribution system.

The ABB T6L 630 configuration used in the 1SDA060321R1 is specifically designed for applications operating at up to 1000 V AC. Its 630 A current rating, adjustable LSI electronic protection and 12 kA Icu at 1000 V AC make it suitable for specialised industrial power distribution installations requiring reliable protection at elevated AC voltages.

Typical Applications

  • Industrial power distribution systems operating up to 1000 V AC.
  • High-voltage AC feeder protection.
  • Industrial switchboards and distribution panels.
  • Manufacturing and process industry electrical systems.
  • Specialised 1000 V AC distribution installations.
  • Three-phase circuits requiring adjustable LSI electronic protection.

Technical Specifications

Series Tmax T4–T8
Order code 1SDA060321R1
Product type Moulded-case circuit breaker (MCCB)
Frame T6
Performance level L
Rated current (In) 630 A
Rated uninterrupted current (Iu) 630 A
Trip unit PR222DS/P-LSI electronic / solid-state release
Protection functions Long-time, short-time and instantaneous (LSI)
Short-time delayed short-circuit setting 378–6300 A
Instantaneous short-circuit setting 945–7560 A
Number of poles 3
Execution Fixed
Terminal connection Front
Rated operational voltage 1000 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) at 1000 V AC 12 kA
Rated service short-circuit breaking capacity (Ics) at 1000 V AC 6 kA
Test voltage 3500 V
Protection rating IP20
Control element Toggle
Power loss at rated operating conditions 20 W per pole
Dimensions (W × H × D) 210 × 268 × 103.5 mm
Product net weight 9.5 kg
Mechanical durability 20,000 cycles
Electrical durability 7,000 cycles
Standard IEC
EAN 8015644627898
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA060321R1 used for?

The ABB 1SDA060321R1 is a Tmax T6L 630 three-pole moulded-case circuit breaker designed to protect AC power distribution circuits operating at voltages up to 1000 V AC.

What is the current rating of the ABB 1SDA060321R1?

The circuit breaker has a rated uninterrupted current of 630 A.

What does LSI mean on the ABB PR222DS/P-LSI trip unit?

LSI denotes long-time (L), short-time (S) and instantaneous (I) protection, providing electronic protection against sustained overloads and short-circuit fault conditions.

What is the breaking capacity of the ABB 1SDA060321R1 at 1000 V AC?

The T6L 630 has a rated ultimate short-circuit breaking capacity (Icu) of 12 kA at 1000 V AC and a rated service short-circuit breaking capacity (Ics) of 6 kA at 1000 V AC.

What does 3P F F mean on the ABB T6L 630?

The designation identifies a three-pole circuit breaker in fixed execution with front terminals, designed for permanent installation in compatible electrical switchboards and distribution assemblies.

Trusted ABB Circuit Protection

ABB Tmax moulded-case circuit breakers provide dependable protection for demanding industrial power distribution systems, combining robust breaker construction, configurable electronic protection and specialised solutions for installations operating at elevated AC voltages.