Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA060263R1 is a 630 A four-pole fixed SACE Tmax T6L moulded case circuit breaker with front connections, a PR221DS-I electronic trip unit, 252–630 A overload adjustment, 1000–10000 A instantaneous short-circuit adjustment and 100 kA breaking capacity at 400 V AC.
£5,362.73
The ABB 1SDA060263R1 is a genuine SACE Tmax T6L moulded case circuit breaker designed for demanding low-voltage power distribution systems. Identified as T6L 630 PR221DS-I In=630 4p F F, it combines a 630 A rated current, four-pole construction, fixed installation and front terminals with ABB's PR221DS-I solid-state electronic protection technology.
The integrated PR221DS-I electronic trip unit provides overload and instantaneous short-circuit protection with adjustable settings for system coordination. The overload release can be adjusted from 252–630 A, while the instantaneous short-circuit release has an adjustment range of 1000–10000 A, enabling the protection characteristics to be matched to the requirements of the connected circuit.
The T6L performance level is intended for installations with high prospective fault currents, providing an ultimate short-circuit breaking capacity of 100 kA at 400 V AC. With its four-pole fixed configuration, front main-circuit connections and electronic protection, the ABB 1SDA060263R1 is well suited to industrial switchboards, commercial distribution systems and high-current power infrastructure.
Electronic trip units provide configurable circuit protection by electronically monitoring current and initiating circuit-breaker operation when programmed protection thresholds are exceeded. The PR221DS-I fitted to the ABB 1SDA060263R1 provides overload and instantaneous short-circuit protection, with the overload threshold adjustable from 252–630 A and the instantaneous short-circuit threshold adjustable from 1000–10000 A.
Combined with the T6L circuit-breaker platform, the PR221DS-I release provides a robust solution for systems where both adjustable electronic protection and high fault-current interruption are required. The breaker offers 100 kA ultimate breaking capacity at 400 V AC and a four-pole fixed construction, making it suitable for high-current industrial and commercial distribution equipment.
| Series | SACE Tmax T |
|---|---|
| Product group | 310511-T-Max T4 - T8 |
| Model / type | T6L 630 PR221DS-I In=630 4p F F |
| Order code | 1SDA060263R1 |
| Product type | Moulded case circuit breaker (MCCB) |
| Frame | Tmax T6 |
| Short-circuit performance level | L |
| Rated uninterrupted current Iu | 630 A |
| Trip-unit type | PR221DS-I electronic / solid-state release |
| Overload release setting | 252–630 A |
| Instantaneous short-circuit release setting | 1000–10000 A |
| Number of poles | 4 |
| Execution | Fixed |
| Main-circuit connection position | Front |
| Main-circuit connection type | Bolt connection |
| Rated voltage | 690 V |
| Ultimate short-circuit breaking capacity | 100 kA at 400 V AC |
| Degree of protection | IP20 |
| Operating element | Toggle |
| Complete with protection unit | Yes |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Integrated earth-leakage protection | No |
| EAN | 8015644627256 |
| Customs tariff number | 85362090 |
| Country of origin | Italy |
| Product weight | 14 kg |
The ABB 1SDA060263R1 is a 630 A four-pole SACE Tmax T6L moulded case circuit breaker with fixed installation, front connections and a PR221DS-I solid-state electronic trip unit.
The PR221DS-I provides electronic overload and instantaneous short-circuit protection, with an overload setting range of 252–630 A and an instantaneous short-circuit setting range of 1000–10000 A.
The ABB T6L 1SDA060263R1 has an ultimate short-circuit breaking capacity of 100 kA at 400 V AC, making it suitable for systems with high prospective fault currents.
The designation identifies a four-pole circuit breaker in a fixed execution with front main-circuit connections.
The ABB 1SDA060263R1 is typically used in industrial and commercial switchboards, transformer secondary protection, main distribution systems and other high-current installations requiring a 630 A four-pole MCCB with adjustable electronic protection and high short-circuit breaking capacity.
ABB SACE Tmax moulded case circuit breakers provide panel builders, electrical contractors and industrial operators with configurable electronic protection and high fault-current interruption capability for demanding low-voltage power distribution systems.
We use cookies