1SDA059172R1 ABB E1B 1000A 4-Pole PR121/P-LI Withdrawable Air Circuit Breaker

1SDA059172R1 ABB E1B 1000A 4-Pole PR121/P-LI Withdrawable Air Circuit Breaker

ABB 1SDA059172R1 is a SACE Emax E1B 1000 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LI electronic overcurrent release for industrial low-voltage power distribution.

SKU: 1SDA059172R1MPN: 1SDA059172R1
Price
List Price £12,568.66 ex VAT
Your Price (ex VAT) Save 25%
£9,426.50 25% OFF
You save £3,142.17 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £9,426.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£9,426.50

Why Choose the ABB 1SDA059172R1 E1B 1000 Air Circuit Breaker?

The ABB 1SDA059172R1 is a SACE Emax E1B 1000 air circuit breaker moving part designed for reliable protection and switching in industrial low-voltage power distribution systems. Identified by the extended product type E1B1000PR121/P-LIIn=1000A4pWM, this four-pole withdrawable unit has a rated current of 1000 A and is equipped with an ABB PR121/P-LI electronic overcurrent release.

As part of the ABB SACE Emax / New Emax family, the 1SDA059172R1 combines high-current switching with electronic protection against overload and instantaneous short-circuit conditions. The PR121/P-LI release provides L and I protection functions, while the E1B circuit breaker offers a rated service and ultimate short-circuit breaking capacity of 42 kA across its specified AC operating voltage range.

The withdrawable moving-part construction supports maintainable switchgear architecture by allowing the circuit breaker to interface with a compatible ABB fixed part. With a 1000 A current rating, 690 V AC rated operational voltage and four-pole configuration, the 1SDA059172R1 is suited to demanding industrial distribution boards, switchboards and main power distribution systems.

Key Advantages

  • Genuine ABB SACE Emax E1B air circuit breaker moving part.
  • 1000 A rated current for industrial power distribution applications.
  • Four-pole configuration for compatible three-phase and neutral systems.
  • PR121/P-LI electronic overcurrent release provides long-time and instantaneous protection functions.
  • 42 kA service and ultimate short-circuit breaking capacity across the specified AC operating voltage range.
  • Withdrawable construction supports efficient switchgear inspection, servicing and maintenance.

Key Features

  • ABB SACE Emax E1B 1000 platform.
  • 1000 A rated current.
  • 690 V AC rated operational voltage.
  • 4-pole configuration.
  • PR121/P-LI electronic trip unit.
  • Long-time (L) and instantaneous (I) protection.
  • 42 kA rated service short-circuit breaking capacity Ics.
  • 42 kA rated ultimate short-circuit breaking capacity Icu.
  • 42 kA for 1 s short-time withstand current Icw.
  • Withdrawable moving part (W MP) construction.
  • Fitted with auxiliary contacts and open/closed position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers provide switching, isolation and overcurrent protection for high-current low-voltage distribution systems. The ABB SACE Emax E1B platform combines substantial short-circuit performance with electronic protection, making it suitable for main distribution and feeder applications where dependable protection of cables, busbars and downstream equipment is required.

The PR121/P-LI release fitted to the 1SDA059172R1 provides long-time overload and instantaneous short-circuit protection. Combined with its 1000 A rating, 690 V AC operational voltage, 42 kA breaking capacity and withdrawable construction, the breaker provides a practical solution for maintainable industrial switchgear systems.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main incoming circuit-breaker applications.
  • High-current feeder protection.
  • Withdrawable switchgear and distribution boards.
  • Manufacturing and process industry installations.
  • Commercial and infrastructure electrical distribution.
  • Protection of busbars, feeders and downstream electrical equipment.

Technical Specifications

Series SACE Emax / New Emax
ABB product group 310513-New Emax
Order code 1SDA059172R1
Extended product type E1B1000PR121/P-LIIn=1000A4pWM
Product type Air circuit breaker moving part
Frame E1
Performance level B
Current type AC
Rated current In 1000 A
Rated uninterrupted current Iu 1000 A
Rated operational current Ie 1000 A
Rated operational voltage 690 V AC
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp 12 kV
Number of poles 4
Trip unit PR121/P-LI
Trip unit type Electronic
Protection functions L (long-time) and I (instantaneous)
Rated service short-circuit breaking capacity Ics 42 kA
Rated ultimate short-circuit breaking capacity Icu 42 kA
Rated short-time withstand current Icw 42 kA for 1 s; 36 kA for 3 s
Electrical durability 10,000 cycles at Ue ≤ 440 V; 8,000 cycles at 500–690 V
Electrical operating frequency 30 cycles per hour
Mechanical durability 25,000 cycles
Mechanical operating frequency 60 cycles per hour
Power loss 147.2 W
Construction Withdrawable moving part
Dimensions (W × H × D) 414 × 461 × 396.5 mm
Net weight 54 kg
EAN 8015644615338
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA059172R1?

The ABB 1SDA059172R1 is a SACE Emax E1B 1000 A four-pole withdrawable air circuit breaker moving part fitted with a PR121/P-LI electronic overcurrent release.

What is the rated current of the ABB 1SDA059172R1?

The circuit breaker has a rated current of 1000 A and is designed for industrial low-voltage power distribution applications.

What protection does the PR121/P-LI trip unit provide?

The PR121/P-LI electronic release provides long-time overload (L) and instantaneous short-circuit (I) protection functions.

What is the breaking capacity of the ABB 1SDA059172R1?

The E1B 1000 has a rated service short-circuit breaking capacity Ics of 42 kA and rated ultimate short-circuit breaking capacity Icu of 42 kA across its specified AC operating voltage range.

Is the ABB 1SDA059172R1 withdrawable?

Yes. The 1SDA059172R1 is a withdrawable moving part designed for installation with a compatible ABB SACE Emax fixed part, supporting maintainable switchgear configurations.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers combine electronic protection, high-current switching and maintainable withdrawable construction for demanding industrial and commercial low-voltage power distribution systems.