ABB 1SDA057293R1 is a SACE Emax E2B-A three-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LSIG electronic overcurrent release providing long-time, short-time, instantaneous and ground-fault protection.
£9,473.42
The ABB 1SDA057293R1 is a SACE Emax E2B-A air circuit breaker moving part designed for protection and switching in demanding low-voltage power distribution systems. Identified as E2B-A 1600 PR122/P-LSIG In=1600A 3p W, this three-pole withdrawable breaker combines a 1600 A rated current with the ABB PR122/P-LSIG electronic overcurrent release.
Designed as part of the ABB SACE Emax E2 platform, this UL-oriented breaker configuration is suitable for industrial, commercial and infrastructure installations requiring dependable high-current protection. Its withdrawable moving-part construction allows the breaker to be isolated and removed from compatible switchgear, supporting inspection, servicing and replacement in critical power distribution systems.
The integrated PR122/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection. The breaker is also fitted with four auxiliary contacts and open/closed position indication, providing useful status signalling for switchboard monitoring and control applications.
Air circuit breakers such as the ABB SACE Emax E2B-A are used to switch and protect substantial low-voltage electrical loads. When abnormal current conditions occur, the electronic trip unit evaluates the fault against its configured protection settings and initiates circuit interruption when required, helping safeguard switchgear, conductors, transformers, generators and connected electrical equipment.
The PR122/P-LSIG release provides four principal protection functions. Long-time protection responds to sustained overload conditions, short-time protection supports controlled short-circuit response and selective coordination, instantaneous protection provides rapid interruption during severe short circuits, and ground-fault protection detects potentially damaging current flowing to earth.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax |
| Extended product type | E2B-A 1600 PR122/P-LSIG In=1600A 3p W MP |
| ABB order code | 1SDA057293R1 |
| Product type | Air circuit breaker moving part |
| Frame | E2 |
| Performance level | B-A |
| Rated current (In) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated voltage | 600 V |
| Overcurrent release rating | R1600 |
| Instantaneous reference | Im 24000 A |
| Number of poles | 3 |
| Execution | Withdrawable moving part |
| Trip unit | PR122/P-LSIG electronic overcurrent release |
| Protection functions | Long-time, short-time, instantaneous and ground-fault |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Ground-fault protection | G |
| Rated service short-circuit breaking capacity (Ics) | 42 kA at 240 V AC; 42 kA at 480 V AC; 42 kA at 600 V AC |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Current type | AC |
| Release type | Electronic |
| Standard | UL 1066 |
| Electrical durability | 10,000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Mechanical operating frequency | 30 cycles per hour |
| Power loss | 215 W per pole at rated operating conditions |
| Product net width | 324 mm |
| Product net height | 461 mm |
| Product net depth | 396.5 mm |
| Net weight | 49 kg |
| EAN | 8015644595562 |
| HS code | 85362090 |
The ABB 1SDA057293R1 is a 1600 A three-pole SACE Emax E2B-A air circuit breaker moving part used for switching and protecting low-voltage electrical distribution systems against overloads, short circuits and ground faults.
The breaker has a rated current of 1600 A and uses an R1600 electronic overcurrent release configuration.
The 1SDA057293R1 is fitted with an ABB PR122/P-LSIG electronic overcurrent release, providing long-time, short-time, instantaneous and ground-fault protection.
This model is a three-pole withdrawable moving part for compatible SACE Emax switchgear, allowing the breaker to be isolated and removed for inspection, servicing or replacement.
LSIG denotes long-time, short-time, instantaneous and ground-fault protection, providing electronic protection against sustained overloads, short circuits and earth-fault conditions.
ABB SACE Emax air circuit breakers provide dependable switching and electronic overcurrent protection for demanding low-voltage power distribution systems, combining robust breaker construction, comprehensive LSIG protection and maintainable withdrawable designs for industrial, commercial and infrastructure applications.