ABB 1SDA059392R1 is a SACE Emax E3S 1000 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSI electronic release providing long-time, short-time and instantaneous protection for demanding low-voltage power distribution systems.
£10,782.41
The ABB 1SDA059392R1 is a high-performance SACE Emax E3S 1000 A four-pole air circuit breaker moving part designed for switching and overcurrent protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product family, it combines a 1000 A rated current with the PR121/P-LSI electronic overcurrent release for industrial, commercial and infrastructure power applications.
The E3S1000 is equipped with an ABB PR121/P-LSI electronic trip unit, providing long-time, short-time and instantaneous protection functions. The LSI protection package helps protect cables, busbars, switchgear and connected equipment against overload and short-circuit conditions, with an overload adjustment range of 400–1000 A, short-time delayed short-circuit adjustment of 1000–10000 A and instantaneous adjustment of 1500–15000 A.
This model features a four-pole withdrawable moving-part (W MP) configuration for use with the corresponding SACE Emax fixed part. The E3S platform provides rated service and ultimate short-circuit breaking capacities of 75 kA across 220–690 V AC, while four auxiliary contacts and open/closed position indication support integration with switchboard control and signalling systems.
Air circuit breakers such as the ABB SACE Emax E3S protect low-voltage electrical distribution systems against potentially damaging overload and short-circuit conditions. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping safeguard cables, busbars, switchgear and connected electrical equipment.
The PR121/P-LSI release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection with the high fault-interruption capability of the E3S platform. Together with its 75 kA short-time withstand current for 1 s and four-pole withdrawable construction, the 1SDA059392R1 is well suited to critical distribution systems requiring adjustable electronic protection and maintainable high-current switchgear.
| Product family | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA059392R1 |
| Product type | Air circuit breaker moving part |
| Frame / subtype | E3S / E3 |
| Short-circuit performance level | S |
| Rated current | 1000 A |
| Rated uninterrupted current | 1000 A |
| Number of poles | 4 |
| Current type | AC |
| Trip unit | PR121/P-LSI R1000 |
| Release type | Electronic |
| Protection functions | LSI (long-time, short-time and instantaneous) |
| Overload release setting range | 400–1000 A |
| Short-time delayed short-circuit release setting range | 1000–10000 A |
| Instantaneous short-circuit release setting range | 1500–15000 A |
| Rated voltage | 690 V |
| Rated service short-circuit breaking capacity | 75 kA at 220–690 V AC |
| Rated ultimate short-circuit breaking capacity | 75 kA at 220–690 V AC |
| Rated short-time withstand current | 75 kA for 1 s; 65 kA for 3 s |
| Execution | Withdrawable |
| Version | Moving part (MP) |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Integrated earth-fault protection | No |
| Motor drive | Optional |
| Electrical durability | 12,000 cycles at ≤440 V AC; 12,000 cycles at 500–690 V AC |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Net weight | 81 kg |
| Standards | IEC |
| ABB product group | 310513-New Emax |
| EAN | 8015644617530 |
The ABB 1SDA059392R1 is a 1000 A four-pole SACE Emax air circuit breaker moving part designed for switching and overcurrent protection in demanding low-voltage industrial, commercial and infrastructure electrical distribution systems.
The PR121/P-LSI electronic release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection, commonly abbreviated as LSI.
The E3S1000 has rated service and ultimate short-circuit breaking capacities of 75 kA across 220–690 V AC, together with a rated short-time withstand current of 75 kA for 1 s.
The 1SDA059392R1 is a four-pole air circuit breaker moving part, making it suitable for distribution systems requiring simultaneous switching and protection of four conductors.
The 1SDA059392R1 is a withdrawable moving-part (W MP) circuit breaker designed for use with the corresponding SACE Emax fixed part, supporting convenient inspection, maintenance and servicing.
ABB SACE Emax air circuit breakers provide dependable switching and electronic protection for demanding low-voltage power distribution systems, combining high short-circuit performance with adjustable protection and maintainable switchboard integration.