ABB 1SDA058898R1 E3V/MS 3200 is a 3200 A four-pole fixed SACE Emax air switch disconnector with rear flat horizontal terminals for high-current low-voltage power distribution and isolation.
£23,957.32
The ABB E3V/MS 3200 4P F HR, order code 1SDA058898R1, is a heavy-duty SACE Emax air switch disconnector designed for high-current switching and isolation in demanding low-voltage power distribution systems. Part of the ABB New Emax E3 series, this four-pole unit provides a rated uninterrupted current of 3200 A and a fixed installation format for industrial switchboards and engineered power distribution assemblies.
The E3V/MS 3200 combines a four-pole fixed construction with rear flat horizontal terminals for integration into high-current switchboard busbar systems. Its V performance level provides a rated short-time withstand current of 85 kA for 1 s and 65 kA for 3 s, together with a rated short-circuit making capacity of 187 kA peak, providing robust performance in installations with substantial prospective fault currents.
Rated for operation up to 690 V AC or 250 V DC, with a rated insulation voltage of 1000 V and a rated impulse withstand voltage of 12 kV, the E3V/MS 3200 is engineered for dependable high-power distribution. ABB /MS switch disconnectors are derived from the corresponding Emax circuit breakers but omit the overcurrent trip unit, making them suitable for switching and isolation duties where circuit protection is provided separately.
Switch disconnectors provide controlled switching and isolation of electrical circuits without incorporating the overcurrent protection functions of a conventional circuit breaker. The ABB E3V/MS is therefore suited to systems where fault and overload protection is provided separately and a robust switching device is required for operational isolation, maintenance and segregation of high-current distribution circuits.
The SACE Emax /MS design retains the overall construction and accessory possibilities of the corresponding Emax circuit-breaker platform while operating as a dedicated switch disconnector. With its 3200 A current rating, four-pole construction, fixed installation format and high short-time withstand capability, this E3V/MS model is particularly suited to major industrial switchboards and critical power distribution infrastructure.
| Series | SACE Emax / New Emax E3 |
|---|---|
| ABB order code | 1SDA058898R1 |
| Product type | Air switch disconnector |
| Frame / subtype | E3 |
| Short-circuit performance level | V |
| Rated current (In) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Number of poles | 4P |
| Current type | AC |
| Rated operational voltage | 690 V AC / 250 V DC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated short-time withstand current (Icw), 1 s | 85 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Rated short-circuit making capacity (Icm) | 187 kA peak |
| Installation version | Fixed |
| Terminal connection | Rear flat horizontal |
| Electrical durability | 6,000 cycles |
| Electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Power loss | 330 W |
| Standard | IEC |
| EAN | 8015644612511 |
| Product weight | 90 kg |
The ABB 1SDA058898R1 is an E3V/MS 3200 SACE Emax four-pole fixed switch disconnector rated at 3200 A and equipped with rear flat horizontal terminals.
The E3V/MS 3200 has a rated uninterrupted current of 3200 A.
The switch disconnector is rated for operation up to 690 V AC or 250 V DC, with a rated insulation voltage of 1000 V.
4P identifies the four-pole construction, F denotes the fixed installation version and HR identifies the rear flat horizontal terminal arrangement.
The E3V/MS 3200 has a rated short-time withstand current of 85 kA for 1 s and 65 kA for 3 s, with a rated short-circuit making capacity of 187 kA peak.
ABB SACE Emax switch disconnectors provide robust high-current switching and isolation for demanding low-voltage distribution systems, combining proven Emax construction with high short-time withstand capability for industrial switchboards and critical power infrastructure.