1sda060271r1  t6n 800 pr222ds/p-lsig in=800 3 pole abb mccb

1sda060271r1 t6n 800 pr222ds/p-lsig in=800 3 pole abb mccb

ABB T6N 800 PR222DS/P-LSIG moulded case circuit breaker with 800 A rating, three poles and PR222DS/P-LSIG electronic trip unit for industrial low voltage power distribution.

SKU: 1SDA060271R1Alt SKU: T6N 800 PR222DS/P-LSIG In=800 3p F FMPN: 1SDA060271R1
Price
List Price £5,806.63 ex VAT
Your Price (ex VAT) Save 25%
£4,354.97 25% OFF
You save £1,451.66 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,354.97
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,354.97

Why Choose the ABB T6N 800 PR222DS/P-LSIG 1SDA060271R1 MCCB?

The ABB 1SDA060271R1 is a premium Tmax T6N moulded case circuit breaker (MCCB) designed to provide dependable protection for industrial and commercial low voltage power distribution systems. Featuring an 800 A rated current, a three-pole fixed configuration and the advanced PR222DS/P-LSIG electronic trip unit, it delivers comprehensive protection against overloads, short circuits and earth faults.

As part of the trusted ABB SACE Tmax T series, this circuit breaker combines excellent interrupting performance with intelligent electronic protection. The integrated LSIG functions provide precise long-time, short-time, instantaneous and ground fault protection, improving system selectivity, reducing unnecessary downtime and enhancing overall electrical system reliability.

With a 690 V AC rated operational voltage, front terminal connections and a robust fixed construction, the ABB 1SDA060271R1 is ideal for switchboards, motor control centres, industrial distribution boards and infrastructure projects requiring dependable high-current protection.

Key Advantages

  • High-performance 800 A moulded case circuit breaker for industrial power distribution.
  • Three-pole fixed construction with front terminal connections.
  • Advanced PR222DS/P-LSIG electronic trip unit with comprehensive LSIG protection.
  • Provides long-time, short-time, instantaneous and ground fault protection.
  • High short-circuit breaking performance for demanding installations.
  • Part of the proven ABB SACE Tmax T6N MCCB range.

Key Features

  • ABB SACE Tmax T6N moulded case circuit breaker.
  • Product code: 1SDA060271R1.
  • 800 A rated current.
  • Three-pole (3P) fixed version.
  • PR222DS/P-LSIG electronic trip unit.
  • Long-time, short-time, instantaneous and ground fault protection.
  • 690 V AC rated operational voltage.
  • Front terminal connections for straightforward installation.

Reliable Protection for Critical Electrical Systems

The ABB Tmax T6N range is designed to safeguard industrial electrical systems from overloads, short circuits and earth faults while maintaining maximum operational reliability. The PR222DS/P-LSIG electronic release enables accurate protection settings and selective coordination, helping reduce downtime and improve system availability.

Whether protecting feeders, transformers, generators or main distribution circuits, the ABB 1SDA060271R1 delivers dependable performance, long service life and consistent protection in demanding industrial environments.

Typical Applications

  • Industrial switchboards.
  • Main power distribution systems.
  • Motor control centres.
  • Commercial electrical installations.
  • Generator and transformer protection.
  • Manufacturing and process industries.
  • Infrastructure and utilities.

Technical Specifications

Tick the specs you need, then view products that match.

Current 800 A
Phase Three Phase
Poles 3-pole
Device Type MCCB
Breaking Capacity 36 kA
Trip Unit Electronic
Manufacturer ABB
Series SACE Tmax T
Model T6N 800 PR222DS/P-LSIG
Product code 1SDA060271R1
EAN 8015644627331
Product type Moulded Case Circuit Breaker (MCCB)
Rated current (In) 800 A
Rated uninterrupted current (Iu) 800 A
Number of poles 3
Trip unit PR222DS/P-LSIG electronic release
Protection functions Long-time, Short-time, Instantaneous and Ground Fault (LSIG)
Rated operational voltage Up to 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated service short-circuit breaking capacity (Ics) Up to 36 kA at 400 V AC
Rated ultimate short-circuit breaking capacity (Icu) Up to 36 kA at 400 V AC
Rated short-time withstand current (Icw) 10 kA for 1 second
Mounting type Fixed
Terminal type Front terminals
Protection rating IP20
Dimensions (H × W × D) 268 × 210 × 103.5 mm
Weight Approx. 9.5 kg

Frequently Asked Questions

What is the ABB 1SDA060271R1 used for?

This moulded case circuit breaker protects industrial electrical systems against overloads, short circuits and earth faults while ensuring reliable power distribution.

What current rating does this MCCB have?

The ABB 1SDA060271R1 has a rated current of 800 A.

What type of trip unit is fitted?

This model is fitted with the PR222DS/P-LSIG electronic trip unit, providing long-time, short-time, instantaneous and ground fault protection.

Is this a three-pole circuit breaker?

Yes. The ABB 1SDA060271R1 is supplied in a three-pole fixed configuration with front terminal connections.

Where is this breaker typically installed?

It is commonly installed in industrial switchboards, distribution panels, motor control centres and commercial power distribution systems.

Trusted by Electrical Engineers Worldwide

ABB SACE Tmax moulded case circuit breakers are trusted worldwide for delivering dependable circuit protection, excellent interruption performance and long service life across demanding industrial and commercial electrical installations.