Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA060314R1 is a three-pole fixed SACE Tmax T6L 800 moulded case circuit breaker with front terminals, a 630 A Ekip M-LRIU electronic motor-protection release and 100 kA ultimate breaking capacity at 380/400/415 V AC.
£5,562.93
The ABB 1SDA060314R1 is a genuine SACE Tmax T6L moulded case circuit breaker for motor protection. Identified in current ABB documentation as T6L 800 Ekip M-LRIU In=630 3p F F, and also associated with the earlier PR222MP-LRIU designation, it combines a T6L 800 frame with a 630 A electronic release, three-pole construction, fixed installation and front terminals.
The integrated Ekip M-LRIU electronic trip unit is specifically designed for motor applications and provides multiple protection functions. These include overload protection (L), locked-rotor protection (R), instantaneous short-circuit protection (I) and phase-unbalance protection (U). The overload threshold is adjustable from 0.4–1 × In, while the instantaneous magnetic threshold is adjustable from 6–13 × In.
The T6L performance level provides high short-circuit interruption capability, including an ultimate short-circuit breaking capacity of 100 kA at 380/400/415 V AC. With its 630 A release rating, motor-specific electronic protection and fixed three-pole construction, the ABB 1SDA060314R1 is suited to demanding industrial motor feeders, process equipment and motor control applications.
Motor circuits have protection requirements that differ from conventional distribution feeders because high starting currents must be distinguished from genuine overload, locked-rotor and short-circuit conditions. The Ekip M-LRIU release fitted to the ABB 1SDA060314R1 provides dedicated protection functions for these conditions, combining overload, locked-rotor, instantaneous short-circuit and phase-unbalance monitoring in a single electronic trip unit.
The release has a nominal current of 630 A, with overload adjustment from 0.4–1 × In, locked-rotor protection adjustable from 3–9 × In and instantaneous short-circuit protection adjustable from 6–13 × In. Combined with the T6L platform's 100 kA breaking capacity at 380/400/415 V AC, this provides robust protection for large industrial motors and associated feeder circuits.
| Series | SACE Tmax T |
|---|---|
| Product group | 310511-T-Max T4 - T8 |
| Authoritative designation | T6L800 PR222MP-LRIU In=630 3p F F |
| Current ABB designation | T6L 800 Ekip M-LRIU In=630 3p F F |
| Order code | 1SDA060314R1 |
| Product type | Moulded case circuit breaker for motor protection |
| Frame | Tmax T6L 800 |
| Short-circuit performance level | L |
| Rated uninterrupted current Iu | 800 A |
| Release rated current In | 630 A |
| Trip-unit type | Ekip M-LRIU electronic / solid-state release |
| Protection functions | L / R / I / U |
| Overload protection setting | 0.4–1 × In |
| Locked-rotor protection setting | 3–9 × In |
| Instantaneous short-circuit setting | 6–13 × In |
| Phase-unbalance protection | ON / OFF |
| Number of poles | 3 |
| Execution | Fixed |
| Main-circuit connection position | Front |
| Terminal connection | Front terminals |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Ultimate short-circuit breaking capacity | 200 kA at 220/230 V AC |
| Service short-circuit breaking capacity | 75 kA at 380/400/415 V AC |
| Rated short-time withstand current Icw | 10 kA for 1 s |
| Power loss | 32 W per pole at rated operating conditions |
| Standard | IEC |
| Product net width | 210 mm |
| Product net height | 268 mm |
| Product net depth | 103.5 mm |
| Product net weight | 9.5 kg |
| EAN | 8015644627829 |
| Customs tariff number | 85362090 |
The ABB 1SDA060314R1 is a Tmax T6L 800 three-pole fixed moulded case circuit breaker with front terminals and a 630 A Ekip M-LRIU electronic release designed for motor protection.
The Ekip M-LRIU release provides overload (L), locked-rotor (R), instantaneous short-circuit (I) and phase-unbalance (U) protection for compatible AC motor circuits.
The overload threshold is adjustable from 0.4–1 × In, locked-rotor protection from 3–9 × In, and instantaneous short-circuit protection from 6–13 × In, while phase-unbalance protection can be switched ON or OFF.
The ABB 1SDA060314R1 has an ultimate short-circuit breaking capacity of 100 kA at 380/400/415 V AC, with voltage-dependent ratings reaching 200 kA at 220/230 V AC.
Yes. The Ekip M-LRIU electronic release is specifically intended for motor protection, providing dedicated overload, locked-rotor, instantaneous short-circuit and phase-unbalance protection functions.
ABB SACE Tmax motor-protection circuit breakers provide panel builders, electrical contractors and industrial operators with configurable electronic protection for large motors and demanding motor feeders, combining dedicated motor protection functions with high fault-current interruption capability.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.