1SDA057140R1 ABB E6V6300 PR122/P-LSI 6300 A 3-Pole Fixed Air Circuit Breaker

1SDA057140R1 ABB E6V6300 PR122/P-LSI 6300 A 3-Pole Fixed Air Circuit Breaker

ABB 1SDA057140R1 is a SACE Emax E6V6300 three-pole fixed air circuit breaker rated at 6300 A with rear horizontal terminals and a PR122/P-LSI electronic release providing long-time, short-time and instantaneous overcurrent protection.

SKU: 1SDA057140R1MPN: 1SDA057140R1
Price
List Price £94,368.44 ex VAT
Your Price (ex VAT) Save 25%
£70,776.33 25% OFF
You save £23,592.11 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £70,776.33
Trade pricing is personalised to your account

Manufacturer Lead Time

£70,776.33

Why Choose the ABB 1SDA057140R1 E6V6300 Air Circuit Breaker?

The ABB 1SDA057140R1 is a high-performance SACE Emax E6V air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. Identified as E6V6300 PR122/P-LSI In=6300A 3p F, this three-pole fixed circuit breaker combines a 6300 A rated current with the ABB PR122/P-LSI electronic overcurrent release.

As part of the ABB SACE Emax E6V series, the breaker is engineered for high-current installations requiring exceptional short-circuit performance, selective protection and dependable operation. Its fixed construction with rear horizontal terminals enables permanent integration into compatible low-voltage switchboards, while four auxiliary change-over contacts provide circuit breaker open/closed position indication.

The integrated PR122/P-LSI electronic trip unit provides long-time, short-time and instantaneous overcurrent protection. With a rated operational voltage of 690 V AC and a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, the 1SDA057140R1 is suitable for high-capacity industrial, infrastructure and main power distribution applications.

Key Advantages

  • High-performance ABB SACE Emax E6V air circuit breaker for demanding power distribution applications.
  • 6300 A rated current for high-power low-voltage systems.
  • PR122/P-LSI electronic overcurrent release for comprehensive circuit protection.
  • LSI protection provides long-time, short-time and instantaneous protection functions.
  • 150 kA rated ultimate short-circuit breaking capacity at 400 V AC.
  • Three-pole fixed configuration for three-phase electrical distribution systems.
  • Rear horizontal terminals support practical integration into compatible high-current switchboard assemblies.

Key Features

  • ABB SACE Emax E6V6300 air circuit breaker platform.
  • 6300 A rated current.
  • 690 V AC rated operational voltage.
  • Three-pole configuration.
  • Fixed circuit breaker construction.
  • Rear horizontal terminals.
  • PR122/P-LSI electronic overcurrent release.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • 150 kA Icu at 400 V AC, 50 Hz.
  • Four auxiliary change-over contacts.
  • Circuit breaker open/closed position indication.

High-Performance Circuit Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax E6V protect high-current low-voltage distribution systems against overloads and short circuits. When configured protection thresholds are exceeded, the breaker interrupts the affected circuit, helping safeguard switchgear, cables, transformers, generators and connected electrical equipment against potentially damaging fault conditions.

The PR122/P-LSI electronic release provides three principal overcurrent protection functions. Long-time protection responds to sustained overload conditions, short-time protection supports selective coordination between protective devices, and instantaneous protection provides rapid circuit interruption when severe short-circuit currents occur.

Typical Applications

  • Main low-voltage distribution switchboards.
  • High-current industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary distribution.
  • Generator and installation protection systems.
  • High-fault-level switchgear assemblies.
  • Power distribution systems requiring LSI protection and selective coordination.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax
ABB order code 1SDA057140R1
Product type Air circuit breaker
Frame E6
Performance level V
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated voltage 690 V AC
Number of poles 3
Execution Fixed
Terminal connection Rear horizontal
Trip unit PR122/P-LSI electronic overcurrent release
Protection functions Long-time, short-time and instantaneous
Overload release setting range 2520–6300 A
Short-time delayed short-circuit release setting 3780 A
Instantaneous short-circuit release adjustment range 9450–94500 A
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 150 kA
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Integrated earth-fault protection No
Motor drive Optional
Weight approx. 133 kg
EAN 8015644584801
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA057140R1 used for?

The ABB 1SDA057140R1 is a 6300 A three-pole SACE Emax E6V air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems.

What is the rated current of the ABB 1SDA057140R1?

The breaker has a rated current of 6300 A, making it suitable for high-capacity industrial, infrastructure and main power distribution applications.

Which trip unit is fitted to this circuit breaker?

The 1SDA057140R1 is fitted with an ABB PR122/P-LSI electronic overcurrent release, providing long-time, short-time and instantaneous overcurrent protection.

Is the ABB 1SDA057140R1 fixed or withdrawable?

This model is a fixed three-pole circuit breaker with rear horizontal terminals, designed for permanent installation within compatible low-voltage switchgear assemblies.

What is the breaking capacity of the ABB E6V6300?

The E6V6300 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, 50 Hz, making it suitable for electrical systems with high prospective fault currents.

Trusted High-Current Protection from ABB

ABB SACE Emax air circuit breakers provide high-performance protection and switching for demanding low-voltage power distribution systems, combining high current capability, electronic protection and robust fixed construction for industrial and infrastructure applications.