ABB E3S/MS 2500 1SDA058976R1 is a 2500 A four-pole fixed SACE Emax switch-disconnector with horizontal rear terminals, a 75 kA one-second short-time withstand rating and AC-23A switching capability.
£17,436.62
The ABB E3S/MS 2500 is a high-performance 2500 A four-pole fixed switch-disconnector designed for dependable switching and isolation in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E3 series, this S-performance device combines substantial continuous-current capability with a robust fixed construction and horizontal rear terminals for integration into industrial, commercial and infrastructure switchboards.
ABB Emax switch-disconnectors identified by the /MS designation are derived from the corresponding Emax air circuit breakers, maintaining their overall dimensions and accessory compatibility while omitting the overcurrent trip unit. The E3S/MS supports AC-23A utilisation category applications in accordance with IEC 60947-3, making it suitable for switching motor loads and other highly inductive circuits as well as general isolation duties.
The 1SDA058976R1 configuration is rated at 2500 A and features a four-pole fixed construction with rear flat horizontal terminals. With a rated operational voltage of up to 690 V AC, a 75 kA one-second short-time withstand current and a 165 kA peak short-circuit making capacity, it provides robust switching and isolation performance for high-current low-voltage distribution systems.
The ABB E3S/MS 2500 provides a dependable means of making, carrying and isolating high-current electrical circuits without an integrated overcurrent trip unit. Its 75 kA one-second short-time withstand rating, 65 kA three-second withstand rating and 165 kA peak making capacity provide strong electrical performance for substantial low-voltage distribution systems when suitable protective equipment is coordinated elsewhere in the installation.
The fixed construction and rear flat horizontal terminals make the 1SDA058976R1 particularly suitable for permanent installation in high-capacity switchboards with rear busbar connections. Combined with its 2500 A current rating, four-pole architecture, AC-23A switching capability and proven SACE Emax mechanical platform, the E3S/MS 2500 provides a robust solution for critical industrial and commercial power distribution.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA058976R1 |
| Product type | Switch-disconnector |
| Frame / device size | E3S/MS 2500 |
| Short-circuit performance level | S |
| Rated current (In) | 2500 A |
| Rated operational current (Ie) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational voltage (Ue), AC | 690 V |
| Rated operational voltage (Ue), DC | 250 V |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Rated short-circuit making capacity (Icm), peak | 165 kA |
| Number of poles | 4 |
| Version | Fixed (F) |
| Terminal connection | Rear flat horizontal (HR) |
| Current type | AC |
| Power loss | 205 W |
| Electrical durability | 8,000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Utilisation category | AC-23A |
| Primary function | Switching and isolation |
| Overcurrent trip unit | Not fitted |
| Product width | 530 mm |
| Product height | 418 mm |
| Product depth | 302 mm |
| Net weight | 76 kg |
| Standard | IEC 60947-3 |
| EAN | 8015644613358 |
| HS code | 85362090 |
| ABB product group | 310513-New Emax |
The ABB E3S/MS 2500 is a 2500 A four-pole fixed switch-disconnector designed for high-current switching and isolation in ABB SACE Emax low-voltage power-distribution systems.
The E3S/MS 2500 has a rated uninterrupted current of 2500 A, making it suitable for substantial industrial and commercial low-voltage distribution circuits.
The E3S/MS 2500 has a rated short-time withstand current of 75 kA for 1 s and 65 kA for 3 s, together with a peak short-circuit making capacity of 165 kA.
The 1SDA058976R1 is a four-pole fixed switch-disconnector with rear flat horizontal terminals, making it suitable for permanent installation in compatible switchboards with high-current rear busbar connections.
No. The E3S/MS 2500 is a switch-disconnector without an overcurrent trip unit. It is designed primarily for switching and isolation, with suitable overload and short-circuit protection coordinated elsewhere in the electrical installation.
ABB SACE Emax switch-disconnectors provide dependable high-current switching and isolation for demanding low-voltage distribution systems, combining robust short-time withstand performance, AC-23A switching capability and proven fixed switchboard integration.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.