ABB 1SDA059258R1 E2N1000 is a 1000 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR121/P-LI electronic trip unit for overload and instantaneous short-circuit protection.
£7,529.14
The ABB E2N1000 PR121/P-LI, order code 1SDA059258R1, is a robust 1000 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage power distribution systems. As part of the proven ABB SACE Emax E2N series, it combines dependable switching performance with electronic overcurrent protection for industrial, commercial and infrastructure switchgear.
This Emax circuit breaker is equipped with the PR121/P-LI electronic trip unit, providing long-time overload (L) and instantaneous short-circuit (I) protection. The R1000 release is matched to the breaker’s 1000 A rated current, helping protect cables, busbars, switchgear and connected equipment against sustained overloads and severe short-circuit faults.
With a rated operational voltage of up to 690 V AC, the E2N1000 provides strong performance across demanding low-voltage distribution systems. This model is supplied as the moving part of a withdrawable circuit breaker and includes four auxiliary contacts for open/closed breaker position indication, supporting service-friendly integration into compatible SACE Emax switchgear.
Air circuit breakers such as the ABB SACE Emax E2N are designed to switch and protect high-current low-voltage distribution circuits. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchgear and connected equipment against damaging overload and short-circuit conditions.
The PR121/P-LI release provides essential long-time and instantaneous protection, while the E2N performance level delivers substantial short-circuit interruption capability. Combined with its withdrawable construction, the E2N1000 is well suited to installations where dependable protection, high fault-current capability and straightforward switchgear maintenance are important.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA059258R1 |
| EAN | 8015644616199 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame / subtype | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Rated operational current (Ie) | 1000 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR121/P-LI R1000 |
| Release type | Electronic |
| Protection functions | L (overload) and I (instantaneous short-circuit) |
| Instantaneous short-circuit release adjustment range | 1500–15000 A |
| Rated ultimate short-circuit breaking capacity (Icu) | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated service short-circuit breaking capacity (Ics) | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated short-time withstand current (Icw) | 55 kA for 1 s; 42 kA for 3 s |
| Version | Withdrawable moving part |
| Auxiliary contacts | 4 for circuit-breaker open/closed position indication |
| Power loss | 83.2 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability | 15,000 operating cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
The ABB 1SDA059258R1 is a 1000 A three-pole SACE Emax air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits.
This circuit breaker is equipped with the ABB PR121/P-LI R1000 electronic trip unit, providing long-time overload and instantaneous short-circuit protection.
The E2N1000 has rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC, reducing to 55 kA at 500–690 V AC.
The 1SDA059258R1 is the moving part of a withdrawable circuit breaker, designed for use with the appropriate compatible SACE Emax fixed part.
The breaker moving part is fitted with four auxiliary contacts for circuit-breaker open and closed position indication.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining robust switching performance, electronic circuit protection and service-friendly withdrawable construction for demanding industrial and commercial switchgear.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.