1SDA059274R1 ABB E2N 1000A 3-Pole Withdrawable Air Circuit Breaker Moving Part PR122/P-LSI

1SDA059274R1 ABB E2N 1000A 3-Pole Withdrawable Air Circuit Breaker Moving Part PR122/P-LSI

ABB 1SDA059274R1 SACE Emax E2N 1000 A three-pole withdrawable air circuit breaker moving part with PR122/P-LSI R1000 electronic protection for demanding low-voltage power distribution systems.

SKU: 1SDA059274R1Alt SKU: E2N1000PR122/P-LSIMPN: 1SDA059274R1
Price
List Price £10,911.99 ex VAT
Your Price (ex VAT) Save 25%
£8,183.99 25% OFF
You save £2,728.00 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,183.99
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,183.99

Why Choose the ABB 1SDA059274R1 E2N 1000 PR122/P-LSI Air Circuit Breaker?

The ABB 1SDA059274R1 is a SACE Emax E2N 1000 air circuit breaker moving part designed for protection and switching in demanding low-voltage power distribution systems. Rated at 1000 A, this three-pole withdrawable breaker is equipped with an ABB PR122/P-LSI R1000 electronic overcurrent release for dependable overload and short-circuit protection.

As part of the ABB SACE Emax range, the E2N 1000 combines substantial short-circuit performance with a serviceable withdrawable construction. The 1SDA059274R1 is supplied as the withdrawable moving part (W MP) for use with a compatible fixed part and incorporates four auxiliary contacts with circuit-breaker open/closed position indication.

With a rated operational current of 1000 A, rated operational voltage of 690 V AC and rated ultimate and service short-circuit breaking capacities of up to 65 kA, the 1SDA059274R1 provides robust protection for substantial three-phase low-voltage distribution circuits.

Key Advantages

  • 1000 A rated current for high-current low-voltage distribution applications.
  • PR122/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection.
  • Three-pole configuration is suited to three-phase electrical distribution systems.
  • Withdrawable moving-part construction supports inspection, servicing and breaker replacement.
  • 65 kA Icu/Ics up to 440 V AC provides substantial short-circuit performance.
  • 55 kA Icu/Ics at 500–690 V AC supports demanding higher-voltage distribution systems.
  • Four auxiliary contacts provide circuit-breaker open/closed position indication.
  • Part of the established ABB SACE Emax E2N air circuit breaker platform.

Key Features

  • ABB SACE Emax E2N 1000 air circuit breaker moving part.
  • 1000 A rated current (In).
  • Three-pole construction.
  • Withdrawable version.
  • Supplied as the moving part (MP).
  • Electronic PR122/P-LSI R1000 overcurrent release.
  • LSI protection functions: long-time, short-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 65 kA Icu/Ics at 220–440 V AC.
  • 55 kA Icu/Ics at 500–690 V AC.
  • 55 kA short-time withstand current for 1 s.
  • Four auxiliary contacts with open/closed circuit-breaker position indication.

Advanced LSI Protection with Withdrawable Switchgear

Air circuit breakers protect and control high-current low-voltage distribution circuits by interrupting overload and short-circuit faults while providing switching and isolation capability. The withdrawable construction of the ABB 1SDA059274R1 allows the breaker moving part to be removed from its compatible fixed assembly, supporting inspection, servicing and replacement within maintainable switchboard installations.

The PR122/P-LSI R1000 electronic overcurrent release provides long-time protection against sustained overload conditions, short-time protection for selected short-circuit conditions and instantaneous protection against severe faults. Combined with the E2N platform's short-circuit performance and 1000 A current rating, the 1SDA059274R1 provides dependable protection for demanding industrial, commercial and infrastructure power distribution applications.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • Three-phase feeder protection and switching.
  • High-current distribution circuit protection.
  • Transformer and installation protection.
  • Manufacturing and process plant switchgear.
  • Commercial and infrastructure electrical distribution.
  • Withdrawable low-voltage switchgear installations.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
Extended product type E2N1000PR122/P-LSIIn=1000A3pWMP
Order code 1SDA059274R1
Product type Air circuit breaker moving part
Frame E2N
Sub-type E2
Short-circuit performance level N
Current type AC
Rated current (In) 1000 A
Rated operational current (Ie) 1000 A
Rated uninterrupted current (Iu) 1000 A
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) 65 kA at 220–440 V AC; 55 kA at 500–690 V AC
Rated service short-circuit breaking capacity (Ics) 65 kA at 220–440 V AC; 55 kA at 500–690 V AC
Rated short-time withstand current (Icw) 55 kA for 1 s; 42 kA for 3 s
Number of poles 3
Installation Withdrawable
Component Moving part
Version W
Trip unit PR122/P-LSI R1000
Release type Electronic
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Auxiliary contacts 4
Position indication Circuit breaker open/closed
Electrical durability 15,000 cycles
Electrical operating frequency 30 cycles per hour
Mechanical durability 25,000 cycles
Mechanical operating frequency 60 cycles per hour
Power loss 83.2 W
Product net width 324 mm
Product net height 461 mm
Product net depth 396.5 mm
Product net weight 49 kg
EAN 8015644616359
Customs tariff number 85362090
Standards IEC

Frequently Asked Questions

What is the ABB 1SDA059274R1 used for?

The ABB 1SDA059274R1 is a SACE Emax E2N air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits.

What current and voltage ratings does the ABB 1SDA059274R1 have?

The 1SDA059274R1 has a rated current of 1000 A and a rated operational voltage of 690 V AC, with a rated insulation voltage of 1000 V.

What protection unit is fitted to the ABB 1SDA059274R1?

The breaker is fitted with an ABB PR122/P-LSI R1000 electronic overcurrent release, providing long-time, short-time and instantaneous protection functions.

What is the breaking capacity of the ABB 1SDA059274R1?

The E2N breaker has rated ultimate and service short-circuit breaking capacities of 65 kA at 220–440 V AC and 55 kA at 500–690 V AC.

Is the ABB 1SDA059274R1 fixed or withdrawable?

The 1SDA059274R1 is a three-pole withdrawable moving part designed for use with the corresponding compatible ABB SACE Emax fixed part, allowing the breaker to be removed for inspection, servicing or replacement.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers combine high-current switching, electronic protection and serviceable withdrawable construction, supporting dependable circuit protection and control across industrial, commercial and infrastructure low-voltage power distribution systems.