1SDA060208R1 ABB T6L 630 TMA 630A 3P Fixed Moulded-Case Circuit Breaker

1SDA060208R1 ABB T6L 630 TMA 630A 3P Fixed Moulded-Case Circuit Breaker

ABB 1SDA060208R1 is a three-pole fixed Tmax T6L 630 moulded-case circuit breaker with a 630 A TMA thermomagnetic trip unit, adjustable 441–630 A overload protection and 3150–6300 A instantaneous short-circuit protection.

SKU: 1SDA060208R1Alt SKU: T6L630TMA630-63003MPN: 1SDA060208R1
Price
List Price £5,794.19 ex VAT
Your Price (ex VAT) Save 25%
£4,345.64 25% OFF
You save £1,448.55 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,345.64
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,345.64

Why Choose the ABB T6L 630 1SDA060208R1 Moulded-Case Circuit Breaker?

The ABB 1SDA060208R1 is a high-performance Tmax T6L 630 three-pole moulded-case circuit breaker (MCCB) designed for protection and control of low-voltage industrial and commercial power distribution circuits. As part of the ABB Tmax T4–T8 range, it combines a 630 A frame with a TMA thermomagnetic trip unit and the high short-circuit performance of the T6L breaker platform.

The breaker incorporates a TMA 630 thermomagnetic trip unit, providing adjustable thermal overload protection together with instantaneous magnetic short-circuit protection. The overload release can be adjusted from 441–630 A, while the instantaneous magnetic release is adjustable from 3150–6300 A, allowing protection settings to be coordinated with the characteristics of the protected circuit.

The 1SDA060208R1 is a fixed, three-pole circuit breaker with front terminals and a rated uninterrupted current of 630 A. The T6L version provides a rated ultimate short-circuit breaking capacity of 100 kA at 415 V AC, making it particularly suitable for demanding distribution systems where high prospective fault currents may be present.

Key Advantages

  • High-performance ABB Tmax T6L 630 moulded-case circuit breaker.
  • 630 A rated uninterrupted current for high-current distribution applications.
  • Adjustable 441–630 A thermal overload protection.
  • Adjustable 3150–6300 A instantaneous magnetic protection.
  • High 100 kA Icu at 415 V AC short-circuit breaking capacity.
  • Fixed three-pole configuration with front terminals for straightforward switchboard integration.

Key Features

  • ABB Tmax T6L 630 circuit-breaker platform.
  • TMA 630 thermomagnetic trip unit.
  • 630 A rated current.
  • 441–630 A overload release adjustment range.
  • 3150–6300 A instantaneous short-circuit release range.
  • Three-pole (3P) construction.
  • Fixed execution with front terminals.
  • 690 V AC rated operational voltage.

High-Performance Protection for Low-Voltage Distribution

Moulded-case circuit breakers protect conductors, switchgear and connected equipment against damaging overload and short-circuit currents. The TMA trip unit fitted to the ABB T6L 630 combines an adjustable thermal element for sustained overload protection with an instantaneous magnetic element designed to disconnect high-current short circuits rapidly.

With an Icu of 100 kA at 415 V AC, the T6L performance level is suited to installations with substantial prospective fault currents. Its adjustable 441–630 A overload range and 3150–6300 A instantaneous protection range provide flexibility when coordinating the breaker with feeders, distribution equipment and connected loads.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main feeder protection.
  • High-fault-level switchboards and distribution panels.
  • Industrial machinery and production facilities.
  • Commercial and infrastructure electrical distribution.
  • Three-phase circuits requiring adjustable thermomagnetic protection.

Technical Specifications

Series Tmax T4–T8
Order code 1SDA060208R1
Product type Moulded-case circuit breaker (MCCB)
Frame T6
Performance level L
Rated uninterrupted current (Iu) 630 A
Trip unit TMA thermomagnetic
Overload release setting 441–630 A
Instantaneous short-circuit release setting 3150–6300 A
Number of poles 3
Execution Fixed
Terminal connection Front
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 8 kV
Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Rated service short-circuit breaking capacity (Ics) at 415 V AC 75 kA
Rated short-time withstand current (Icw) 7.6 kA for 1 s
Power loss per pole at rated operating conditions 30.6 W
Standard IEC
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA060208R1 used for?

The ABB 1SDA060208R1 is a Tmax T6L 630 three-pole moulded-case circuit breaker used to protect low-voltage power distribution circuits against overloads and short circuits.

What is the current rating of the ABB 1SDA060208R1?

The breaker has a rated uninterrupted current of 630 A, with its TMA thermal overload release adjustable from 441–630 A.

What is the magnetic trip range of the ABB T6L 630 1SDA060208R1?

The instantaneous magnetic short-circuit release is adjustable from 3150–6300 A.

What is the breaking capacity of the ABB 1SDA060208R1?

The T6L 630 has a rated ultimate short-circuit breaking capacity (Icu) of 100 kA at 415 V AC and a rated service short-circuit breaking capacity (Ics) of 75 kA at 415 V AC.

What does 3P F F mean on the ABB T6L 630?

The designation identifies a three-pole circuit breaker in fixed execution with front terminals, a configuration designed for permanent installation in compatible low-voltage switchboards and distribution assemblies.

Trusted ABB Circuit Protection

ABB Tmax moulded-case circuit breakers provide dependable overload and short-circuit protection for demanding industrial and commercial power distribution systems, combining robust breaker construction with adjustable protection and high short-circuit performance.