1SDA058952R1 ABB SACE Emax E2N/MS 1600 A 4-Pole Fixed Rear Horizontal Switch-Disconnector

1SDA058952R1 ABB SACE Emax E2N/MS 1600 A 4-Pole Fixed Rear Horizontal Switch-Disconnector

ABB 1SDA058952R1 is a 1600 A four-pole fixed SACE Emax E2N/MS switch-disconnector with rear horizontal terminals, a 690 V AC operational rating and a 55 kA short-time withstand current for 1 second.

SKU: 1SDA058952R1Alt SKU: E2N/MS1600MPN: 1SDA058952R1
Price
List Price £11,014.24 ex VAT
Your Price (ex VAT) Save 25%
£8,260.68 25% OFF
You save £2,753.56 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,260.68
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,260.68

Why Choose the ABB 1SDA058952R1 Emax E2N/MS 1600 Switch-Disconnector?

The ABB 1SDA058952R1 is a SACE Emax E2N/MS 1600 four-pole fixed switch-disconnector designed for dependable switching and electrical isolation in low-voltage power distribution systems. Identified by ABB as E2N/MS 1600 4p F HR new, it combines a 1600 A current rating with a fixed four-pole construction and rear horizontal terminals.

The E2N/MS configuration is intended for switching and isolation duties rather than automatic overcurrent protection. Its four-pole arrangement enables switching across four conductors, while the fixed installation and rear flat horizontal terminal arrangement make it suitable for permanent integration into compatible industrial and commercial switchboards.

With a rated operational voltage of 690 V AC and 250 V DC, the E2N/MS 1600 provides robust electrical performance for demanding distribution applications. It offers a rated short-time withstand current of 55 kA for 1 s and 42 kA for 3 s, together with a 1000 V insulation voltage and 12 kV impulse withstand voltage.

Key Advantages

  • Genuine ABB SACE Emax E2N/MS switch-disconnector.
  • 1600 A rated uninterrupted current for high-current distribution applications.
  • Four-pole configuration for four-conductor switching.
  • Fixed installation for permanent switchboard integration.
  • Rear flat horizontal terminals for compatible busbar arrangements.
  • 690 V AC / 250 V DC rated operational voltage.
  • 55 kA short-time withstand current for 1 s.
  • 42 kA short-time withstand current for 3 s.
  • 1000 V rated insulation voltage.
  • ABB N short-circuit performance level.

Key Features

  • ABB SACE Emax E2N/MS 1600 switch-disconnector.
  • 1600 A rated current.
  • Four-pole configuration.
  • Fixed version (F).
  • Rear flat horizontal terminal connection (HR).
  • E2 frame.
  • N short-circuit performance level.
  • 690 V AC rated operational voltage.
  • 250 V DC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 55 kA short-time withstand current for 1 s.
  • 42 kA short-time withstand current for 3 s.
  • Designed in accordance with IEC requirements.

Fixed High-Current Switching and Isolation

ABB SACE Emax /MS switch-disconnectors are designed to provide controlled switching and electrical isolation within low-voltage distribution systems. The E2N/MS 1600 performs these functions without the electronic overcurrent release associated with an automatic Emax circuit breaker, allowing protective functions to be coordinated separately within the electrical installation.

The fixed four-pole configuration of the 1SDA058952R1 is particularly suited to permanent switchboard installations requiring substantial current-carrying capability. Its rear horizontal terminals facilitate compatible busbar connections, while its 55 kA for 1 s short-time withstand rating supports use in distribution systems with demanding prospective fault-current conditions.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Four-pole switching and electrical isolation.
  • Fixed high-current switchgear assemblies.
  • 1600 A feeder switching and isolation.
  • Transformer secondary distribution systems.
  • Manufacturing and process industry installations.
  • Commercial and infrastructure power distribution systems.

Technical Specifications

Series SACE Emax / New Emax
Product group 310513-New Emax
ABB order code 1SDA058952R1
Extended product type E2N/MS16004pFHRnew
Product name Switch Disconnector
Product type Switch-disconnector
ABB description E2N/MS 1600 4p F HR new
Frame / subtype E2
Short-circuit performance level N
Rated current 1600 A
Rated operational current 1600 A
Rated uninterrupted current 1600 A
Number of poles 4
Version Fixed
Terminal connection Rear flat horizontal
Current type AC
Rated operational voltage 690 V AC / 250 V DC
Rated voltage 690 V
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated short-time withstand current 55 kA for 1 s / 42 kA for 3 s
Power loss 115 W
Electrical durability 12,000 cycles
Maximum electrical operating frequency 30 cycles per hour
Mechanical durability 25,000 cycles
Maximum mechanical operating frequency 60 cycles per hour
Standard IEC
Product dimensions (W × H × D) 386 × 418 × 302 mm
Product net weight 56 kg
EAN 8015644613112
Minimum order quantity 1 piece
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA058952R1?

The ABB 1SDA058952R1 is a SACE Emax E2N/MS 1600 four-pole fixed switch-disconnector with rear horizontal terminals and a rated uninterrupted current of 1600 A.

What is the rated current of the ABB 1SDA058952R1?

The E2N/MS 1600 has a rated uninterrupted current of 1600 A.

What does 4P F HR mean on the ABB E2N/MS 1600?

4P identifies the four-pole configuration, F identifies the fixed version and HR identifies the rear horizontal terminal arrangement.

What voltage is the ABB 1SDA058952R1 rated for?

The ABB 1SDA058952R1 has a rated operational voltage of 690 V AC and 250 V DC, with a rated insulation voltage of 1000 V.

What is the short-time withstand current of the ABB E2N/MS 1600?

The E2N/MS 1600 has a rated short-time withstand current of 55 kA for 1 s and 42 kA for 3 s.