ABB 1SDA059308R1 is a SACE Emax E2S 1000 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSI electronic trip unit for high-performance low-voltage power distribution protection.
£10,484.33
The ABB 1SDA059308R1 is a high-performance SACE Emax E2S 1000 air circuit breaker designed for protection, switching and isolation in demanding low-voltage power distribution systems. Configured as E2S 1000 PR121/P-LSI In=1000A 4p W, it combines a 1000 A rated current, four-pole construction and ABB's PR121/P-LSI electronic overcurrent release.
The PR121/P-LSI release provides long-time, short-time and instantaneous protection functions, enabling the breaker to protect electrical distribution circuits against overloads and short circuits. The E2S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, making this model suitable for distribution systems with demanding fault-level requirements.
The 1SDA059308R1 is supplied as a four-pole withdrawable moving part for use with the corresponding SACE Emax fixed part. Its withdrawable construction supports efficient inspection and servicing, while four auxiliary change-over contacts and circuit-breaker open/closed position indication provide useful status signalling for switchboard applications.
The ABB SACE Emax E2S is designed to protect high-current low-voltage distribution circuits while also providing dependable switching and isolation. Its PR121/P-LSI electronic release combines long-time overload protection with short-time delayed and instantaneous short-circuit protection, supporting effective protection and coordination of feeders, busbars and connected electrical equipment.
The withdrawable construction of the 1SDA059308R1 makes it particularly suitable for switchboards where maintainability and operational flexibility are priorities. When used with the corresponding SACE Emax fixed part, the circuit-breaker moving assembly can be withdrawn for inspection, testing or servicing while permanent switchboard connections remain installed.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059308R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame | E2S |
| Rated current | 1000 A |
| Rated uninterrupted current | 1000 A |
| Number of poles | 4 |
| Trip unit | PR121/P-LSI |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Execution | Withdrawable |
| Configuration | Moving part (W/MP) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity | 85 kA at 400 V AC, 50 Hz |
| Rated service short-circuit breaking capacity | 85 kA at 400 V AC, 50 Hz |
| Rated short-time withstand current | 65 kA for 1 s |
| Overload release adjustment range | 400–1000 A |
| Short-time release adjustment range | 1000–10000 A |
| Instantaneous release adjustment range | 1500–15000 A |
| Ground-fault protection | No |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Short-circuit performance level | S |
| Standards | IEC |
| EAN | 8015644616694 |
The ABB 1SDA059308R1 is a SACE Emax E2S 1000 four-pole withdrawable air circuit breaker moving part equipped with a PR121/P-LSI electronic overcurrent release.
The circuit breaker has a rated current and rated uninterrupted current of 1000 A.
The 1SDA059308R1 is equipped with the ABB PR121/P-LSI electronic trip unit.
LSI denotes long-time, short-time and instantaneous protection, providing electronic protection against sustained overloads and short-circuit conditions.
The 1SDA059308R1 is a withdrawable moving-part circuit breaker intended for use with the corresponding ABB SACE Emax fixed part.
The E2S 1000 has a rated ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz.
No. This model uses a PR121/P-LSI release providing long-time, short-time and instantaneous protection; ground-fault protection is not included in the LSI configuration.
ABB SACE Emax air circuit breakers are engineered for demanding industrial, commercial and infrastructure power distribution systems where dependable high-current protection, electronic trip functionality and maintainable switchgear construction are required.