ABB 1SDA058683R1 is a 2000 A four-pole fixed SACE Emax E2S air circuit breaker with rear flat horizontal terminals, a PR122/P-LSIRc R2000 electronic overcurrent release, four auxiliary contacts and open/closed position indication.
£15,187.25
The ABB 1SDA058683R1 is a SACE Emax E2S 2000 A four-pole fixed air circuit breaker designed for high-current low-voltage power distribution and circuit protection. It combines the E2S short-circuit performance level with an ABB PR122/P-LSIRc R2000 electronic overcurrent release, providing advanced protection and monitoring for demanding industrial and commercial electrical systems.
This configuration has a rated uninterrupted current of 2000 A, a four-pole construction and a fixed mounting arrangement with rear flat horizontal terminals. The E2S performance level provides rated ultimate and service short-circuit breaking capacities of 85 kA at 400–415 V AC and 65 kA at 500–690 V AC, making it suitable for installations with substantial prospective fault currents.
ABB order code 1SDA058683R1 is equipped with the PR122/P-LSIRc R2000 electronic release and includes four auxiliary contacts with open/closed circuit breaker position indication. The LSIRc release provides Long-time, Short-time and Instantaneous overcurrent protection together with residual-current functionality, supporting comprehensive protection of critical low-voltage distribution circuits.
The ABB SACE Emax E2S platform is engineered for high-current switching and protection in low-voltage distribution systems. With a rated current of 2000 A, an 85 kA short-circuit breaking capacity across 220–440 V AC and a 65 kA capability at 500–690 V AC, the 1SDA058683R1 provides robust protection for switchboards, busbars, feeders and other critical electrical distribution circuits.
The integrated PR122/P-LSIRc electronic release combines Long-time overload, Short-time and Instantaneous short-circuit protection with residual-current functionality. Together with the breaker’s four-pole construction and fixed rear-horizontal connection arrangement, this makes the E2S 2000 suitable for sophisticated power distribution systems requiring high fault-interruption capability and comprehensive electronic protection.
| Series | SACE Emax |
|---|---|
| Extended product type | E2S2000PR122/P-LSIRcIn=2000A4pFHR |
| ABB order code | 1SDA058683R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Sub-type | E2 |
| Short-circuit performance level | S |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 4 |
| Installation | Fixed |
| Terminal connection | Rear flat horizontal |
| Overcurrent release | PR122/P-LSIRc R2000 |
| Release type | Electronic |
| Protection functions | Long-time, Short-time, Instantaneous and residual-current functionality |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Power loss | 180 W |
| Electrical endurance at Ue ≤ 440 V | 10,000 cycles |
| Electrical endurance at Ue 500–690 V | 8,000 cycles |
| Mechanical endurance | 25,000 cycles |
| Current type | AC |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Standards | IEC |
| EAN | 8015644610296 |
| Product net width | 386 mm |
| Product net height | 418 mm |
| Product net depth | 302 mm |
| Product net weight | 56 kg |
| Minimum order quantity | 1 piece |
| Customs tariff number | 85362090 |
The ABB 1SDA058683R1 is a SACE Emax E2S 2000 A four-pole fixed air circuit breaker with rear flat horizontal terminals and a PR122/P-LSIRc R2000 electronic overcurrent release.
The PR122/P-LSIRc electronic release provides Long-time overload, Short-time and Instantaneous short-circuit protection together with residual-current functionality.
The E2S breaker has rated ultimate and service short-circuit breaking capacities of 85 kA at 220–440 V AC and 65 kA at 500–690 V AC.
The 1SDA058683R1 is a fixed four-pole air circuit breaker equipped with rear flat horizontal terminals.
Yes. This E2S 2000 configuration is fitted with four auxiliary contacts and circuit breaker open/closed position indication.
The ABB SACE Emax E2S 2000 combines a 2000 A current rating, high short-circuit performance, four-pole switching and PR122/P-LSIRc electronic protection in a robust fixed air circuit breaker for demanding industrial and commercial low-voltage power distribution.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.