ABB 1SDA058138R1 is a three-pole Tmax T4L 250 UL/CSA moulded-case circuit breaker with a 150 A TMA thermomagnetic trip unit and adjustable 750–1500 A magnetic short-circuit protection.
£1,717.08
The ABB 1SDA058138R1 is a Tmax T4L 250 three-pole moulded-case circuit breaker (MCCB) designed for reliable protection of low-voltage industrial and commercial electrical distribution systems. As part of the ABB Tmax T4–T8 range, this breaker combines the T4 250 frame with a TMA thermomagnetic trip unit and is designed for applications requiring UL/CSA-compliant circuit protection.
The breaker incorporates a TMA adjustable thermomagnetic trip unit, providing thermal overload protection together with magnetic short-circuit protection. Its overload setting is based around a 150 A rating, while the instantaneous magnetic protection is adjustable from 750–1500 A, enabling protection to be coordinated with the requirements of the connected circuit.
The T4L 250 is supplied in a three-pole fixed configuration and is intended for three-phase distribution applications. Its high-performance L breaking-capacity version, adjustable protection and established ABB Tmax construction make the 1SDA058138R1 suitable for switchboards, distribution panels, machinery supplies and industrial feeder protection.
Moulded-case circuit breakers protect electrical conductors and connected equipment against potentially damaging overcurrents. The TMA trip unit in the ABB T4L 250 combines a thermal protection element for sustained overload conditions with an adjustable magnetic element that provides rapid operation during high-current short circuits.
For the 1SDA058138R1, the magnetic protection range of 750–1500 A allows the instantaneous trip threshold to be selected to suit the application. Combined with the robust Tmax T4 platform and three-pole construction, this makes the breaker a practical solution for protecting three-phase feeders, machinery circuits and industrial distribution equipment.
| Series | Tmax T4–T8 |
|---|---|
| Order code | 1SDA058138R1 |
| Product type | Moulded-case circuit breaker (MCCB) |
| Frame | T4 |
| Frame size | 250 A |
| Breaking-capacity version | L |
| Trip unit | TMA thermomagnetic |
| Trip-unit rating | 150 A |
| Magnetic protection setting | 750–1500 A |
| Number of poles | 3 |
| Mounting / execution | Fixed |
| Protection functions | Thermal overload and magnetic short circuit |
| Certification version | UL/CSA |
| ABB product group | 310511-T-Max T4 - T8 |
The ABB 1SDA058138R1 is a three-pole Tmax T4L 250 moulded-case circuit breaker used to provide overload and short-circuit protection in low-voltage electrical distribution systems.
The breaker uses an ABB TMA adjustable thermomagnetic trip unit, combining thermal overload protection with magnetic short-circuit protection.
The TMA trip unit is rated at 150 A and is installed within the T4L 250 circuit-breaker platform.
The instantaneous magnetic protection is adjustable over a range of 750–1500 A, allowing the short-circuit trip threshold to be coordinated with the protected circuit.
The 1SDA058138R1 is a three-pole (3P) circuit breaker designed for applications including three-phase low-voltage distribution systems.
ABB Tmax moulded-case circuit breakers provide dependable overload and short-circuit protection for industrial and commercial electrical distribution systems, combining robust breaker construction with coordinated trip-unit technology and a comprehensive range of installation accessories.