1SDA058874R1 ABB SACE Emax E2S/MS 2000 A 4-Pole Fixed Rear Horizontal Switch-Disconnector

1SDA058874R1 ABB SACE Emax E2S/MS 2000 A 4-Pole Fixed Rear Horizontal Switch-Disconnector

ABB 1SDA058874R1 is a 2000 A four-pole fixed SACE Emax E2S/MS switch-disconnector with rear horizontal terminals, a 690 V AC operational rating and 65 kA short-time withstand current for 1 second.

SKU: 1SDA058874R1MPN: 1SDA058874R1
Price
List Price £18,497.67 ex VAT
Your Price (ex VAT) Save 25%
£13,873.25 25% OFF
You save £4,624.42 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,873.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,873.25

Why Choose the ABB 1SDA058874R1 Emax E2S/MS 2000 Switch-Disconnector?

The ABB 1SDA058874R1 is a SACE Emax E2S/MS 2000 four-pole fixed switch-disconnector designed for high-current switching and isolation in low-voltage power distribution systems. Identified as E2S/MS 2000 4P F HR, this configuration combines a 2000 A current rating with fixed installation and rear horizontal terminals.

The E2S/MS configuration is intended for switching and isolation rather than automatic overcurrent protection. Its four-pole arrangement enables simultaneous switching across four conductors, making it suitable for power distribution systems where the neutral conductor also needs to be switched alongside the three phase conductors.

With a rated uninterrupted current of 2000 A, rated operational voltage of 690 V AC and an S short-circuit performance level, the E2S/MS 2000 provides robust electrical withstand characteristics. Its fixed construction and rear horizontal terminals make it particularly suitable for permanent installation in industrial switchboards and high-current distribution assemblies.

Key Advantages

  • Genuine ABB SACE Emax E2S/MS switch-disconnector.
  • 2000 A rated uninterrupted current for high-current power distribution.
  • Four-pole configuration for switching four conductors.
  • Fixed installation for permanent switchboard mounting.
  • Rear horizontal terminals for compatible busbar and conductor arrangements.
  • 690 V AC rated operational voltage.
  • 65 kA short-time withstand current for 1 s.
  • 50 kA short-time withstand current for 3 s.
  • Suitable for use as a main switching and isolation device in compatible installations.
  • Optional voltage release and motor operating accessories support enhanced switchgear functionality.

Key Features

  • ABB SACE Emax E2S/MS 2000 switch-disconnector.
  • 2000 A rated current.
  • Four-pole configuration.
  • Fixed version (F).
  • Rear horizontal terminals (HR).
  • S short-circuit performance level.
  • 690 V AC rated operational voltage.
  • 250 V DC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 65 kA short-time withstand current for 1 s.
  • 50 kA short-time withstand current for 3 s.
  • IP30 front protection rating.
  • Push-button operating mechanism.
  • Lockable mechanical construction.
  • Optional voltage release and motor operation.

High-Current Switching and Isolation with Emax E2S/MS

ABB SACE Emax switch-disconnectors provide controlled switching and isolation in high-current power distribution systems. The /MS configuration is intended for switching and disconnection duties rather than automatic overcurrent protection, allowing the device to form part of a coordinated electrical system where fault protection is provided by other suitable protective equipment.

The E2S/MS 2000 provides a substantial 65 kA short-time withstand current for 1 s and 50 kA for 3 s. Combined with its 2000 A rating, four-pole construction and rear horizontal terminals, this makes the 1SDA058874R1 well suited to permanent installation in high-capacity industrial distribution switchboards.

Typical Applications

  • Industrial low-voltage power distribution systems.
  • Main and sub-main electrical switchboards.
  • Four-pole power switching and isolation.
  • Fixed high-current switchgear assemblies.
  • Transformer secondary distribution systems.
  • High-current feeder isolation.
  • Manufacturing and process industry installations.
  • Commercial and infrastructure power distribution.

Technical Specifications

Series SACE Emax / New Emax
Product group 310513-New Emax
ABB order code 1SDA058874R1
Product type Switch-disconnector
ABB description E2S/MS 2000 4P F HR
Frame / subtype E2
Performance level S
Rated current 2000 A
Rated operational current 2000 A
Rated uninterrupted current 2000 A
Number of poles 4
Version Fixed
Terminal connection Rear horizontal
Current type AC
Rated operational voltage 690 V AC / 250 V DC
Rated voltage 690 V
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Rated short-time withstand current 65 kA for 1 s / 50 kA for 3 s
AC-21 rated current at 400 V 2000 A
Front protection rating IP30
Operating element Push button
Lockable Yes
Integrated motor operator No
Optional motor operator Yes
Optional voltage release Yes
Power loss 180 W
Electrical durability 10,000 cycles
Maximum electrical operating frequency 30 cycles per hour
Mechanical durability 25,000 cycles
Maximum mechanical operating frequency 60 cycles per hour
Standard IEC
Net weight approx. 68 kg
EAN 8015644612276
Minimum order quantity 1 piece
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA058874R1?

The ABB 1SDA058874R1 is a SACE Emax E2S/MS 2000 four-pole fixed switch-disconnector rated at 2000 A and configured with rear horizontal terminals.

What is the rated current of the ABB 1SDA058874R1?

The E2S/MS 2000 has a rated uninterrupted current of 2000 A.

What does 4P F HR mean on the ABB E2S/MS 2000?

4P identifies the four-pole configuration, F identifies the fixed version and HR identifies the rear horizontal terminal arrangement.

Is the ABB 1SDA058874R1 a circuit breaker or a switch-disconnector?

The 1SDA058874R1 is an E2S/MS switch-disconnector designed primarily for high-current switching and electrical isolation rather than automatic overcurrent protection.

What is the short-time withstand current of the ABB E2S/MS 2000?

The E2S/MS 2000 has a rated short-time withstand current of 65 kA for 1 s and 50 kA for 3 s.

Trusted ABB SACE Emax Switching and Isolation

ABB SACE Emax switch-disconnectors provide dependable high-current switching and isolation for industrial power distribution, with the E2S/MS 2000 combining a 2000 A rating, four-pole fixed construction, rear horizontal connections and robust short-time current withstand performance.