ABB 1SDA059385R1 SACE Emax E3S 1000 three-pole fixed air circuit breaker rated at 1000 A with rear horizontal terminals, a PR121/P-LI R1000 electronic release and 75 kA breaking capacity.
£7,762.41
The ABB 1SDA059385R1 is a high-performance SACE Emax E3S air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. This configuration combines a 1000 A rated current, three-pole construction and fixed installation with the PR121/P-LI R1000 electronic overcurrent release.
The PR121/P-LI release provides long-time overload and instantaneous short-circuit protection, helping protect cables, busbars, switchgear and connected equipment against damaging overcurrent conditions. The E3S performance level provides a rated ultimate and service short-circuit breaking capacity of 75 kA across its rated AC voltage range up to 690 V AC.
This model is the three-pole fixed version with rear flat horizontal terminals (F HR). It is supplied with four auxiliary changeover contacts and circuit-breaker open/closed position indication, providing useful signalling capabilities for integration into industrial and commercial switchboard control systems.
Air circuit breakers such as the ABB SACE Emax E3S provide switching and protection at the heart of low-voltage power distribution systems. The electronic overcurrent release monitors circuit current and initiates tripping when configured protection thresholds are exceeded, helping safeguard conductors, switchgear and connected equipment from damaging overload and short-circuit conditions.
The PR121/P-LI release fitted to this E3S 1000 combines long-time overload protection with instantaneous short-circuit protection. Together with the E3S frame's 75 kA breaking capacity, fixed construction and rear horizontal terminals, this configuration provides a dependable solution for main and feeder protection in industrial, commercial and infrastructure switchboards.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059385R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame / sub-type | E3 |
| Short-circuit performance level | S |
| Rated current (In) | 1000 A |
| Rated operational current (Ie) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 3 |
| Version | Fixed (F) |
| Terminal arrangement | Rear flat horizontal (HR) |
| Trip unit | PR121/P-LI R1000 |
| Release type | Electronic (EL) |
| Protection functions | Long-time and instantaneous |
| Overload release adjustment range | 400–1000 A |
| Instantaneous short-circuit release adjustment range | 1500–15000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 75 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 75 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 75 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 75 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Auxiliary contacts | 4 changeover contacts |
| Position indication | Open / closed |
| Motor drive | Optional |
| Power loss | 38.4 W |
| Electrical durability | 12,000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 404 × 418 × 302 mm |
| Product net weight | 60 kg |
| EAN | 8015644617462 |
| Customs tariff number | 85362090 |
| Standard | IEC |
The ABB 1SDA059385R1 is a SACE Emax E3S 1000 three-pole fixed air circuit breaker rated at 1000 A, with rear horizontal terminals and a PR121/P-LI R1000 electronic overcurrent release.
The PR121/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
The E3S 1000 has a rated ultimate and service short-circuit breaking capacity of 75 kA, including at 400 V AC and 690 V AC.
ABB 1SDA059385R1 is the fixed (F) version of the E3S 1000 and is equipped with rear flat horizontal (HR) terminals.
It is typically used in industrial, commercial and infrastructure low-voltage switchboards for main incomer and feeder protection where a 1000 A three-pole circuit breaker with electronic LI protection and high short-circuit performance is required.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining electronic overcurrent protection, high short-circuit performance and robust construction for industrial and infrastructure switchboards.