1SDA060258R1 ABB T6L 630 PR222DS/P-LSI 630 A 3P Fixed Moulded-Case Circuit Breaker

1SDA060258R1 ABB T6L 630 PR222DS/P-LSI 630 A 3P Fixed Moulded-Case Circuit Breaker

ABB 1SDA060258R1 is a three-pole fixed Tmax T6L 630 moulded-case circuit breaker with a 630 A rating, PR222DS/P-LSI electronic trip unit and 100 kA ultimate short-circuit breaking capacity at 400–415 V AC.

SKU: 1SDA060258R1MPN: 1SDA060258R1
Price
List Price £6,783.06 ex VAT
Your Price (ex VAT) Save 25%
£5,087.30 25% OFF
You save £1,695.77 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,087.30
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,087.30

Why Choose the ABB T6L 630 1SDA060258R1 Moulded-Case Circuit Breaker?

The ABB 1SDA060258R1 is a high-performance Tmax T6L 630 three-pole moulded-case circuit breaker (MCCB) designed for protection of demanding low-voltage industrial and commercial power distribution systems. As part of the ABB Tmax T4–T8 range, it combines a rated uninterrupted current of 630 A with the advanced PR222DS/P-LSI electronic trip unit and the high short-circuit performance of the T6L platform.

The PR222DS/P-LSI solid-state release provides long-time, short-time and instantaneous protection functions. This LSI protection arrangement enables the breaker to protect circuits against sustained overloads and short-circuit faults while offering adjustable protection settings for effective coordination with downstream equipment and the characteristics of the electrical installation.

The 1SDA060258R1 is supplied as a fixed, three-pole circuit breaker with front terminals and is rated for operation at up to 690 V AC. The T6L performance level provides a rated ultimate short-circuit breaking capacity of 100 kA at 400–415 V AC, making it particularly suitable for switchboards and distribution systems with high prospective fault currents.

Key Advantages

  • High-performance ABB Tmax T6L 630 moulded-case circuit breaker.
  • 630 A rated uninterrupted current for high-current distribution applications.
  • Advanced PR222DS/P-LSI electronic trip unit.
  • LSI protection covering long-time, short-time and instantaneous fault conditions.
  • High 100 kA Icu at 400–415 V AC short-circuit breaking capacity.
  • Fixed three-pole configuration with front terminals for switchboard integration.

Key Features

  • ABB Tmax T6L 630 circuit-breaker platform.
  • PR222DS/P-LSI electronic solid-state release.
  • 630 A rated uninterrupted current (Iu).
  • 252–630 A overload release setting range.
  • 378–6300 A short-time delayed short-circuit setting range.
  • 945–7560 A instantaneous short-circuit setting range.
  • Three-pole (3P) construction.
  • Fixed execution with front terminals.

Advanced LSI Protection for Power Distribution

Electronic moulded-case circuit breakers monitor current and initiate tripping when configured protection thresholds are exceeded. The PR222DS/P-LSI release provides dedicated long-time protection against sustained overloads together with short-time and instantaneous protection for short-circuit conditions, enabling effective coordination throughout a low-voltage distribution system.

The ABB T6L platform is designed for demanding installations with substantial prospective fault currents. With a rated uninterrupted current of 630 A, an Icu of 100 kA at 400–415 V AC and adjustable LSI protection, the 1SDA060258R1 provides a flexible protection solution for high-current feeders, industrial switchboards and commercial power distribution systems.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main feeder protection.
  • High-fault-level switchboards and distribution panels.
  • Manufacturing and industrial production facilities.
  • Commercial and infrastructure power distribution.
  • Three-phase circuits requiring adjustable LSI electronic protection.

Technical Specifications

Series Tmax T4–T8
Order code 1SDA060258R1
Product type Moulded-case circuit breaker (MCCB)
Frame T6
Performance level L
Rated uninterrupted current (Iu) 630 A
Trip unit PR222DS/P-LSI electronic / solid-state release
Protection functions Long-time, short-time and instantaneous (LSI)
Overload release setting 252–630 A
Short-time delayed short-circuit setting 378–6300 A
Instantaneous short-circuit setting 945–7560 A
Number of poles 3
Execution Fixed
Terminal connection Front
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 400–415 V AC 75 kA
Rated short-time withstand current (Icw) 7.6 kA for 1 s
Protection rating IP20
Control element Toggle
Main circuit connection Bolt connection
Dimensions (W × H × D) 210 × 268 × 103.5 mm
Product net weight 9.5 kg
Mechanical durability 20,000 cycles
Electrical durability 7,000 cycles
EAN 8015644627201
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA060258R1 used for?

The ABB 1SDA060258R1 is a Tmax T6L 630 three-pole moulded-case circuit breaker designed to protect high-current low-voltage distribution circuits using a PR222DS/P-LSI electronic trip unit.

What is the current rating of the ABB 1SDA060258R1?

The breaker has a rated uninterrupted current of 630 A, with its electronic overload protection adjustable over a 252–630 A range.

What does LSI mean on the ABB PR222DS/P-LSI trip unit?

LSI denotes long-time (L), short-time (S) and instantaneous (I) protection, providing coordinated protection against sustained overloads and different short-circuit fault conditions.

What is the breaking capacity of the ABB 1SDA060258R1?

The T6L 630 has a rated ultimate short-circuit breaking capacity (Icu) of 100 kA at 400–415 V AC and a rated service short-circuit breaking capacity (Ics) of 75 kA at 400–415 V AC.

What does 3P F F mean on the ABB T6L 630?

The designation identifies a three-pole circuit breaker in fixed execution with front terminals, designed for permanent installation in compatible low-voltage switchboards and distribution assemblies.

Trusted ABB Circuit Protection

ABB Tmax moulded-case circuit breakers provide dependable protection for demanding industrial and commercial low-voltage power distribution systems, combining robust breaker construction, configurable electronic protection and high short-circuit performance.