1SDA059213R1 ABB E1N 1000A 3-Pole Fixed Air Circuit Breaker PR121/P-LI

1SDA059213R1 ABB E1N 1000A 3-Pole Fixed Air Circuit Breaker PR121/P-LI

ABB 1SDA059213R1 SACE Emax E1N 1000 A three-pole fixed air circuit breaker with rear horizontal terminals, PR121/P-LI electronic protection and 50 kA breaking capacity for low-voltage power distribution systems.

SKU: 1SDA059213R1MPN: 1SDA059213R1
Price
List Price £9,554.69 ex VAT
Your Price (ex VAT) Save 25%
£7,166.02 25% OFF
You save £2,388.67 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,166.02
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,166.02

Why Choose the ABB 1SDA059213R1 E1N 1000 PR121/P-LI Air Circuit Breaker?

The ABB 1SDA059213R1 is a SACE Emax E1N 1000 air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. Rated at 1000 A, this three-pole fixed circuit breaker is equipped with an ABB PR121/P-LI R1000 electronic overcurrent release for dependable overload and short-circuit protection.

As part of the ABB SACE Emax range, the E1N 1000 provides high-current switching and protection for industrial, commercial and infrastructure switchboards. The 1SDA059213R1 is a fixed version with rear horizontal terminals and is fitted with four auxiliary contacts for circuit-breaker open/closed position indication.

With a rated operational current of 1000 A, rated operational voltage of 690 V AC and rated ultimate short-circuit breaking capacity of 50 kA, the 1SDA059213R1 provides robust protection for substantial three-phase low-voltage distribution circuits.

Key Advantages

  • 1000 A rated current for substantial low-voltage distribution loads.
  • PR121/P-LI electronic overcurrent release provides long-time and instantaneous protection functions.
  • Three-pole configuration for three-phase electrical distribution systems.
  • Fixed installation provides a robust permanent switchboard arrangement.
  • Rear horizontal terminals support practical switchgear integration.
  • 50 kA ultimate and service short-circuit breaking capacity across the specified 220–690 V AC range.
  • Four auxiliary contacts provide circuit-breaker open/closed position indication.
  • Part of the established ABB SACE Emax E1N air circuit breaker platform.

Key Features

  • ABB SACE Emax E1N 1000 air circuit breaker.
  • 1000 A rated current (In).
  • Three-pole construction.
  • Fixed version.
  • Rear horizontal terminals.
  • Electronic PR121/P-LI R1000 overcurrent release.
  • LI protection functions: long-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 50 kA rated ultimate and service short-circuit breaking capacity.
  • 50 kA short-time withstand current for 1 s.
  • Four auxiliary contacts with open/closed breaker position indication.

High-Performance Electronic Protection for Low-Voltage Distribution

Air circuit breakers protect and control high-current low-voltage distribution circuits by interrupting overload and short-circuit faults while also providing switching and isolation functionality. The E1N performance level gives the 1SDA059213R1 a 50 kA rated ultimate and service short-circuit breaking capacity, making it suitable for installations with substantial prospective fault currents.

The PR121/P-LI electronic overcurrent release provides long-time protection against sustained overload conditions and instantaneous protection against severe short-circuit faults. Combined with the 1000 A rating, three-pole construction, fixed mounting and rear horizontal terminals, this makes the ABB 1SDA059213R1 a capable solution for industrial and commercial power distribution.

Typical Applications

  • Main low-voltage distribution switchboards.
  • Industrial power distribution systems.
  • High-current feeder protection.
  • Transformer and installation protection.
  • Manufacturing and process plant switchgear.
  • Commercial building electrical distribution.
  • Infrastructure and utility distribution assemblies.
  • Fixed low-voltage switchgear installations.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
Extended product type E1N1000PR121/P-LIIn=1000A3pFHR
Order code 1SDA059213R1
Product type Air circuit breaker
Frame E1N
Short-circuit performance level N
Current type AC
Rated current (In) 1000 A
Rated operational current (Ie) 1000 A
Rated uninterrupted current (Iu) 1000 A
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 220–690 V AC
Rated service short-circuit breaking capacity (Ics) 50 kA at 220–690 V AC
Rated short-time withstand current (Icw) 50 kA for 1 s; 36 kA for 3 s
Number of poles 3
Installation Fixed
Terminal arrangement Rear horizontal
Trip unit PR121/P-LI R1000
Release type Electronic
Protection functions LI
Overload release adjustment 400–1000 A
Instantaneous short-circuit adjustment 1500–15000 A
Auxiliary contacts 4
Position indication Circuit breaker open/closed
Electrical durability 10,000 cycles at Ue ≤ 440 V; 8,000 cycles at 500–690 V
Mechanical durability 25,000 cycles
Power loss 96 W
Product net width 296 mm
Product net height 418 mm
Product net depth 302 mm
Product net weight 40 kg
EAN 8015644615741
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA059213R1 used for?

The ABB 1SDA059213R1 is a SACE Emax E1N air circuit breaker used for switching and protecting high-current low-voltage electrical distribution circuits.

What current and voltage ratings does the ABB 1SDA059213R1 have?

The 1SDA059213R1 has a rated current of 1000 A and a rated operational voltage of 690 V AC, with a rated insulation voltage of 1000 V.

What protection unit is fitted to the ABB 1SDA059213R1?

The circuit breaker is fitted with an ABB PR121/P-LI R1000 electronic overcurrent release, providing long-time and instantaneous protection functions.

What is the breaking capacity of the ABB 1SDA059213R1?

The E1N breaker has a rated ultimate short-circuit breaking capacity (Icu) and rated service short-circuit breaking capacity (Ics) of 50 kA across the specified 220–690 V AC range.

Is the ABB 1SDA059213R1 fixed or withdrawable?

The 1SDA059213R1 is a three-pole fixed air circuit breaker with rear horizontal terminals and four auxiliary contacts for open/closed position indication.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers combine high-current switching, electronic protection and robust switchgear integration, supporting dependable circuit protection and control across industrial, commercial and infrastructure low-voltage power distribution systems.