ABB 1SDA060223R1 T6S 800 TMA 800-8000 moulded case circuit breaker, fixed four-pole design with front terminals, fully rated neutral and thermomagnetic release for industrial low-voltage power distribution systems.
£4,632.94
The ABB 1SDA060223R1 is a high-performance SACE Tmax T6S moulded case circuit breaker designed for dependable protection of low-voltage power distribution systems. Supplied as a fixed four-pole circuit breaker with front terminals, it is suitable for demanding industrial switchboards, commercial distribution panels and electrical assemblies requiring reliable overload and short-circuit protection.
This breaker is part of the proven ABB Tmax T circuit breaker range, widely used by panel builders, electrical contractors and industrial engineers. It is fitted with a TMA thermomagnetic release, providing robust protection against overload and short-circuit conditions with an adjustable magnetic trip range for demanding AC and DC applications.
With a rated uninterrupted current of 800 A and a fully rated neutral configuration of InN = 100% In, the ABB 1SDA060223R1 is ideal for four-pole distribution systems where full neutral protection is required. Its compact T6 frame, strong breaking capacity and fixed front-terminal configuration make it a dependable choice for modern low-voltage installations.
Moulded case circuit breakers such as the ABB 1SDA060223R1 are used to protect electrical circuits, conductors and connected equipment from overloads and fault currents. By automatically interrupting abnormal current flow, they help protect switchgear, cables, machinery and downstream electrical devices.
The Tmax T6S range is designed for demanding industrial and commercial environments where high breaking performance, long service life and dependable operation are essential. With its fully rated neutral and thermomagnetic release, this MCCB is well suited to installations requiring four-pole disconnection and robust low-voltage protection.
Tick the specs you need, then view products that match.
| Current | 500 A | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | MCCB | |
| Breaking Capacity | 50 kA | |
| Trip Unit | Thermal-magnetic | |
| Manufacturer | ABB | |
| Series | SACE Tmax T | |
| Model | T6S 800 TMA 800-8000 4p F F InN=100%In | |
| Product ID / MPN | 1SDA060223R1 | |
| Product type | Moulded case circuit breaker | |
| Breaker type | Automatic circuit breaker | |
| Number of poles | 4P | |
| Rated current | 800 A | |
| Rated uninterrupted current | 800 A | |
| Neutral rating | InN = 100% In | |
| Rated operational voltage | 690 V AC / 750 V DC | |
| Rated insulation voltage | 1000 V | |
| Rated impulse withstand voltage | 8 kV | |
| Release | TMA | |
| Release type | Thermomagnetic | |
| Magnetic setting range | 4000-8000 A | |
| Short-circuit performance level | S | |
| Terminal connection | Fixed front terminals | |
| Rated ultimate breaking capacity at 415 V AC | 50 kA | |
| Rated short-time withstand current | 10 kA for 1 second | |
| Mechanical durability | 20,000 cycles | |
| Electrical durability | 5,000 cycles | |
| Power loss | 31 W per pole at rated conditions | |
| Dimensions (H × W × D) | approx. 268 × 280 × 103.5 mm | |
| Weight | approx. 12 kg | |
| EAN | 8015644626839 |
The ABB 1SDA060223R1 is used for circuit protection in low-voltage industrial and commercial power distribution systems.
This circuit breaker has a rated uninterrupted current of 800 A.
The ABB 1SDA060223R1 is a four-pole moulded case circuit breaker.
InN = 100% In means the neutral pole is fully rated, allowing the neutral to carry the same rated current as the phase poles.
It is fitted with a TMA thermomagnetic release, providing overload and short-circuit protection.
ABB Tmax moulded case circuit breakers are widely used by panel builders, electrical contractors and industrial engineers for reliable low-voltage protection, durable performance and dependable integration into power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.