1SDA059211R1 ABB E1B/MS1000 1000 A 4-Pole Fixed Switch-Disconnector

1SDA059211R1 ABB E1B/MS1000 1000 A 4-Pole Fixed Switch-Disconnector

ABB 1SDA059211R1 is a SACE Emax E1B/MS 1000 A four-pole fixed switch-disconnector with rear horizontal terminals designed for dependable switching and isolation in low-voltage power distribution systems.

SKU: 1SDA059211R1MPN: 1SDA059211R1
Price
List Price £10,637.50 ex VAT
Your Price (ex VAT) Save 25%
£7,978.13 25% OFF
You save £2,659.38 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,978.13
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,978.13

Why Choose the ABB 1SDA059211R1 E1B/MS1000 Switch-Disconnector?

The ABB 1SDA059211R1 is a robust SACE Emax E1B/MS 1000 A four-pole switch-disconnector designed for dependable switching and isolation in low-voltage electrical distribution systems. Part of the ABB New Emax product family, this fixed unit combines high-current switching capability with a proven air switch-disconnector platform for industrial and commercial switchboard applications.

The E1B/MS1000 has a 1000 A rated uninterrupted current and a four-pole configuration, making it suitable for systems where all four conductors require switching and isolation. It is rated for operational voltages up to 690 V AC and provides the electrical withstand performance required for demanding low-voltage distribution installations.

This model is supplied in a fixed (F) configuration with rear horizontal (HR) terminals for permanent installation within compatible switchboards. With a rated short-time withstand current of 42 kA for 1 s, the E1B/MS1000 provides robust performance for power distribution applications where reliable isolation and high-current switching are required.

Key Advantages

  • Heavy-duty ABB SACE Emax switch-disconnector for low-voltage power distribution.
  • 1000 A rated uninterrupted current for high-current industrial applications.
  • Four-pole configuration for comprehensive switching and isolation.
  • Fixed installation for permanent integration into low-voltage switchboards.
  • Rear horizontal terminals support practical switchboard busbar connections.
  • Rated operational voltage up to 690 V AC.
  • 42 kA short-time withstand current for 1 s for demanding distribution systems.

Key Features

  • ABB SACE Emax E1B/MS series.
  • 1000 A rated current.
  • Four-pole switch-disconnector.
  • Fixed (F) execution.
  • Rear horizontal (HR) terminal arrangement.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Rated short-time withstand current of 42 kA for 1 s and 36 kA for 3 s.
  • Designed for IEC low-voltage switchgear applications.

Reliable Switching and Isolation for Power Distribution

Switch-disconnectors such as the ABB SACE Emax E1B/MS provide dependable switching and isolation within low-voltage power distribution systems. They allow electrical circuits to be disconnected for operational control or maintenance while providing the continuous current-carrying and short-time withstand capability required in demanding industrial switchboards.

The fixed E1B/MS1000 is designed for permanent integration into a suitable electrical distribution assembly. Its rear horizontal terminals facilitate connection within the switchboard, while its 1000 A current rating and four-pole construction make it suitable for high-current applications requiring simultaneous isolation of four conductors.

Typical Applications

  • Industrial low-voltage switchboards.
  • Main power isolation and switching.
  • Three-phase and four-wire electrical distribution systems.
  • Manufacturing and process facilities.
  • Commercial building power distribution.
  • Electrical distribution panels and assemblies.
  • Infrastructure and utility installations.
  • Systems requiring fixed high-current switch-disconnectors.

Technical Specifications

Product family SACE Emax / New Emax
ABB order code 1SDA059211R1
Product type Switch-disconnector
Frame / subtype E1B / E1
Rated current 1000 A
Rated operational current 1000 A
Rated uninterrupted current 1000 A
Number of poles 4
Current type AC
Rated operational voltage 690 V AC
Rated voltage 690 V
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated short-time withstand current 42 kA for 1 s; 36 kA for 3 s
Execution Fixed
Terminal connection Rear flat horizontal
Electrical durability 10,000 cycles
Mechanical durability 25,000 cycles
Power loss 96 W
Protection rating IP20 front
Standards IEC
Weight approx. 62 kg
ABB product group 310513-New Emax
EAN 8015644615727

Frequently Asked Questions

What is the ABB 1SDA059211R1 used for?

The ABB 1SDA059211R1 is a 1000 A four-pole SACE Emax switch-disconnector designed for switching and isolation duties in low-voltage electrical distribution systems.

What is the rated current of the ABB 1SDA059211R1?

The E1B/MS1000 has a rated uninterrupted current of 1000 A.

How many poles does the ABB 1SDA059211R1 have?

The 1SDA059211R1 is a four-pole switch-disconnector, making it suitable for distribution systems where four conductors need to be switched and isolated.

Is the ABB 1SDA059211R1 fixed or withdrawable?

The 1SDA059211R1 is a fixed (F) switch-disconnector with rear horizontal terminals for permanent installation within a suitable low-voltage switchboard.

What voltage and short-time current ratings does the ABB 1SDA059211R1 have?

The unit has a rated operational voltage of up to 690 V AC and a rated short-time withstand current of 42 kA for 1 s or 36 kA for 3 s.

Trusted ABB Power Distribution Technology

ABB SACE Emax switch-disconnectors provide robust switching and isolation for low-voltage power distribution systems, combining high-current performance with flexible installation options for demanding industrial and commercial switchgear applications.