ABB 1SDA057139R1 is a SACE Emax E6V6300 three-pole fixed air circuit breaker rated at 6300 A with rear horizontal terminals and a PR122/P-LI electronic release providing long-time overload and instantaneous short-circuit protection.

SKU: 1SDA057139R1MPN: 1SDA057139R1
Price
List Price £93,600.02 ex VAT
Your Price (ex VAT) Save 25%
£70,200.02 25% OFF
You save £23,400.01 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £70,200.02
Trade pricing is personalised to your account

Manufacturer Lead Time

£70,200.02

Why Choose the ABB 1SDA057139R1 E6V6300 Air Circuit Breaker?

The ABB 1SDA057139R1 is a high-performance SACE Emax E6V air circuit breaker designed for protection and switching in demanding low-voltage power distribution systems. Identified as E6V6300 PR122/P-LI In=6300A 3p FH, this three-pole fixed circuit breaker combines a 6300 A rated current with the ABB PR122/P-LI electronic overcurrent release.

As part of the ABB SACE Emax E6V series, the breaker is engineered for high-current installations requiring exceptional short-circuit performance and dependable circuit protection. Its fixed construction with rear horizontal terminals enables permanent integration into compatible low-voltage switchboards, while four auxiliary change-over contacts provide circuit breaker open/closed position indication.

The integrated PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of up to 150 kA, the 1SDA057139R1 is suitable for high-capacity industrial, infrastructure and main power distribution applications.

Key Advantages

  • High-performance ABB SACE Emax E6V air circuit breaker for demanding power distribution applications.
  • 6300 A rated current for high-power low-voltage systems.
  • PR122/P-LI electronic overcurrent release for overload and short-circuit protection.
  • LI protection provides long-time and instantaneous protection functions.
  • Ultimate short-circuit breaking capacity of up to 150 kA at specified operating voltages.
  • Three-pole fixed configuration for three-phase electrical distribution systems.
  • Rear horizontal terminals support integration into compatible high-current switchboard assemblies.

Key Features

  • ABB SACE Emax E6V6300 air circuit breaker platform.
  • 6300 A rated current.
  • 690 V AC rated operational voltage.
  • Three-pole configuration.
  • Fixed circuit breaker construction.
  • Rear horizontal terminals.
  • PR122/P-LI electronic overcurrent release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 150 kA Icu at 400 V AC.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary change-over contacts with open/closed circuit breaker position indication.

High-Performance Circuit Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax E6V protect high-current low-voltage distribution systems against overloads and short circuits. When configured protection thresholds are exceeded, the breaker interrupts the affected circuit, helping safeguard switchgear, cables, transformers, generators and connected electrical equipment against potentially damaging fault conditions.

The PR122/P-LI electronic release provides long-time and instantaneous protection functions. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid circuit interruption when severe short-circuit currents occur, helping protect high-value electrical distribution equipment.

Typical Applications

  • Main low-voltage distribution switchboards.
  • High-current industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary distribution.
  • Generator and installation protection systems.
  • High-fault-level switchgear assemblies.
  • Power distribution systems requiring high-capacity overload and instantaneous short-circuit protection.

Technical Specifications

Product group 310513-New Emax
Series SACE Emax
ABB order code 1SDA057139R1
Product type Air circuit breaker
Frame E6
Short-circuit performance level V
Rated current (In) 6300 A
Rated uninterrupted current (Iu) 6300 A
Rated operational current (Ie) 6300 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 3
Execution Fixed
Terminal connection Rear flat horizontal
Trip unit PR122/P-LI electronic overcurrent release
Protection functions Long-time and instantaneous
Overload release setting range 2520–6300 A
Instantaneous short-circuit release setting range 9450–94500 A
Rated ultimate short-circuit breaking capacity (Icu) 150 kA at 220–440 V AC; 130 kA at 500 V AC; 100 kA at 660–690 V AC
Rated service short-circuit breaking capacity (Ics) 150 kA at 220–415 V AC; 125 kA at 440 V AC; 100 kA at 500–690 V AC
Rated short-time withstand current (Icw) 100 kA for 1 s; 85 kA for 3 s
Power loss 650 W
Electrical durability 2000 cycles at Ue ≤ 440 V; 1500 cycles at Ue 500–690 V
Mechanical durability 12,000 cycles
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Current type AC
Release type Electronic
Standard IEC
Weight approx. 133 kg
EAN 8015644584795
HS code 85362090

Frequently Asked Questions

What is the ABB 1SDA057139R1 used for?

The ABB 1SDA057139R1 is a 6300 A three-pole SACE Emax E6V air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems.

What is the rated current of the ABB 1SDA057139R1?

The breaker has a rated current of 6300 A, making it suitable for high-capacity industrial, infrastructure and main power distribution applications.

Which trip unit is fitted to this circuit breaker?

The 1SDA057139R1 is fitted with an ABB PR122/P-LI electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection.

Is the ABB 1SDA057139R1 fixed or withdrawable?

This model is a fixed three-pole circuit breaker with rear horizontal terminals, designed for permanent installation within compatible low-voltage switchgear assemblies.

What is the breaking capacity of the ABB E6V6300?

The E6V6300 provides an ultimate short-circuit breaking capacity of up to 150 kA, with the applicable value depending on the system operating voltage.

Trusted High-Current Protection from ABB

ABB SACE Emax air circuit breakers provide high-performance protection and switching for demanding low-voltage power distribution systems, combining high current capability, electronic protection and robust fixed construction for industrial and infrastructure applications.